S10 Power system analysis · Practice
Every topic, mixed
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Topics: all 52
Check
A three-phase line carries 200 MW at 69 kV, power factor 0.95. What's the line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A line with 15 Ω per phase carries 100 MW at 138 kV and 0.95 power factor. What fraction of the power is lost in it?
Check
A load takes 40 MW at 0.7 power factor lagging. How many vars does it absorb?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
How much capacitive compensation raises a 30 MW load from 0.7 to 0.98 power factor?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
One phase carries 100 A at 13.8 kV line to neutral, with the current lagging the voltage by 60°. What real power does that phase carry?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A line's voltage is raised from 115 kV to 230 kV for the same power and conductors. By what factor does the resistive loss fall?
Check
A balanced Y-connected load of 8 + j40 Ω per phase is supplied at 480 V line to line.
(a)
What is the line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What real power does it take?
(c)
At what power factor?
Check
Line current: 30 MW, 34.5 kV, pf 0.98?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Capacitor to raise 2 MW from 0.65 to 1 pf?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
Apparent power of 15 MW at pf 0.75?
Write units the way you normally would: 1.5 MVA, 1500 kVA and 0.0015 GVA are the same answer.
Check
What's the base impedance at 13.8 kV on a 10 MVA base?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
What's the base current at 34.5 kV on 10 MVA?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Equipment rated 25 MVA at 13.2 kV has X = 0.15 pu on its rating. What is it on 100 MVA at 14.4 kV?
Check
A 115 kV line has a series reactance of 40 Ω. What is it in per unit on 100 MVA?
Check
A 4.16/138 kV transformer has X = 0.05 pu on 100 MVA. How many ohms is that seen from the 138 kV side?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A source of 1 pu behind a total of 0.6 pu (100 MVA base) is shorted. What's the current in kA at 13.8 kV?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A load takes 10 MW at power factor 0.8 and its rated 69 kV. Work on a 100 MVA base.
(a)
What is its current in per unit, at 1 pu voltage?
(b)
What is that in amperes?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Base impedance at 69 kV, 10 MVA?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
0.1 pu on 30 MVA, 22 kV to 100 MVA, 24 kV?
Check
10 Ω at 69 kV in pu on 100 MVA?
Check
A short-circuit test reads 489 V, 2.5 A and 300 W. What's the leakage reactance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A transformer with R = 0.005 pu and X = 0.04 pu runs at full load, power factor 0.9 lagging. What's its exact regulation?
Check
A 100 kVA two-winding transformer is reconnected as a 115/230 kV autotransformer. What's its new rating?
Write units the way you normally would: 1.5 kVA, 1500 VA and 0.0015 MVA are the same answer.
Check
A Y-connected bank of single-phase units serves a 230 kV line. What voltage does each unit's winding see?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
Check
A transformer rated 15 kW (unity power factor) runs at 0.75 of full load, with core loss 100 W and full-load copper loss 600 W. What's its efficiency?
Check
A regulator covers ±10% in 16 equal steps. What's one step?
Check
A 100 kVA transformer has 0.2% core loss and 3% copper loss at full load, both relative to its rating.
(a)
At what fraction of full load is it most efficient?
(b)
What efficiency does it reach there, at unity power factor?
(c)
What is the copper loss at that load?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
Winding resistance from a test at 120 V, 4 A, 900 W?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
Approximate regulation: R = 0.008, X = 0.05, pf 0.95 lagging?
Check
Autotransformer rating: 25 kVA winding, 12/13.8 kV?
Write units the way you normally would: 1.5 kVA, 1500 VA and 0.0015 MVA are the same answer.
Check
Phase spacings are 7, 5 and 15 m. What's the geometric mean distance?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
Check
A transposed line has = 8 m and conductor GMR 8 mm. What's its inductance per kilometer?
Write units the way you normally would: 1.5 mH, 1500 µH and 0.0015 H are the same answer.
Check
A two-conductor bundle uses conductors of GMR 8 mm spaced 0.3 m. What's its effective GMR?
Write units the way you normally would: 1.5 mm, 1500 µm and 0.0015 m are the same answer.
Check
A line has = 9 m and conductor radius 10 mm. What's its capacitance to neutral per kilometer?
Write units the way you normally would: 1.5 nF, 1500 pF and 0.0015 µF are the same answer.
Check
A 500 kV line has L = 1 mH/km and C = 9 nF/km. What's its surge impedance loading?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A line of solid round conductors, radius 10 mm, has = 5 m. What's its 60 Hz series reactance per km?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A line has a geometric mean distance of 12 m, effective bundle GMR 0.1 m and effective radius 0.18 m, at 500 kV.
(a)
What is its inductance per kilometer?
Write units the way you normally would: 1.5 mH/km, 1500 µH/km and 0.0015 H/km are the same answer.
(b)
What is its surge impedance?
(c)
What is its SIL?
Check
GMD for spacings 3, 6, 18 m?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
Check
L per km for = 6 m, = 10 mm?
Write units the way you normally would: 1.5 mH, 1500 µH and 0.0015 H are the same answer.
Check
C per km for = 5 m, r = 12 mm?
Write units the way you normally would: 1.5 nF, 1500 pF and 0.0015 µF are the same answer.
Check
A three-phase line (12 Ω per phase) carries 80 MW at 115 kV, power factor 0.95.
(a)
Line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Line loss?
(c)
Vars carried?
Check
An 8 MW load at 0.7 power factor lagging, corrected to 0.97.
(a)
Capacitor needed?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(b)
Percentage cut in line loss?
Check
Bases of 10 MVA and 34.5 kV.
(a)
Base impedance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
Base current?
Check
A machine rated 20 MVA, 13.2 kV with X = 0.08 pu; a 138 kV line of 20 Ω. System base: 100 MVA, 14.4 kV on the machine's side.
(a)
Machine's X on the system base?
(b)
Line in per unit?
Check
A generator (X'' = 0.25 pu) and transformer (X = 0.08 pu) feed a 345 kV line of j120 Ω, all on 100 MVA. A three-phase short occurs at the line's far end.
(a)
Fault current in per unit?
(b)
In kA on the line?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A 25 kVA transformer's short-circuit test on its 13800 V side reads 350 V, 3 A and 400 W.
(a)
Per-unit resistance?
(b)
Per-unit reactance?
Check
A transformer with R = 0.006 pu, X = 0.05 pu at full load.
(a)
Regulation at 0.9 lagging?
(b)
Regulation at 0.9 leading?
Check
A 40 kVA transformer rewired as an autotransformer from 66 kV to 66 + 33 kV; and an 80 kW transformer with core loss 120 W and full-load copper loss 300 W, at 0.6 of full load.
(a)
Autotransformer rating?
Write units the way you normally would: 1.5 kVA, 1500 VA and 0.0015 MVA are the same answer.
(b)
Second transformer's efficiency?
Check
Phases spaced 5, 6 and 16 m; two-conductor bundles 0.4 m apart with conductor GMR 12 mm.
(a)
GMD?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
(b)
Bundle GMR?
(c)
Inductance per km?
Check
Two-conductor bundles 0.6 m apart, conductor radius 12 mm, = 6 m.
(a)
Capacitance per km?
Write units the way you normally would: 1.5 nF, 1500 pF and 0.0015 µF are the same answer.
(b)
Capacitance per km without bundling?
Check
A 765 kV line with L = 0.85 mH/km and C = 9.5 nF/km.
(a)
Surge impedance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
SIL?
Check
A line's voltage rises from 69 kV to 2 times that; separately, a Y bank serves 500 kV.
(a)
Factor by which the loss falls?
(b)
Voltage across each Y unit?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
Check
A balanced Δ load has 12 + j32 Ω per phase across 480 V.
(a)
What is the line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
How many vars does it absorb?
Check
A 100 kVA transformer has 0.15% core loss and 2% full-load copper loss.
(a)
At what load is it most efficient?
(b)
What is its full-load efficiency at unity power factor?
Check
A 10 MW load at power factor 0.8 runs at its rated 13.8 kV. Use a 100 MVA base.
(a)
What is its current in per unit?
(b)
And in amperes?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
An open overhead line 300 km long (wavelength 4940 km). What's its receiving-end voltage relative to the sending end?
Check
A lossless line has L = 1.1 mH/km and C = 9 nF/km. What's its phase constant per km at 60 Hz?
Check
A 345 kV line with B = 3 µS/km is 200 km long. About how many vars does its capacitance generate at rated voltage?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A lossless line with x = 0.3 Ω/km and b = 3 µS/km is 250 km long. What's its nominal-π A constant?
Check
A lossless 400 km line (wavelength 4940 km) carries a resistive load of 0.5 times its SIL. What's the receiving voltage in per unit of the sending voltage?
Check
A short line with Z = 1 + j8 Ω delivers 20 MW at unity power factor and 34.5 kV. How much higher must the sending voltage be?
Check
A lossless overhead line is 400 km long (wavelength 4940 km).
(a)
What is its exact A constant?
(b)
What does the nominal π give?
(c)
How far does the open far end rise, as a multiple of the sending voltage?
Check
Ferranti rise of a 400 km open line?
Check
Charging vars: 230 kV, 3.5 µS/km, 300 km?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
Wavelength at 60 Hz for L = 0.9 mH/km, C = 10 nF/km?
Write units the way you normally would: 1.5 km and 1500 m are the same answer.
Check
Buses at 1 pu and 0.98 pu are joined by X = 0.5 pu, with a 40° angle between them. How much real power flows?
Check
Two 1 pu buses joined by X = 0.15 pu must transfer 0.6 pu. What angle does that take?
Check
Bus 1 at 1 pu leads bus 2 at 0.95 pu by 30° across X = 0.4 pu. How much reactive power leaves bus 1 into the line?
Check
A line with R = 0.01, X = 0.08 pu carries 1 + j0.4 pu. Estimate the voltage drop.
Check
A source of 1 pu feeds a unity-power-factor load through X = 0.25 pu. What's the most power it can deliver?
