S10 · Lesson 7 · Power transfer and voltage
Real power flow set by the angle across a line, reactive power flow set by voltage magnitudes, the voltage-drop approximation, the steady-state transfer limit, and the nose curve that marks voltage collapse
Two facts govern how power moves on a grid. Real power flows from the bus whose voltage leads to the one that lags, in proportion to the sine of the angle between them. Reactive power flows from the higher voltage magnitude to the lower. Almost everything an operator does follows from these: generators push real power by advancing their rotors, capacitors and generators hold voltages up by supplying vars, and a line asked to carry too much reaches a point where the voltage at its end collapses.
- The nose curve of a lossless line: the receiving-end voltage against the power delivered, with the sending end held at 1 pu, for series reactance X and a load whose Q/P ratio you set.
- At light load the voltage barely falls. Push P up and the voltage drops faster and faster until the curve turns back at the nose: no more power can be delivered, and the lower branch is unstable.
- A lagging load (positive Q/P) lowers the nose; a leading one (negative Q/P, local capacitors) raises it.
Predict
Two buses at 1 pu are joined by a line of reactance 0.5 pu, with bus 1 leading by 30°. How much real power flows, and who supplies the line's vars?
= sin 30°/0.5 = 1 pu. Each end sends = 0.268 pu of vars into the line, which absorbs = 0.536 pu in its reactance. With equal voltage magnitudes, the var demand splits evenly.
Name it
Flow on a lossless line
For buses at and joined by reactance X, with :
Real power follows angle; it peaks at at δ = 90°, the steady-state stability limit. Reactive power follows voltage magnitude: with small δ, .
Voltage drop
On a line with R + jX carrying P + jQ to a bus at about 1 pu,
On transmission lines X ≫ R, so voltage is controlled by reactive power; on distribution feeders R matters too.
The nose curve
With the sending end at and a load P + jQ at the receiving end,
Real solutions exist only up to a maximum P. At unity power factor that's , reached at . Lagging loads lower it; local var support raises it. Operating near the nose risks voltage collapse, which caused major blackouts in France in 1978 and Tokyo in 1987.
Worked example
A line of X = 0.5 pu from a 1 pu source feeds a unity-power-factor load. What's the receiving voltage at 0.8 pu load, and how much can it deliver at most?
Show the solution
- Receiving voltage at 0.8 pu. From the nose-curve formula with Q = 0: so = 0.894 pu.
- Maximum power. at = 0.707.
- At 0.9 power factor lagging. The maximum falls to 0.627 pu, at a voltage of only 0.59 pu.
Answer = 0.894 pu at 0.8 pu of load, and the line can deliver at most 1 pu (at 0.707 pu voltage).
Worked example
A feeder has R = 0.02 pu and X = 0.1 pu and carries 0.8 + j0.4 pu. Estimate the voltage drop.
Show the solution
- Estimate the drop. which is 5.6%.
- Where it comes from. Most of it, 4 of the 5.6 points, comes from the reactive power.
- Supply the vars locally. A capacitor supplying 0.4 pu at the load would cut the drop to 1.6%.
Answer about 0.056 pu, a 5.6% drop.
Worked example
A 1 pu source feeds a load through X = 0.5 pu. How much power can it deliver at unity power factor, at 0.9 lagging and at 0.9 leading?
Show the solution
- The limit. For a load of power factor angle φ the maximum, at the nose of the P–V curve, is
- Unity power factor.
- 0.9 lagging. Here sin φ = 0.436:
- 0.9 leading. Here sin φ = −0.436:
- Why lagging loads are worst. Lagging loads drain vars from the line and collapse the voltage sooner, which is why reactive support sets how much a weak line can carry.
Answer 1.0 pu at unity power factor, 0.63 pu at 0.9 lagging and 1.60 pu at 0.9 leading.
Check
Buses at 1 pu and 0.98 pu are joined by X = 0.5 pu, with a 40° angle between them. How much real power flows?
Check
Two 1 pu buses joined by X = 0.15 pu must transfer 0.6 pu. What angle does that take?
Check
Bus 1 at 1 pu leads bus 2 at 0.95 pu by 30° across X = 0.4 pu. How much reactive power leaves bus 1 into the line?
Check
A line with R = 0.01, X = 0.08 pu carries 1 + j0.4 pu. Estimate the voltage drop.
Check
A source of 1 pu feeds a unity-power-factor load through X = 0.25 pu. What's the most power it can deliver?
Check
A 1 pu source feeds 0.4 pu at unity power factor through X = 0.2 pu. What's the receiving voltage (upper branch)?
Check
A source of 1 pu feeds a load at power factor 0.95 lagging through X = 0.2 pu.
(a)
What is the most real power it can deliver?
(b)
And at unity power factor?
Check
Buses at V and W pu, with V leading by d radians, are joined by reactance X.
Step 1
What real power flows from V to W?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What reactive power leaves the first bus?
Step 3
What reactive power leaves the second bus?
Explain why
Why does real power follow voltage angle while reactive power follows voltage magnitude on a transmission line?
A transmission line is mostly reactance, so the current through it is the voltage difference across it divided by jX, which turns it 90° from that difference. When the two ends differ mainly in angle, the difference phasor is nearly perpendicular to the bus voltages, and the current it drives through jX comes out nearly in phase with them: real power. When they differ mainly in magnitude, the difference points along the voltages, and the current comes out 90° behind them: reactive power. That decoupling is why operators control real power flows with generator output and angles, and voltages with vars, nearly independently.