S10 · Lesson 1 · The power system and complex power
How electricity gets from generators to loads, why transmission runs at hundreds of kilovolts, balanced three-phase power, complex power and power factor, and correcting power factor with capacitors
The interconnected grid is the largest machine people have built: thousands of generators spinning in lockstep at 60 Hz across a continent, feeding millions of loads through lines that run at up to 765 kV. Everything in this course, from the per-unit system to power flow, fault currents and stability, is a tool for predicting how that machine behaves and keeping it running. This lesson lays out its structure and the quantity that every power engineer reasons in: complex power.
- The loss on a three-phase line with 10 Ω per phase carrying 100 MW at 0.95 power factor, against the line-to-line voltage.
- Loss goes as , and for a fixed power the current goes as 1/V, so the loss falls as : 23% of the power at 69 kV, under 1% at 345 kV.
- That's the whole reason for transmission voltages: doubling the voltage cuts the loss to a quarter, for the same conductors.
Predict
A utility moves a line from 138 kV to 345 kV, carrying the same 100 MW on the same conductors. What happens to the line's resistive loss?
The current falls by 345/138 = 2.5 times, and the loss goes as the current squared: (2.5)² = 6.25 times less, from 5.82 MW to 0.93 MW. The price is bigger insulators, taller towers and wider rights-of-way.
Name it
Structure
Generators produce power at 13.8 to 25 kV. Step-up transformers raise it to transmission voltages (115, 138, 230, 345, 500 and 765 kV in North America), substations step it down to subtransmission (34.5 to 138 kV) and distribution (4 to 35 kV), and pole or pad transformers deliver 120/240 V or 480 V. All of it is three-phase except the last few hundred meters to homes.
Balanced three-phase power
A balanced system is analyzed one phase at a time, line to neutral. With line-to-line voltage and line current :
where φ is the angle by which the current lags the voltage. The line-to-neutral voltage is .
Complex power
For one phase with phasors V and I, . P (watts) is the average power; Q (vars) measures energy sloshing back and forth, positive for inductive loads that absorb it. Power factor is , lagging for inductive loads.
Power-factor correction
Shunt capacitors supply vars locally so the line doesn't have to carry them. To raise a load P from power factor to :
Less reactive current means less line loss, less voltage drop and more capacity for real power.
Worked example
A plant draws 50 MW at 0.8 power factor lagging. How large a capacitor bank brings it to 0.95?
Show the solution
- Reactive power now. At 0.8 power factor: and |S| = 62.5 MVA.
- Reactive power at 0.95.
- Bank size. The bank must supply the difference:
- What it saves. The apparent power falls to 52.6 MVA, so the line current falls by 16% and the line loss by 29%.
Answer a 21.1 Mvar bank, which cuts the line current by 16% and the line loss by 29%.
Worked example
A 20 MVA generator runs at 13.8 kV. What's its rated current?
Show the solution
- Rated current. per phase.
- Why so modest a voltage. Generators are built at modest voltages because insulating a rotating winding is hard; the step-up transformer next to the generator takes the voltage up to transmission level.
Answer 837 A per phase.
Worked example
A balanced Δ-connected load has 30 + j40 Ω in each phase and sits across a 480 V three-phase supply. Find its current, its complex power and its power factor.
Show the solution
- Phase current. Each phase sees the full 480 V line voltage across |Z| = 50 Ω: The line current is √3 times that, 16.6 A.
- Power per phase.
- All three phases. Three phases give 8.29 kW and 11.06 kvar, 13.82 kVA in all.
- Power factor. lagging.
Answer 9.6 A in each phase (16.6 A in each line), a complex power of 8.29 kW + j11.06 kvar (13.82 kVA), and a power factor of 0.6 lagging.
Check
A three-phase line carries 200 MW at 69 kV, power factor 0.95. What's the line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A line with 15 Ω per phase carries 100 MW at 138 kV and 0.95 power factor. What fraction of the power is lost in it?
Check
A load takes 40 MW at 0.7 power factor lagging. How many vars does it absorb?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
How much capacitive compensation raises a 30 MW load from 0.7 to 0.98 power factor?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
One phase carries 100 A at 13.8 kV line to neutral, with the current lagging the voltage by 60°. What real power does that phase carry?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A line's voltage is raised from 115 kV to 230 kV for the same power and conductors. By what factor does the resistive loss fall?
Check
A balanced Y-connected load of 8 + j40 Ω per phase is supplied at 480 V line to line.
(a)
What is the line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What real power does it take?
(c)
At what power factor?
Check
A balanced Δ load has impedance of magnitude Z and angle a (radians) per phase, across line voltage V.
Step 1
What is the phase current?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is the total apparent power?
Step 3
And the real power?
Explain why
Why does a load with poor power factor cost the utility money even though reactive power does no net work?
A load with poor power factor draws more current for the same real power, because part of its current is out of phase with the voltage and just shuttles energy back and forth each cycle. The utility's generators, transformers and lines must still carry that extra current, so they heat up as if they were delivering more power, the line loss grows with the square of the current, and the voltage drop along the lines grows too. Equipment is sized by current and apparent power, not real power, so the reactive part uses up capacity that could otherwise sell real energy. That's why industrial customers pay for low power factor and install capacitors to supply their vars locally.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.