Check
A 1 pu source feeds 0.4 pu at unity power factor through X = 0.2 pu. What's the receiving voltage (upper branch)?
Check
A source of 1 pu feeds a load at power factor 0.95 lagging through X = 0.2 pu.
(a)
What is the most real power it can deliver?
(b)
And at unity power factor?
Check
Power across X = 0.1 pu at 5°, both buses at 1 pu?
Check
Voltage drop for 0.9 + j0.6 on 0.03 + j0.05?
Check
Unity-pf transfer limit through X = 0.4 pu from 1 pu?
Check
A line of X = 0.5 pu between 1 pu buses gets 0.25 series compensation. What's its new transfer limit?
Check
A 50 Mvar capacitor bank sees its bus sag to 0.7 pu. What does it supply?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A 50 Mvar STATCOM at rated current sees its bus sag to 0.7 pu. What does it supply?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A 40 Mvar shunt bank is switched in at a bus with a 500 MVA short-circuit level. Estimate the voltage change.
Check
A line of X = 0.4 pu joins buses at 1 pu, and its midpoint voltage is held at 1 pu too. What's its transfer limit?
Check
What series compensation lets a line of X = 0.4 pu between 1 pu buses reach a 3 pu transfer limit?
Check
A 345 kV line 300 km long has a shunt susceptance of 3 µS/km.
(a)
How many vars does it generate at rated voltage?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(b)
What shunt reactor rating compensates 0.7 of it?
Check
Transfer limit of X = 0.25 with 0.3 compensation?
Check
Output of a 30 Mvar capacitor at 0.75 pu?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
Voltage change from 15 Mvar at a 400 MVA bus?
Check
An overhead line has L = 1 mH/km and C = 9 nF/km. What's its surge impedance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
How long does a surge take to travel 200 km along a line with L = 0.9 mH/km and C = 12 nF/km?
Write units the way you normally would: 1.5 µs, 1500 ns and 0.0015 ms are the same answer.
Check
A line with = 300 Ω ends in 200 Ω. What's the voltage reflection coefficient there?
Check
A 600 kV surge arrives at a substation bus where the line continues into 2 other lines, all with the same surge impedance. What voltage leaves along each of them?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
Check
A 20 kA stroke hits a phase conductor of a line with = 300 Ω. What's the voltage of the surge on each side?
Write units the way you normally would: 1.5 MV, 1500 kV and 0.0015 GV are the same answer.
Check
A 1 pu source with 100 Ω of internal resistance is switched onto an unloaded line with = 300 Ω. What's the far end's voltage, in per unit, when the first wave arrives?
Check
A rectifier has 200 kV RMS on its valve side, fires at α = 10° and carries 3 kA through = 12 Ω. What's its DC voltage?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
Check
Equipment with a BIL of 1050 kV is protected by an arrester clamping at 900 kV; surges rise at 2000 kV/µs and travel at 300 m/µs. A margin of 1.15 is wanted.
(a)
How far from the equipment may the arrester be?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
Check
for L = 0.73 mH/km, C = 12 nF/km?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
Reflection coefficient: = 40 Ω into 93 Ω?
Check
A 230 kV surge on a 320 Ω line meets a 50 Ω cable. What enters the cable?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
Check
Rectifier: 170 kV, α = 7.1°, = 12 Ω, = 2.8 kA. ?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
Check
Travel time over 110 km at 170 km/ms?
Write units the way you normally would: 1.5 µs, 1500 ns and 0.0015 ms are the same answer.
Check
Bus 1 has lines of reactance j\given0.1 and j\given0.08 pu and a generator of j\given0.3 pu to its source. What's the magnitude of the susceptance in ?
Check
A line has series reactance j\given0.08 pu and total charging susceptance 0.04 pu. What net susceptance magnitude does it add to each end's diagonal?
Check
A transformer of reactance j\given0.05 pu has an off-nominal tap a = 0.95 on bus i's side. What's the magnitude of ?
Check
A generator (j\given0.1) at bus 1 feeds bus 3 directly through j\given0.1 and through bus 2 by j\given0.3 then j\given0.4. What's ?
Check
A bus has = j0.15 pu and prefault voltage 0.95 pu. What's its bolted three-phase fault current?
Check
In a 10000-bus network each bus connects to 3 others on average. About how many nonzero entries does have?
Check
Two buses are joined by j0.1 pu, and each has a generator of j0.2 pu to ground.
(a)
What is ?
(b)
What is the bolted-fault current at bus 1, from 1 pu?
(c)
What voltage does bus 2 hold during that fault?
Check
for branches j\given0.04, j\given0.1 and a generator j\given0.35?
Check
Net diagonal susceptance from a line j\given0.03 with charging 0.1?
Check
Fault current at a bus with = j0.05, = 0.98?
Check
A susceptance matrix has = −6, = −3, = −4 and = 14. Eliminating bus k, what does become?
Check
A bus with no load or generation sits between two lines of j0.1 and j0.08 pu and nothing else. Eliminating it by Kron reduction leaves one branch. What's its reactance, in per unit?
Check
A new bus p is connected to existing bus k ( = j0.25 pu) through a branch of j0.1 pu. What's the new , in per unit?
Check
A generator of j0.2 pu is connected at bus k, where was j0.25 pu. What's the new , in per unit?
Check
A line of j0.4 pu is added between existing buses j and k, where = j0.25, = j0.35 and = j0.2. What's the new , in per unit?
Check
A hub bus connects to 10 buses that aren't connected to each other. Eliminating the hub first, how many fill-in entries appear (counting each new branch once)?
Check
A network has 5000 buses and 1.4 times as many branches. What percentage of its entries are nonzero?
Check
A load-free hub connects to three otherwise unconnected buses through j0.1, j0.1 and j0.5 pu. Eliminate it.
(a)
What reactance joins the first two buses?
(b)
And the second and third?
Check
Eliminate the middle bus of j0.063 and j0.028 in series. The equivalent reactance?
Check
= j0.12; add j0.074 from bus k to the reference. New ?
Check
Rule 4: = 0.27, = 0.32, = 0.12, new line 0.56. New ?
Check
Fill-in from eliminating a hub with 23 unconnected neighbors?
Check
An overhead line 350 km long (wavelength 4940 km), 230 kV, B = 5.5 µS/km.
(a)
Open-end voltage rise factor?
(b)
Charging vars at rated voltage?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A lossless line, L = 0.9 mH/km, C = 9.5 nF/km, 450 km, loaded resistively at 1.4 times SIL.
(a)
Electrical length βl?
(b)
Receiving voltage relative to sending?
Check
A medium line: x = 0.35 Ω/km, b = 3.5 µS/km, 220 km, lossless.
(a)
Nominal-π A?
(b)
No-load ?
Check
Buses at 0.97 and 0.95 pu, angle 30° apart, across X = 0.4 pu.
(a)
Real power?
(b)
Reactive power leaving bus 1?
(c)
Steady-state transfer limit?
Check
A 1 pu source feeds a unity-pf load of 0.3 pu through X = 0.2 pu; separately, a feeder R = 0.06, X = 0.2 carries 0.3 + j0.35 pu.
(a)
Receiving voltage on the upper branch?
(b)
Maximum deliverable power at unity pf?
(c)
Feeder voltage drop estimate?
Check
A line of X = 0.3 pu between 1 pu buses, with 0.3 series compensation, carries 1.5 pu.
(a)
Transfer limit?
(b)
Angle needed?
(c)
Angle without compensation?
Check
A 25 Mvar capacitor and a 25 Mvar STATCOM at a bus of 4000 MVA short-circuit level.
(a)
Capacitor's output at 0.8 pu?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(b)
STATCOM's output at 0.8 pu?
(c)
Voltage rise when the capacitor is switched on at 1 pu?
Check
A line of X = 0.3 pu between buses held at 0.98 pu.
(a)
Transfer limit?
(b)
Limit with the midpoint held at 0.98 pu?
Check
Bus 1 has lines of j\given0.06 and j\given0.1 pu (the first with total charging 0.3 pu) and a generator of j\given0.25.
(a)
ignoring charging?
(b)
Including the first line's charging?
(c)
Off-diagonal magnitude to the first line's far bus?
Check
A transformer j\given0.06 pu with tap a = 0.95 on bus i's side.
(a)
Its contribution to ?
(b)
?
Check
Generator j\given0.12 at bus 1; bus 3 fed directly by j\given0.15 and via bus 2 by j\given0.2 + j\given0.5. Prefault 1 pu.
(a)
?
(b)
Fault current at bus 3?
Check
A 2000-bus network with 2.5 connections per bus on average.
(a)
Nonzeros in ?
(b)
Fraction of entries that are nonzero?
Check
A 600 kV surge on an overhead line ( = 350 Ω) enters a substation through a short cable ( = 50 Ω) that ends at an open breaker.
(a)
Voltage entering the cable?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
(b)
Voltage at the open breaker when that wave first arrives?
(c)
Reflection coefficient, at the cable–line junction, for the wave returning up the cable?
Check
A rectifier has 220 kV RMS on its valve side, fires at α = 12° and carries 2.5 kA through = 12 Ω.
(a)
Ideal no-load DC voltage ?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
(b)
DC voltage at this operating point?
(c)
Power sent by this pole?
Check
Build branch by branch: a generator of j0.1 pu at bus 1, a line of j0.1 from bus 1 to new bus 2, a line of j0.25 from bus 1 to new bus 3, then a line of j0.4 between buses 2 and 3.
(a)
before the 2–3 line is added, in per unit?
(b)
after the 2–3 line, in per unit?
(c)
Bolted three-phase fault current at bus 3, in per unit?
Check
Bus 2 has no load or generation and connects only to bus 1 (j0.05 pu) and bus 3 (j0.1 pu). Buses 1 and 3 are also joined directly by j0.3 pu. Bus 2 is eliminated by Kron reduction.
(a)
Magnitude of the reduced network's susceptance between buses 1 and 3?
(b)
Equivalent reactance between buses 1 and 3, in per unit?
Check
A conductor of diameter 28.1 mm with 0.05 Ω/km at its 100 °C limit sits in 25 °C air with h = 30 W/m²K, ε = α = 0.5 and 1000 W/m² of sun.
(a)
What net cooling is available per meter at the limit?
Write units the way you normally would: 1.5 W/m, 1500 mW/m and 0.0015 kW/m are the same answer.
(b)
What is its ampacity?
Check
A span of 150 m has conductor weighing 16 N/m at a horizontal tension of 50 kN.
(a)
What is its sag?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
(b)
How much longer than the span is the conductor?
Check
A span of 300 m sags 4 m. Its ACSR conductor ( = 19 × 10⁻⁶ per °C) heats by 80 °C; ignore elastic stretch.
(a)
How much longer does it get?
Write units the way you normally would: 1.5 cm, 15 mm and 0.015 m are the same answer.
(b)
What is the new sag?
Check
A conductor at its limit loses 50 W/m by convection and 10 W/m by radiation and gains 15 W/m from the sun. The wind then multiplies convection by 3.
(a)
By what factor does its ampacity rise?
Check
A conductor's resistance is 0.06 Ω/km at 20 °C, rising 0.0039 per °C.
(a)
What is it at 100 °C?
Write units the way you normally would: 1.5 Ω/km, 1500 mΩ/km and 0.0015 kΩ/km are the same answer.
Check
A conductor has 1.6 kg/m of mass with specific heat 900 J/kg·K, and its net cooling rises 4 W/m per kelvin near its operating point.
(a)
What is its thermal time constant?
Check
Sag: 10 N/m, span 200 m, tension 40 kN?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
Check
Ampacity factor when convection 40 W/m rises 2-fold (radiation 15, sun 12)?
Check
Resistance at 75 °C if 0.07 Ω/km at 20 °C, 0.004 per °C?
Write units the way you normally would: 1.5 Ω/km, 1500 mΩ/km and 0.0015 kΩ/km are the same answer.
Check
A source of 1 pu feeds a load at power factor 0.95 lagging through X = 0.1 pu.
(a)
What is the maximum load?
(b)
What is the critical voltage at the nose?
Check
A 1 pu source feeds 1 pu at power factor 0.95 lagging through X = 0.1 pu.
(a)
What is the load voltage?
(b)
What is the loadability margin?
Check
A 1 pu source feeds 1 pu at unity power factor through X = 0.05 pu.
(a)
What is the bus's reactive margin?
(b)
At what voltage is the Q–V curve's minimum?
Check
A tap changer raises a load bus by 5%; the load's power varies as with n = 1.
(a)
By how much does the load's power rise?
Check
A load's power factor angle is −15° (negative is leading), fed from 1 pu.
(a)
What is the critical voltage at the nose?
Check
A 50 Mvar capacitor bank is switched at a bus whose short-circuit level is 2000 MVA.
(a)
Roughly how much does it raise the voltage?
(b)
If the voltage then sagged by that same fraction, how much of its output would the capacitor lose?
Check
Maximum load through X = 0.2 pu at pf 0.9 lagging, from 1 pu?
Check
Critical voltage at pf 0.8 lagging?
Check
Reactive margin: P = 0.8, X = 0.1, unity pf?
Check
A conductor of diameter 28 mm with 0.06 Ω/km at 100 °C is rated in 35 °C air with h = 20 W/m²K, ε = α = 0.5 and 900 W/m² of sun.
(a)
What is its ampacity?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What share of the cooling is convective?
Check
At its rating a conductor sheds 60 W/m by convection and 12 W/m by radiation and absorbs 15 W/m of sun. The wind changes convection by a factor of 3.
(a)
What fraction of its static rating may it now carry?
Check
A span of 250 m carries a conductor of 16 N/m at 35 kN tension; it then heats by 70 °C ( = 19 × 10⁻⁶/°C, ignore elastic stretch).
(a)
What is the initial sag?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
(b)
How much does the sag grow?
Check
A source of 1 pu feeds 0.8 pu at power factor 0.95 lagging through X = 0.15 pu.
(a)
What is the loadability margin?
(b)
At what voltage would collapse occur?
Check
A 1 pu slack feeds 1 + j0.1 pu through lossless X = 0.15 pu.
(a)
What is the operating voltage?
(b)
What angle does the load bus sit behind the slack?
Check
A 1 pu source supplies 1 pu at unity power factor through X = 0.05 pu.
(a)
What reactive margin does its Q–V curve show?
(b)
How many vars must be supplied at the bus to hold it at 1 pu?
Check
After a disturbance a distribution bus sags to 0.9 pu; its load's power varies as with n = 1. Tap changers then restore it to 1 pu.
(a)
By what percentage did the sag cut the load's power?
(b)
By what percentage does restoring the voltage raise it again from the sagged level?
Check
A transposed line has phase spacings 6, 6 and 16 m and two-conductor bundles 0.4 m apart, each conductor with GMR 0.012 m.
(a)
What is the geometric mean distance?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
(b)
What is its inductance?
Check
A lossless line with x = 0.35 Ω/km and b = 4.5 µS/km is 500 km long.
(a)
What is βl?
(b)
How much does its open far end rise?
Check
A step of 1 pu through source resistance 0 Ω energizes an open-ended line with = 300 Ω.
(a)
What voltage first appears at the far end?
(b)
What is the source's reflection coefficient?
Check
A 30 kA lightning stroke hits a phase conductor of a 50 km line ( = 250 Ω, wave speed 300 m/µs) and splits both ways.
(a)
How long does a surge take to travel the line's length and back?
Write units the way you normally would: 1.5 µs, 1500 ns and 0.0015 ms are the same answer.
(b)
What voltage does the stroke raise on the conductor?
Check
A 345 kV line of 100 km (b = 4.5 µS/km) is energized unloaded, and shunt reactors absorb 0.8 of its charging.
(a)
How many vars does the source still have to absorb?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A conductor with 1.6 kg/m (specific heat 900 J/kg·K) gains 3 W/m of net cooling per kelvin near its operating point.
(a)
What is its thermal time constant?
(b)
What fraction of its final temperature rise does a step in current produce after 10 minutes?
Check
A power-flow case has 118 buses: one slack, 12 PV buses and the rest PQ. How many unknowns does it have?
Check
A slack bus at 1 pu feeds 0.5 + j0.6 pu through a lossless X = 0.1 pu. What's the load bus voltage magnitude?
Check
For the same two-bus case, what's the load bus's angle?
Check
For the same case, how many vars must the slack generator supply?
Check
A branch with series admittance 1.5 − j\given4 pu joins buses at 1∠0° and 0.96∠−12°. How much real power leaves the first bus?
Check
A branch with R = 0.01 pu delivers 0.6 + j0.5 pu at 1.02 pu. What's its real power loss?
Check
A slack bus at 1 pu feeds 2 + j0.2 pu through a lossless X = 0.1 pu.
(a)
What is the operating (high) voltage at the load?
(b)
And the other, low-voltage solution?
Check
Unknowns: 57 buses, 9 PV?
Check
Loss: R = 0.005, 0.4 + j0.8 at 1.05 pu?
Check
Load voltage for 0.4 + j0.4 through X = 0.15?
Check
A slack at 1∠0° feeds a load of 0.5 + j0.5 pu through X = 0.2. What's the magnitude of the first Gauss–Seidel iterate for the load bus, from a flat start?
Check
A PV bus at 1.05 pu injects 0.8 pu into a slack at 1∠0° through X = 0.1. What angle does Gauss–Seidel converge to?
Check
For the same PV bus, how many vars does its generator inject at the solution?
Check
Each iteration multiplies the error by 0.3, starting from 0.05. How many iterations until it's below 1 × 10⁻⁶?
Check
An iteration moves a voltage from 0.95 to 0.9. With an acceleration factor of 1.5, what value is kept?
Check
A PV bus's generator can supply at most 0.3 pu of vars. An iteration computes that it would need 0.2 pu. What Q does the next update use?
Check
A PV bus set to 1.02 pu would need 0.5 pu of vars, but its generator is limited to 0.4 pu. The bus's short-circuit level is 10 pu.
(a)
How many vars short is it?
(b)
Roughly where does its voltage settle?
Check
First GS iterate magnitude: X = 0.15, load 0.4 + j0.6?
Check
Iterations to go from 0.1 to 1 × 10⁻⁸ at rate 0.5?
Check
PV-bus angle for 0.2 pu through X = 0.05, both at 1 pu?
Check
In the two-bus Newton power flow with line reactance X = 0.1 pu, what's at the flat start?
Check
A load of 0.5 pu sits at the end of X = 0.2. What angle does Newton's first step from a flat start give the load bus?
Check
A load of P + j0.2 pu at the end of X = 0.2. What voltage magnitude does Newton's first step give?
Check
Near the solution Newton's error obeys with C = 1. Starting from 0.1, what's the error after two steps?
Check
A two-bus case has the load bus guessed at 0.9∠−5° behind X = 0.2, with 1 pu of load. What's the real power mismatch ?
Check
A case has 300 buses, 30 of them PV. How many rows does its Newton Jacobian have?
Check
A two-bus Newton power flow has the load bus at 0.9∠−5° behind lossless X = 0.2 pu.
(a)
What is the Jacobian's determinant?
(b)
What is (the determinant vanishes when it reaches 1)?
Check
Newton's first angle step: P = 0.3, X = 0.08?
Check
Error after one quadratic step from 0.05, C = 0.5?
Check
Jacobian rows: 57 buses, 6 PV?
Check
In a DC power flow (100 MVA base), a line of x = 0.05 pu has 0.08 rad across it. How many MW does it carry?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Two parallel paths of reactance 0.2 and 0.15 pu carry a transfer between the same two buses. What fraction takes the 0.2 pu path?
Check
A load bus draws 0.9 pu through a single line of x = 0.05 pu from the slack. What's its DC power-flow angle?
Check
A triangle network has = 0.1, = 0.15 and = 0.45 pu. What fraction of a transfer from bus 1 to bus 3 flows on line 1–3?
Check
At an angle difference of 15°, by what percentage does the DC model's θ overstate the AC flow's sin θ?
Check
A bus connects to three lines of x = 0.05, 0.08 and 0.25 pu. What's its diagonal entry in the DC power flow's B matrix?
Check
A ring of 4 buses has identical lines. A transfer is made between two adjacent buses.
(a)
What share does the line directly between them carry?
(b)
What share goes around the rest of the ring?
Check
DC flow: 0.01 rad across x = 0.03 pu, 100 MVA base?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Share on the 0.05 path with a parallel 0.1 path?
Check
Triangle: share on the direct line 1–3 (0.3) with = 0.05, = 0.1?
Check
Two parallel transformers with reactances j0.06 and j0.12 pu have taps 4% apart. About how much current circulates between them, in per unit?
Check
A phase shifter adds 5° to a path of x = 0.05 pu, in parallel with a path of x = 0.3 pu. How much real power does it move between them (100 MVA base)?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A transfer of 1.5 pu splits between path A (x = 0.1 pu, rated 0.75 pu) and path B (x = 0.3 pu). What phase shift on path A brings it to exactly its rating?
Check
A transformer of reactance j0.05 pu has a tap a = 0.975 (a:1) on bus i's side. What's the magnitude of its contribution to ?
Check
A tap changer covers ±10% in 32 steps. How many steps up does it take to raise a bus voltage by at least 3.5%?
Check
A transformer of reactance 0.05 pu joins two stiff 1 pu buses whose angles are equal. Its tap is raised to give 1.04 times the voltage toward bus 2. About how much reactive power flows into bus 2 (100 MVA base)?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A phase shifter of x = 0.1 pu shifts by 5°.
(a)
What is the magnitude of its off-diagonal entries?
(b)
What is the angle of , for the shift on bus i's side?
Check
Parallel transformers j0.052 and j0.11, taps 3.5% apart: circulating current, pu?
Check
Phase shift 2.6° with paths of 0.038 and 0.14 pu: MW moved?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Tap a = 0.97 on bus i's side, reactance 0.057 pu: contribution?
Check
For a transfer between the ends of line k, line k itself carries 0.4 of it and line ℓ carries 0.2. What's line ℓ's outage distribution factor for line k?
Check
Line ℓ carries 0.6 pu and line k 0.5 pu. Line ℓ's distribution factor for the outage of line k is 0.6. What does line ℓ carry after line k trips (100 MVA base)?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A line's generation shift factor for bus 5 is 0.35. A generator at bus 5 raises its output by 20 MW, taken up by the slack. How much does the line's flow change?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A line's generation shift factors are 0.3 for bus m and 0.1 for bus n. What's its PTDF for a transfer from m to n?
Check
After an outage a line would be 0.07 pu over its rating. Moving generation to bus j changes its post-outage flow by −0.4 per unit moved. How much generation must move, in MW (100 MVA base)?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A network has 120 lines and 10 generators. How many pairs of line outages does a full N − 2 study of lines alone examine?
Check
A monitored line carries 0.3 pu. Line A carries 0.5 pu with distribution factor 0.5 onto it; line B carries 0.7 pu with factor 0.3.
(a)
What does it carry if line A trips?
(b)
And if line B trips?
Check
= 0.11, = 0.27: ?
Check
Flows 0.26 and 0.13 pu, factor 0.33: line ℓ after line k trips, in MW?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Overload 0.029 pu, post-outage shift factor −0.27: MW to move?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A case with 118 buses: one slack, 12 PV and the rest PQ.
(a)
Unknowns?
(b)
PQ buses?
Check
A slack at 1∠0° feeds 0.6 + j0.5 pu through a lossless X = 0.1.
(a)
Load bus voltage?
(b)
Its angle?
(c)
Slack's vars?
Check
A branch 2 − j\given5 pu joins 1.01∠0° to 0.97∠−10°; a branch of R = 0.01 delivers 0.8 + j0.2 at 0.96 pu.
(a)
Real power leaving the first branch's sending end?
(b)
The second branch's loss?
Check
Gauss–Seidel and Newton on the two-bus case: X = 0.12, load 0.5 + j0.45, flat start.
(a)
Magnitude of the first Gauss–Seidel iterate?
(b)
Angle after Newton's first step?
(c)
Voltage after Newton's first step?
Check
A PV bus at 1.05 pu injects 0.4 pu into a slack at 1∠0° through X = 0.1; its generator is limited to 0.2 pu of vars.
(a)
Angle?
(b)
Vars needed to hold 1.05 pu?
(c)
Vars it actually supplies?
Check
Linear convergence at rate 0.4 from 0.03; quadratic convergence with C = 4 from 0.05.
(a)
Linear: iterations to reach 1 × 10⁻⁷?
(b)
Quadratic: error after two steps?
Check
A two-bus guess: load bus at 0.92∠−4° behind X = 0.25, load 0.9 + j0.1.
(a)
ΔP?
(b)
ΔQ?
Check
DC power flow on a 100 MVA base.
(a)
Flow on a line of x = 0.08 with 0.03 rad across it?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Angle of a bus drawing 1.3 pu radially through x = 0.08?
Check
A triangle: = 0.1, = 0.2, = 0.4 pu; a transfer of 200 MW from bus 1 to bus 3.
(a)
PTDF of line 1–3?
(b)
MW on line 2–3?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A bus with lines of x = 0.05, 0.1 and 0.4 pu; an angle difference of 20°.
(a)
Its B-matrix diagonal?
(b)
DC model's overstatement at 20°?
Check
A Newton Jacobian of size 500 with about 10 nonzeros per row.
(a)
Dense LU operation count?
(b)
Fraction of entries that are nonzero?
Check
Two parallel lines, x = 0.08 and 0.12 pu, carry 1.5 pu between two buses.
(a)
Flow on the 0.08 pu line?
(b)
Increase on the 0.12 pu line if the 0.08 pu line trips?
Check
A transfer of 1.6 pu splits between path A (x = 0.1 pu, rated 0.85 pu) and path B (x = 0.3 pu). A phase shifter can be installed on path A (100 MVA base, DC model).
(a)
Path A's flow without the shifter?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Shift that brings path A to exactly its rating?
(c)
Path B's flow with that shift?
Check
Line ℓ carries 0.4 pu and line k 0.6 pu. For a transfer between line k's ends, line k carries 0.7 of it and line ℓ carries 0.3. Line ℓ is rated 0.8 pu (100 MVA base).
(a)
Line ℓ's outage distribution factor for line k?
(b)
Line ℓ's flow after line k trips?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(c)
That flow as a percentage of line ℓ's rating?
Check
Two identical parallel transformers, each j0.06 pu, serve a load drawing 0.6 pu of reactive power at 1 pu (100 MVA base). One transformer's tap gives 4% more voltage than the other's.
(a)
Circulating current, in per unit?
(b)
Reactive power supplied by the higher-tapped transformer?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(c)
Reactive power supplied by the other one (negative means it absorbs)?
Check
A 60 MW load at 0.9 power factor lagging is served at 138 kV.
(a)
Line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Capacitor to reach 0.98?
Check
A machine (40 MVA, 22 kV, X = 0.1 pu) and a 230 kV line of j40 Ω, on 100 MVA with 24 kV on the machine's side.
(a)
Machine's X?
(b)
Line's X?
(c)
Current on the line for a bolted fault at its far end (1 pu source)?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A short-circuit test reads 400 V, 4 A, 600 W; and a transformer with R = 0.015, X = 0.06 pu at full load, 0.8 lagging.
(a)
Leakage reactance from the test?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
Regulation of the second transformer?
Check
Phases spaced 6, 7, 18 m; two-conductor bundles 0.4 m apart; conductor GMR 13 mm, radius 13 mm.
(a)
L per km?
Write units the way you normally would: 1.5 mH, 1500 µH and 0.0015 H are the same answer.
(b)
C per km?
Check
A 500 kV line with L = 0.9 mH/km and C = 10 nF/km, 500 km long.
(a)
SIL?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Open-end voltage rise?
Check
Buses at 0.98 and 0.96 pu, 28° apart, across X = 0.35 pu.
(a)
Real power?
(b)
Reactive power leaving bus 1?
Check
A 1 pu source feeds a unity-pf load of 0.4 pu through X = 0.2 pu.
(a)
Load voltage?
(b)
Maximum deliverable?
Check
A line of X = 0.35 pu with 0.3 series compensation; a 120 Mvar capacitor at 0.92 pu.
(a)
Transfer limit between 1 pu buses?
(b)
Capacitor output?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
Generator j\given0.15 at bus 1; bus 3 fed directly by j\given0.1 and via bus 2 by j\given0.15 + j\given0.35; the j\given0.1 line has total charging 0.1 pu.
(a)
?
(b)
Net susceptance the j\given0.1 line adds to bus 3's diagonal?
Check
A 118-bus case with 12 PV buses; and a two-bus case with X = 0.25 and a 1 pu load.
(a)
Unknowns in the first?
(b)
Angle after Newton's first step in the second?
Check
Two-bus: X = 0.15, load 0.5 + j0.4, flat start.
(a)
First Gauss–Seidel iterate's magnitude?
(b)
Converged magnitude?
Check
A triangle with = 0.1, = 0.15, = 0.35 pu carrying 250 MW from bus 1 to bus 3.
(a)
Flow on line 1–3?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Angle drop across line 1–2 (100 MVA base)?
Check
A stiff 1 pu source closes, through a resistance of 200 Ω, onto an unloaded lossless line 300 km long with = 300 Ω and wave speed 295 km/ms.
(a)
Size of the first wave launched, in per unit?
(b)
When does it reach the far end?
Write units the way you normally would: 1.5 ms, 1500 µs and 0.0015 s are the same answer.
(c)
Far-end voltage just after it arrives, in per unit?
(d)
Far-end voltage after the second arrival, at three travel times, in per unit?
Check
Line ℓ carries 0.5 pu and line k carries 0.7 pu. Line k carries 0.75 of any transfer between its own ends, and line ℓ carries 0.35 of it. A generator's shift factor on line ℓ is −0.3 with line k in service (100 MVA base).
(a)
Line ℓ's outage distribution factor for line k?
(b)
Line ℓ's flow after line k trips?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(c)
Line ℓ is rated 80 MW. Ignoring the outage's effect on the shift factor, how much must that generator raise its output beforehand to keep line ℓ within its rating after the outage?
Check
A conductor of 22 mm with 0.07 Ω/km at 75 °C sits in 25 °C air with h = 25 W/m²K, ε = α = 0.5 and 1000 W/m² of sun.
(a)
What is its 75 °C ampacity?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A 1 pu source feeds 0.9 pu at power factor 0.9 lagging through X = 0.2 pu.
(a)
What is the loadability margin?
Check
A generator with = 1.2 pu delivers 0.5 + j(0.6) pu at 1 pu. What's its internal voltage magnitude?
Check
For the same machine, what's the power angle?
Check
A generator with E = 1.8 pu behind = 1 pu runs at δ = 50° on a 1 pu bus. How much real power does it deliver?
Check
And how much reactive power?
Check
What's the steady-state power limit of a generator with E = 1.6 pu behind = 0.8 pu on an infinite 1 pu bus?
Check
A generator's field limits E to 1.8 pu, with = 1 pu, on a 1 pu bus. What's the most reactive power it can supply at P = 0.9?
Check
A generator with = 1.2 pu delivers 0.5 pu and 0.4 pu of vars at 1 pu.
(a)
What is |E|?
(b)
What is δ?
Check
|E| for = 1, 0.3 + j0.5?
Check
P for E = 1.5, = 1.1, δ = 40°?
Check
Steady-state limit: E = 1.4, = 0.9?
Check
A generator rated 1 pu with = 1.2 pu and a field limit of E = 1.8 pu runs at 0.8 pu and 1.05 pu terminal voltage.
(a)
What reactive power does the armature limit allow?
(b)
What does the field limit allow?
Check
A machine with = 1.2 pu connects to a stiff 1 pu bus through = 0.2 pu and delivers 0.9 pu.
(a)
At what reactive power (negative is absorbing) does it reach the steady-state stability limit?
Check
Two equal generators with reactive droops of 4% and 6% share a 100 Mvar increase in demand.
(a)
How much does the first one take?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A proportional voltage regulator with gain 20 controls a generator of open-circuit gain 1.
(a)
What steady voltage error does it leave?
Check
A 500 MVA generator is rated to deliver its full apparent power at power factor 0.85.
(a)
What real power does that correspond to?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
How many vars can it supply at that point?
Check
A generator with = 1.5 pu runs at no load and 0.9 pu terminal voltage.
(a)
How many vars can it absorb before the steady-state stability limit, with its field at zero?
Check
Armature-limited vars at P = 0.6, V = 0.95 (rated 1 pu)?
Check
Share of 90 Mvar for droop 3% against 5%?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
AVR steady error with gain 50?
Check
A unit's cost is dollars per hour. What's its incremental cost at 350 MW, in dollars per MWh?
Check
Units with incremental costs 5 + 2(0.003)P and 6.5 + 2(0.008)P share 300 MW. What's λ, in dollars per MWh?
Check
For the same pair, how much does the first unit produce?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
What does a unit with cost cost per hour at 450 MW?
Check
A unit's incremental cost is 7 dollars per MWh and each extra MW it produces raises losses by 0.02 MW. What's its effective incremental cost, in dollars per MWh?
Check
A cheap unit is pinned at its 300 MW maximum, and a second unit with cost 5.5P + 0.004P² (plus constant) supplies the rest of a 650 MW load. What's the system λ, in dollars per MWh?
Check
Three units have incremental costs 7 + 2(0.004)P, 10 + 2(0.012)P and 6 + 2(0.005)P dollars per MWh, sharing 600 MW.
(a)
What is λ, in dollars per MWh?
(b)
How much does the first unit produce?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Incremental cost (dollars per MWh): b = 3.5, c = 0.001, P = 500 MW?
Check
λ for two units (4.5, 0.002) and (6, 0.01) sharing 400 MW (dollars per MWh)?
Check
Effective incremental cost: 6 dollars per MWh, loss sensitivity 0.03?
Check
A plant sends its output over a line of resistance 0.02 pu at 0.95 pu and power factor 0.9. What's its loss coefficient B, in per unit?
Check
A plant's losses are with B = 0.0004 per MW. What's its penalty factor at P = 200 MW?
Check
A unit's incremental cost is 22 dollars per MWh and its penalty factor is 1.03. What incremental cost does the load see, in dollars per MWh?
Check
A unit's incremental cost is 6 + 0.01P dollars per MWh and its losses are with B = 0.0002 per MW. At λ = 12 dollars per MWh, how much does it produce?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A unit could run through an off-peak hour at its 60 MW minimum, costing 200 dollars per hour of no-load cost and 8 dollars per MWh more than the unit that would otherwise make that energy. How many dollars does keeping it on for the hour cost?
Check
A unit's cost is 600 + 18P dollars per hour. What's its full-load average cost at 500 MW, in dollars per MWh, the number a priority list sorts by?
Check
A remote plant's incremental cost is 18 dollars per MWh with penalty factor 1.03; a local plant's is 21 with penalty factor 1.
(a)
What is the remote plant's delivered incremental cost?
(b)
By how much is the remote plant cheaper at the margin (negative if dearer)?
Check
Penalty factor for , B = 0.00011, P = 64 MW?
Check
Output at λ = 14 with incremental cost 6.4 + 0.0061P and B = 0.00022?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Full-load average cost: 670 + 18P dollars per hour at 440 MW?
Check
A cheap generator at A sends power over a line rated 150 MW to a 450 MW load at B, where a costlier generator also sits. How much must B's generator produce?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A congested line carries 300 MW from a bus priced at 12 to one priced at 30 dollars per MWh. What's its congestion rent, in dollars per hour?
Check
A 550 MW load at B is served by a 10 dollars per MWh generator at A through a 300 MW line and by a 30 dollars per MWh generator at B. What's the total cost per hour?
Check
A triangle of identical lines has generators at buses 1 and 2 and a 300 MW load at bus 3, with line 1–3 limited to 110 MW. What's the most bus 1's generator can produce?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
In the same triangle, with line 1–3 binding, generator 1 costs 20 and generator 2 costs 35 dollars per MWh. What's the LMP at bus 3?
Check
A unit costs 20000 dollars to start and 800 dollars per hour to keep running at minimum output when it isn't needed. Above what idle gap is shutting it down cheaper?
Check
An uncongested line carries 600 MW from a generator priced at 20 dollars per MWh, with losses , B = 5 × 10⁻⁵ per MW.
(a)
What is the marginal loss factor?
(b)
What is the LMP at the receiving bus?
Check
Congestion rent (dollars per hour): 400 MW from 8 to 25 dollars per MWh?
Check
Bus-3 LMP in the binding triangle, costs 10 and 40?
Check
Breakeven idle time: start cost 3000, no-load cost 500 per hour?
Check
A 30 GW system with H = 5 s loses 1.2 GW of generation. What's the initial rate of change of frequency?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
A 500 MW unit with 0.05 droop sees frequency fall by 0.1 Hz. How much does its governor raise output?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A system (all generation at droop 0.04) loses 0.05 pu of generation, with load damping D = 2. Where does frequency settle?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A 300 MW unit at 0.04 droop and a 600 MW unit at 0.07 droop share a 50 MW load increase. How much does the first take?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
An area's tie-line flow is −50 MW from schedule, frequency is 0.03 Hz from 60, and its bias is −400 MW/0.1 Hz. What's its ACE?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A system of 50 MW with H = 5 s is falling at 1 Hz/s just after a disturbance. How large was the power deficit?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A 20 GW system with H = 2 s loses 2 GW. Load shedding begins at 59.3 Hz.
(a)
What is the initial ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
(b)
If that rate held, how soon would shedding begin?
Check
ROCOF: lose 0.3 GW from 20 GW with H = 6 s?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
Settling Δf: loss 0.03 pu, R = 0.04, D = 1.5?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
ACE: tie −120 MW, Δf 0.02 Hz, B = −300?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Meter A (σ = 0.015 pu) reads 0.8 and meter B (σ = 0.05 pu) reads 0.84 for the same flow. What's the weighted least-squares estimate, in per unit?
Check
For those two meters (σ = 0.01 and 0.02 pu), what's the standard deviation of the estimate, in per unit?
Check
An estimator has 30 measurements and 5 state variables. How many degrees of freedom does its chi-square test have?
Check
A residual is 0.03 pu and the residual's standard deviation is 0.006 pu. What's its normalized residual?
Check
A meter has σ = 0.01 pu, and its row of has diagonal entry 0.005² pu². What's the standard deviation of its residual, in per unit?
Check
A reading is off from its estimate by 0.3 pu with σ = 0.01 pu. How much does that one residual add to J?
Check
Two meters read the same flow: 0.98 pu (σ = 0.01) and 1.1 pu (σ = 0.05).
(a)
What is the WLS estimate?
(b)
What is J?
Check
WLS estimate from 0.86 (σ = 0.022) and 0.61 (σ = 0.041)?
Check
Normalized residual: r = 0.014, = 0.0048?
Check
Degrees of freedom for 78 measurements and 3 states?
Check
A generator with = 1.4 pu delivers 0.6 + j(0.4) pu at 1 pu.
(a)
|E|?
(b)
Power angle?
(c)
Steady-state limit at this excitation?
Check
A generator with E = 1.5 pu behind = 1.1 pu on a 1 pu bus.
(a)
P at δ = 35°?
(b)
Q at δ = 35°?
(c)
Most Q at P = 0.8 if E is the field limit?
Check
Two units, = 5, = 0.003 and = 6.5, = 0.008 (costs dollars per hour), share 300 MW.
(a)
λ, in dollars per MWh?
(b)
Unit 1's output?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(c)
Unit 2's output?
Check
A unit at 7.5 dollars per MWh with loss sensitivity 0.03; and a cheap unit pinned at 250 MW with a second unit ( = 6.5, = 0.008) covering the rest of 550 MW.
(a)
First unit's effective incremental cost?
(b)
System λ in the second case?
Check
A 500 MW load at B, a cheap generator (10 dollars per MWh) at A behind a 250 MW line, and a costlier one (35) at B.
(a)
B's generator output?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Total cost, dollars per hour?
(c)
Congestion rent, dollars per hour?
Check
A triangle of identical lines, generators at buses 1 (25) and 2 (55 dollars per MWh), 240 MW at bus 3, line 1–3 limited to 120 MW.
(a)
Bus 1's output?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Bus 3's LMP?
Check
A 40 GW system with H = 6 s.
(a)
ROCOF after losing 0.6 GW?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
(b)
Deficit if frequency falls at 0.3 Hz/s?
Check
Loss of 0.03 pu with droop 0.04 and load damping 1.5; a 600 MW unit at droop 0.04 during a 0.15 Hz dip.
(a)
Settling frequency deviation?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
The unit's governor response?
Check
Units of 400 MW at 0.04 droop and 500 MW at 0.07 droop share 80 MW.
(a)
First unit's share?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Frequency drop (no load damping)?
Check
An area: tie flow −40 MW off schedule, Δf = 0.04 Hz, bias −500 MW/0.1 Hz.
(a)
ACE?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Generation change AGC will ask for?
Check
A unit with start cost 8000 dollars and no-load cost 600 dollars per hour; another with cost 300 + 6P + 0.006P² at 120 MW.
(a)
Breakeven idle time?
(b)
Second unit's hourly cost, in dollars?
(c)
Its incremental cost, dollars per MWh?
Check
A remote plant's incremental cost is 6 + 0.008P dollars per MWh, and its share of the losses is with B = 0.0003 per MW. The system λ is 12 dollars per MWh.
(a)
The plant's output?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Its penalty factor there?
(c)
The losses it causes?
Check
A unit could stay on through a 1-hour dip at its 80 MW minimum, with 200 dollars per hour of no-load cost and making energy at 7 dollars per MWh more than the unit that would otherwise make it. Restarting it costs 1500 dollars.
(a)
Cost of staying on through the dip, in dollars?
(b)
How many dollars does staying on save compared with restarting? (Negative means shutting down is cheaper.)
Check
Two voltmeters on the same bus read 1 pu (σ = 0.01) and 0.98 pu (σ = 0.02).
(a)
Weighted least-squares estimate of the voltage, in per unit?
(b)
Standard deviation of the estimate, in per unit?
(c)
The minimum J?
Check
Three units have incremental costs 7 + 2(0.004)P, 9 + 2(0.004)P and 6.5 + 2(0.007)P dollars per MWh and share 800 MW.
(a)
What is λ?
(b)
How much does the third unit produce?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A system has 6 identical units, each with forced outage rate 0.02.
(a)
What's the probability all are available?
(b)
That exactly one is out?
(c)
That two or more are out?
Check
Five 100 MW units (FOR 0.05) serve a daily peak of 310 MW on 250 days a year, and much lighter loads otherwise.
(a)
What's the loss-of-load probability on a peak day?
(b)
What LOLE do the peak days contribute per year?
Check
A system has 1200 MW installed for a peak of 1091 MW.
(a)
What is its reserve margin?
Check
A 100 MW unit (FOR 0.05) and a 150 MW unit (FOR 0.08) make up a system.
(a)
What's the probability of no capacity out?
(b)
Of everything out?
(c)
Of exactly one unit out (either)?
Check
A system's LOLE is 2 days per year, and each loss-of-load day averages 4 hours of shortfall.
(a)
By what factor must its risk fall to meet one day in ten years?
(b)
About how many loss-of-load hours per year is that?
Check
A 200 MW wind farm adds the same reliability as 15% of its nameplate in perfectly reliable capacity.
(a)
What is its capacity credit?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Probability exactly one of 3 units (FOR 0.04) is out?
Check
Reserve margin: 900 MW for a 750 MW peak?
Check
LOLE from 60 days at daily LOLP 0.001?
Check
A generator rated 1 pu ( = 1.4 pu, field limit E = 2 pu) runs at 0.9 pu and 1.05 pu terminal voltage.
(a)
How many vars can it supply?
Check
A machine ( = 1.6 pu) reaches a stiff 1 pu bus through = 0.15 pu and delivers 0.8 pu.
(a)
How many vars can it absorb before the steady-state stability limit?
Check
A 250 MVA generator, rated at power factor 0.85, delivers its rated real power while the terminal voltage sags to 0.96 pu; its armature limit binds.
(a)
How many vars can it still supply?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(b)
By what percentage has its reactive capability fallen?
Check
Three equal generators with reactive droops of 2%, 5% and 6% share a 150 Mvar rise in demand.
(a)
How much does the first one take?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A proportional AVR with gain 100 holds a generator's terminal voltage; a load change would shift the uncontrolled voltage by 0.02 pu.
(a)
How much does the regulated voltage shift?
Check
6 identical units, each with forced outage rate 0.03.
(a)
What is the probability that three or more are out at once?
Check
Six 100 MW units (FOR 0.04) see 80 days a year with a 420 MW peak and the rest at 360 MW.
(a)
What LOLE do the high days contribute?
(b)
And the other days?
Check
A system of a 150 MW unit (FOR 0.05) and a 250 MW unit (FOR 0.08) serves 260 MW.
(a)
What is its loss-of-load probability?
Check
A system with 1000 MW installed and an 820 MW peak adds a 400 MW wind farm whose capacity credit is 25%.
(a)
What was its reserve margin?
(b)
What is it counting the wind at its capacity credit?
Check
Two units with incremental costs 8 + 2(0.004)P and 10 + 2(0.008)P share 700 MW; the first is limited to 300 MW.
(a)
What does the first unit produce?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A remote plant sends 300 MW with losses , B = 0.0001 per MW; the system λ is 15 dollars per MWh.
(a)
What is its penalty factor?
(b)
What incremental cost should it run at?
Check
An 18 dollars per MWh unit at A and a 40 dollars per MWh unit at B serve 500 MW at B through a 350 MW line.
(a)
What is the price at B?
(b)
What congestion rent accrues per hour?
Check
A unit costs 5000 dollars to start and loses 300 dollars per hour running at its minimum through off-peak hours.
(a)
For how many off-peak hours is it cheaper to keep it running than to shut it down and restart?
Check
A 50 MVA, 22 kV generator with X″ = 0.2 pu is shorted at its terminals. What's the subtransient current?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A generator (X″ = 0.15) and transformer (X = 0.08, both on 100 MVA) feed a 230 kV bus that's shorted. What's the fault current there?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A bus has a Thevenin impedance of 0.15 pu on a 100 MVA base. What's its short-circuit level?
Write units the way you normally would: 1.5 MVA, 1500 kVA and 0.0015 GVA are the same answer.
Check
A fault at bus k has = j0.35; another bus has = j0.1. What's that bus's voltage during the fault, prefault voltages 1 pu?
Check
A fault of 10 kA RMS symmetrical occurs where X/R = 15. Estimate the worst first peak.
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A bus is fed by two sources whose Thevenin reactances to it are 0.1 and 0.15 pu. What's the fault current at the bus in per unit?
Check
A fault with X/R = 15 at 60 Hz is interrupted when the breaker's contacts part 2 cycles after it starts.
(a)
What is the DC offset's time constant?
Write units the way you normally would: 1.5 ms, 1500 µs and 0.0015 s are the same answer.
(b)
By what factor is the worst-case RMS current raised at that moment?
Check
Subtransient current: 25 MVA, 20 kV, X″ = 0.1?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
Short-circuit MVA: = 0.08 pu on 100 MVA?
Write units the way you normally would: 1.5 MVA, 1500 kVA and 0.0015 GVA are the same answer.
Check
Voltage at bus i during a fault at k: = 0.25, = 0.05?
Check
A line-to-line load draws 20 A from phase a and returns it on phase b. How big is its positive-sequence current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Phase currents are 100∠0°, 70∠−120° and 110∠120° A. What's the neutral current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
For the same currents, what's the positive-sequence magnitude?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Phase b's voltage sags to 0.9 pu while phases a and c stay at 1 pu, all 120° apart. What's the negative-sequence unbalance ?
Check
A voltage has = 1 pu, = 0.3 pu (both at 0° in phase a) and no zero sequence. What's the magnitude of phase b?
Check
A negative-sequence voltage sits at 0° on the low side of a standard Y–Δ transformer. At what angle does it appear on the high side?
Check
A single-phase load draws 300 A from phase a only of a four-wire system.
(a)
What is the positive-sequence current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What flows in the neutral?
Check
for a line-to-line load of 50 A?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Unbalance when phase b sags to 0.7?
Check
Neutral current for 50∠0°, 40∠−120°, 70∠120°?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A bus has = j0.15, = j0.15 and = j0.6 pu. What's the bolted single line-to-ground fault current?
Check
With = j0.2 and = j0.12 pu, what's the current in phase b for a bolted b–c fault?
Check
A bus has = j0.15 and = j0.2 pu with solid grounding. What neutral reactance limits a line-to-ground fault to 2.2 pu?
Check
A bus has = j0.15 and = j0.1 pu. How much current flows into the ground for a bolted double line-to-ground fault?
Check
A line-to-ground fault through 0.2 pu of resistance occurs at a bus with = j0.15 and = j0.2. What's the fault current?
Check
A generator has = j0.15 and = j0.05, solidly grounded. What's the ratio of line-to-ground to three-phase fault current at its terminals?
Check
A 13.8 kV bus has = j0.1 and = j0.2 pu on 100 MVA. A neutral resistor must limit ground faults to 1000 A.
(a)
What resistance does it need?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
Line-to-ground current: = 0.1, = 0.1, = 0.5?
Check
Line-to-line current: = 0.1, = 0.1?
Check
Neutral reactance limiting ground faults to 2.5 pu ( = 0.2, = 0.15)?
Check
A line of j0.2 pu runs between two buses that are also connected through the rest of the network by j0.3 pu. What impedance, in per unit, does one sequence network present across a break in the line?
Check
One conductor of a line carrying 1 pu opens. Across the break = j0.5 and = j3 pu. What's the positive-sequence current, in per unit?
Check
Two conductors of a line carrying 1 pu open. Across the break = j0.5 and = j3 pu. What current, in per unit, does the remaining conductor carry?
Check
One conductor of a line carrying 1 pu opens. Across the break and is 1 times as large. How much current returns through the ground, in per unit?
Check
A bolted line-to-ground fault on the grounded-wye side of a delta–wye transformer draws 3 pu. How much current, in per unit, flows in each of the two faulted phases on the delta side?
Check
An ungrounded delta system has = j0.2 pu at a bus; a zigzag grounding transformer adds a zero-sequence impedance of j0.02 pu.
(a)
What single line-to-ground fault current can flow?
(b)
How does it compare with the three-phase fault current, as a ratio?
Check
One open: I = 0.73, = 0.43, = 2.9. ?
Check
Two open: I = 0.73, = 0.43, = 2.9. Current in the closed phase?
Check
LG fault of 1.5 pu on the wye side of a delta–wye. Delta-side current in each faulted phase?
Check
A 400:1 CT carries 8000 A of fault current. What flows in its secondary?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
An IEEE very inverse relay with time dial 0.5 sees 5 times pickup. When does it operate?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A downstream relay operates in 0.4 s for a fault. With a coordination interval of 0.2 s, how fast may the upstream relay operate for the same fault?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A line's impedance is 60 Ω primary. With CT ratio 120 and VT ratio 3000, what's it in secondary ohms?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A 200 km line has 40 Ω of positive-sequence impedance. Zone 1 is set to 0.8 of the line. What's its reach in primary ohms?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A transformer differential relay sees 10 A in and 9.2 A out (secondary, after ratio correction) during an external fault. What's the operating current as a percentage of the restraint current?
Check
A differential relay with a 30% slope sees 10 A entering and 1 A leaving its zone (secondary, after ratio correction).
(a)
What is the operating current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What is its ratio to the restraint current (the relay trips above 30%)?
Check
Extremely inverse time: dial 1, M = 8?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
Secondary ohms: 30 Ω, CTR 160, VTR 3500?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
CT secondary: 3000 A through a 600:1 CT?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A 300 MVA, 18 kV generator (X″ = 0.12 pu) with an 18/138 kV transformer (X = 0.08 pu on 300 MVA).
(a)
Terminal fault current?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(b)
Fault current on the 138 kV side?
(c)
Short-circuit level there?
Check
A fault at bus k ( = j0.25) with = j0.1 and = j0.15, prefault 1 pu.
(a)
Fault current?
(b)
Bus i voltage?
(c)
Voltage difference between buses j and i?
Check
A 15 kA symmetrical fault where X/R = 20; and a bus fed by sources of 0.3 and 0.5 pu.
(a)
Worst first peak?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(b)
Fault current at the bus in pu?
Check
Phase currents 90∠0°, 60∠−120°, 120∠120° A; and a line-to-line load of 60 A.
(a)
Neutral current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Positive-sequence magnitude?
(c)
Line-to-line load's negative-sequence current?
Check
Phase b sags to 0.88 pu; separately, = 1 and = 0.15 pu; and a negative-sequence voltage at 10° on a Y–Δ low side.
(a)
Unbalance from the sag?
(b)
|V_b| for the second case?
(c)
Its angle on the high side?
Check
A bus with = j0.2 and = j0.08 pu.
(a)
Three-phase fault current?
(b)
Line-to-ground?
(c)
Line-to-line?
Check
A bus with = j0.15, = j0.15.
(a)
Ground current for a double line-to-ground fault?
(b)
Line-to-ground current through 0.15 pu of fault resistance?
Check
Neutral grounding for a bus with = j0.15, = j0.1.
(a)
Reactance limiting ground faults to 2 pu?
(b)
Ground-to-three-phase ratio when solidly grounded?
Check
A 300:1 CT on a feeder with a very inverse relay (dial 1.5) picking up at 1.2 A secondary; fault current 2500 A.
(a)
CT secondary current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Multiple of pickup?
(c)
Operating time?
Check
A downstream relay operates in 0.25 s; an upstream very inverse relay sees 4 times pickup for the same fault; coordination interval 0.4 s.
(a)
Required upstream time?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
Upstream time dial?
Check
A line of 25 Ω, CT ratio 200, VT ratio 3000.
(a)
Line in secondary ohms?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
Zone 1 setting (0.85 of the line), secondary?
(c)
Zone 2 setting (1.2 of the line), secondary?
Check
A differential relay with slope 0.35 sees 8 A in and 7 A out.
(a)
Operating current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
As a percentage of the restraint?
Check
One phase of a line carrying 1 pu breaks. Across the break = j0.6 pu and = j3 pu.
(a)
Positive-sequence current, in per unit?
(b)
Negative-sequence current magnitude, in per unit?
(c)
Current returning through the ground, in per unit?
Check
A bolted line-to-ground fault occurs on the grounded-wye low side (34.5 kV) of a delta–wye transformer, where = j0.15 pu and = j0.1 pu on 200 MVA.
(a)
Fault current in per unit?
(b)
Fault current in kiloamperes?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(c)
Current in each of the two faulted phases on the delta side, in per unit?
Check
A 40 kA symmetrical fault with X/R = 12 (60 Hz) is interrupted after 1.5 cycles.
(a)
What is the DC time constant?
Write units the way you normally would: 1.5 ms, 1500 µs and 0.0015 s are the same answer.
(b)
What worst-case RMS current must the breaker interrupt?
Check
A generator delivers 0.8 pu with = 1.5 pu. What's its equilibrium rotor angle?
Check
For the same machine, what's the synchronizing power coefficient?
Check
A machine with H = 5 s has a synchronizing power coefficient of 1 pu/rad. At what frequency do its rotor swings oscillate?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A machine with H = 5 s delivers 0.5 pu when a fault drops its output to zero. How far does its angle advance in 0.15 s?
Check
How much kinetic energy does a 100 MVA machine with H = 4 s store at rated speed?
Write units the way you normally would: 1.5 MJ, 1500 kJ and 0.0015 GJ are the same answer.
Check
A 200 MVA machine has H = 3 s on its rating. What's H on a 1000 MVA system base?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A unit with H = 6 s delivers 1 pu with = 1.8 pu (60 Hz).
(a)
What is its synchronizing power coefficient, in pu per radian?
(b)
At what frequency does it swing?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
Equilibrium angle: 0.3 pu, = 1.2?
Check
Swing frequency: H = 2 s, = 0.8?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
Advance during a zero-output fault: H = 3, P = 0.6, t = 0.2 s?
Check
A machine delivers 0.7 pu with = 1.6 pu. A fault drops its output to zero and is cleared with the network unchanged. What's the critical clearing angle?
Check
A machine with H = 5 s delivers 0.5 pu from δ₀ = 30°. A fault drops its output to zero. When does it reach 80°?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A machine at 0.6 pu is accelerated from 20° to 95° by a fault with zero electrical output. What's the accelerating area?
Check
After clearing at 90°, the curve is 1.5 sin δ and = 0.5. How much decelerating area is available before the unstable equilibrium?
Check
After a fault is cleared the transfer curve is 1.4 sin δ with = 0.8. At what angle is the unstable equilibrium?
Check
Pre-fault = 2, during the fault 0.2 of that, after clearing 0.7 of it, with = 1. What's the critical clearing angle?
Check
A machine with = 0.6 pu and = 1.5 pu before and after a fault that drops its output to zero is cleared at 70°.
(a)
What accelerating area did the fault store, in pu·rad?
(b)
What decelerating area is available up to the unstable equilibrium?
Check
Critical clearing angle: 0.5 pu, = 1.5, zero-transfer fault?
Check
Time from 35° to 100° at zero output: H = 2.5, P = 0.6?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
Unstable equilibrium for 1.5 sin δ and = 0.4?
Check
Two machines have H = 5 s and 3 s on a common base. What's the equivalent inertia of their relative motion?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
Machines with H = 6 s and 4 s swing against each other through = 2.5 pu/rad. What's the swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A mode has eigenvalues . What's its damping ratio?
Check
A mode's real part is −0.2 s⁻¹. How long does its amplitude take to halve?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A 200 MVA machine with H = 3 s and a 1200 MVA machine with H = 5 s are lumped into one on a 100 MVA base. What's the combined H?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A system with 50 synchronous machines: how many electromechanical oscillation modes does its linearized model have?
Check
An oscillation mode at s⁻¹ has its real part moved 0.5 s⁻¹ further left by a stabilizer.
(a)
What was its damping ratio?
(b)
What is it now?
(c)
How long does its amplitude now take to halve?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
for 4 s and 6 s?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
Damping of −0.15 ± j3?
Check
Two-machine swing frequency: H 4 and 5 s, = 3?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A system's synchronous units have H = 5 s. If 0.3 of the generation becomes inverter-based with no inertia, what's the system H on the same base?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A 30 GW system with H = 5 s loses 1.5 GW. What's the initial ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
A 100 MW wind farm connects at a bus with a 1500 MVA short-circuit level. What's its short-circuit ratio?
Check
An inverter of 50 MW rating emulates H = 2 s. How much power does it inject while frequency falls at 1 Hz/s?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A 100 MW inverter plant limits its fault current to 1.5 times rated. How much does it contribute at 69 kV?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A 30 GW system with H = 2.5 s must keep ROCOF below 0.8 Hz/s when it loses 4 GW. How much fast frequency response must act immediately?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A 100 MW inverter plant connects at a bus with an 800 MVA short-circuit level; a synchronous condenser of 300 MVA with X″ = 0.25 pu is added there.
(a)
What was the short-circuit ratio?
(b)
What is it with the condenser?
Check
System H with 0.2 inverter share, synchronous H = 3.5?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
SCR: 300 MVA bus, 80 MW plant?
Check
Synthetic inertia power: H = 3 s, 20 MW, 0.6 Hz/s?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A current has a fundamental of 200 A with harmonics of 25, 5 and 10 A. What's its THD?
Check
Each phase of a balanced load carries 20 A of third harmonic. How much third-harmonic current flows in the neutral?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A 1 Mvar capacitor bank sits at a bus with a 150 MVA short-circuit level. At what harmonic order do they resonate?
Check
A generator exports 3 MW and absorbs 1 Mvar at the end of a feeder of 1 + j2 Ω at 12.47 kV. Estimate the voltage rise.
Check
A load lumped at the end of a feeder would cause a 6% drop. What's the drop if the same load is spread evenly along it?
Check
A utility serving 10000 customers had 4000 customer interruptions in a year, averaging 180 minutes each. What's its SAIDI?
Check
Solar inverters export 3 MW and absorb 1 Mvar at the end of a 12.47 kV feeder of 1.5 + j1 Ω.
(a)
By how much do they raise the voltage there?
(b)
At what power factor do they run?
Check
THD: 150 A with 6, 4, 12 A of harmonics?
Check
Resonant order: 2 Mvar at 60 MVA?
Check
DG voltage change: 0.5 + j1 Ω, 2 MW out, 0.8 Mvar in, 12.47 kV?
Check
A machine with H = 6 s delivers 0.9 pu with = 1.6 pu.
(a)
Equilibrium angle?
(b)
Synchronizing coefficient?
(c)
Swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A 150 MVA machine with H = 2.5 s on its rating, delivering 1 pu when a fault drops its output to zero.
(a)
Stored energy?
Write units the way you normally would: 1.5 MJ, 1500 kJ and 0.0015 GJ are the same answer.
(b)
H on a 1000 MVA base?
(c)
Angle advance in 0.06 s?
Check
A zero-transfer fault on a machine at 0.5 pu, = 1.8, H = 6 s, cleared with the network unchanged.
(a)
Critical clearing angle?
(b)
Critical clearing time?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
After clearing at 85° the curve is 1.6 sin δ with = 0.6; the machine started at its equilibrium on the same curve.
(a)
Accelerating area for a zero-transfer fault?
(b)
Available decelerating area?
Check
= 2 before the fault, 0.2 of it during, 0.7 of it after; = 1.
(a)
Post-fault unstable equilibrium?
(b)
Critical clearing angle?
Check
Two machines with H = 3 s and 5 s, = 2.5; a mode at .
(a)
?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
Swing frequency?
(c)
Damping ratio of the mode?
Check
A 90 GW system whose synchronous fleet has H = 4 s; 0.3 of generation becomes inverter-based. It loses 2 GW.
(a)
System H?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
ROCOF?
Check
A 150 MW inverter plant (fault current 1.4 × rated) at a 230 kV bus with a 600 MVA short-circuit level.
(a)
SCR?
(b)
Its fault contribution?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
An inverter of 50 MW emulating H = 3 s at 0.8 Hz/s; a 30 GW system with H = 1.5 s losing 7 GW with ROCOF capped at 0.5 Hz/s.
(a)
Synthetic inertia power?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Fast frequency response needed?
Check
A 12.47 kV feeder 3 km long, z = 0.25 + j0.5 Ω/km, carrying 6 MW at 0.85 pf.
(a)
Drop with the load lumped at the end?
(b)
With the load spread evenly?
Check
A 160 A fundamental with 12, 8 and 9 A of 3rd, 5th and 7th harmonics; a 2 Mvar capacitor at a 50 MVA bus.
(a)
THD?
(b)
Neutral third-harmonic current in a balanced set?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(c)
Resonant harmonic order?
Check
A utility of 20000 customers with 9000 interruptions averaging 120 minutes; and a DG exporting 1 MW, absorbing 0.3 Mvar, at the end of 2.5 + j1.5 Ω at 12.47 kV.
(a)
SAIDI?
(b)
SAIFI?
(c)
Voltage change at the DG?
Check
A unit with H = 5 s and = 2 pu goes from 1.2 pu to 1.8 pu of output (60 Hz).
(a)
What was its swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
What is it now?
Check
A power system stabilizer moves a mode at s⁻¹ left by 0.4 s⁻¹.
(a)
What damping ratio results?
(b)
By what factor does the halving time shrink?
Check
A 150 MW inverter plant sits at a 500 MVA bus; a 400 MVA synchronous condenser (X″ = 0.2 pu) is added there.
(a)
What short-circuit ratio results?
Check
Two buses are joined by j0.1 pu and each has a generator of j0.15 pu. A bolted three-phase fault occurs at bus 1.
(a)
What fault current flows, in per unit?
(b)
What voltage does bus 2 keep?
Check
A bus has = j0.2 and = j0.05 pu.
(a)
What is its bolted single line-to-ground fault current?
(b)
What ground current does a bolted double line-to-ground fault draw?
(c)
What phase current does a line-to-line fault draw?
Check
A three-phase fault through j0.02 pu occurs at a bus whose Z-bus diagonal is j0.2 pu.
(a)
What current flows?
(b)
What voltage remains at the faulted bus?
Check
A breaker interrupts a fault with X/R = 20 (60 Hz) when its contacts part 2 cycles after the fault starts.
(a)
By what factor does the worst-case offset raise the RMS current?
Check
A 4.16 kV system with = j0.15, = j0.2 pu (100 MVA) must limit ground faults to 800 A with a neutral resistor.
(a)
What resistance does it need?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A downstream very inverse relay (dial 1) sees 5 times its pickup during a fault; the upstream very inverse relay sees 4 times its pickup and must trail it by 0.4 s.
(a)
When does the downstream relay trip?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
What time dial does the upstream relay need?
Check
A differential relay with a 40% slope sees 15 A in and 7.4 A out of its zone.
(a)
What is the ratio of operating to restraint current?
Check
A unit with H = 6 s delivers 0.6 pu with = 1.8 pu on a 60 Hz system.
(a)
What is its rotor angle?
(b)
At what frequency does it swing?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A machine with H = 6 s at 0.6 pu ( = 1.8 pu before and after) has a fault that drops its output to zero.
(a)
What is the critical clearing angle?
(b)
What is the critical clearing time?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A machine at 0.8 pu has = 2 pu before a fault, 0.4 of that during it and 0.85 of it after clearing.
(a)
Where is the post-fault unstable equilibrium?
(b)
What is the critical clearing angle?
Check
Two machines (H = 3 and 2 s, E = 1.15 pu each) are joined by 1 pu and run 15° apart, on 60 Hz.
(a)
At what frequency do they swing against each other?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
An oscillation mode sits at s⁻¹.
(a)
What is its damping ratio?
(b)
How long does its amplitude take to halve?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A zero-output fault on a machine at 0.8 pu ( = 2 pu before and after) is cleared at 65°.
(a)
How much decelerating area is left over after absorbing the accelerating area (negative if it fails)?
Check
What does a transformer of reactance j0.05 with tap 0.95 on bus i's side add to ?
Check
Net susceptance magnitude on each end's diagonal: j0.05 line, charging 0.04?
Check
First Gauss–Seidel iterate's magnitude for the two-bus case: X = 0.1, load 0.5 + j0.5?
Check
Jacobian size for 30 buses with 3 PV?
Check
Branch loss: R = 0.01, 0.5 + j0.6 at 1.03 pu?
Check
Voltage at bus i during a fault at k: = 0.2, = 0.08?
Check
A 345 kV line, 150 km: phases spaced 7, 8, 20 m; two-conductor bundles 0.4 m apart, conductor GMR 14 mm.
(a)
Total series reactance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
Transfer limit between buses held at rated voltage?
Check
A generator (X″ = 0.15) and transformer (X = 0.1, 100 MVA) feed a 230 kV line of j80 Ω, faulted at its far end; the line's relay uses a 100:5 CT and very inverse curve, dial 1, pickup 0.5 × 5 A.
(a)
Fault current on the line?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Multiple of pickup?
(c)
Relay time?
Check
A slack at 1∠0° serves 0.6 + j0.5 pu through X = 0.15.
(a)
Load voltage?
(b)
Capacitor (pu) to bring the load to 0.95 lagging?
Check
A generator ( = 1) delivers 0.7 + j0.5 at 1 pu; in a transient stability study its is 2.2 pu.
(a)
Internal voltage |E|?
(b)
Critical clearing angle for a zero-transfer fault?
Check
Two units (5, 0.003) and (6.5, 0.008) share 300 MW; unit 1's loss sensitivity is 0.03.
(a)
λ ignoring losses, dollars per MWh?
(b)
Unit 1's effective incremental cost at that dispatch?
Check
A 40 GW system (synchronous H = 3 s, 0.6 inverter-based, droop 0.04, D = 1) loses 3 GW.
(a)
Initial ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
(b)
Settling frequency deviation?
Check
A 138 kV bus (100 MVA base) with = j0.15, = j0.1.
(a)
Line-to-ground fault current?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(b)
Line-to-line fault current?
Check
A triangle ( = 0.1, = 0.15, = 0.35 pu) carries 250 MW from bus 1 to bus 3; line 1–3 is rated 120 MW.
(a)
Flow on line 1–3?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Largest transfer before line 1–3 overloads?
Check
Two machines (H = 3 and 5 s) with E = 1.15 pu each, joined by X = 0.8 pu, 15° apart.
(a)
Synchronizing coefficient?
(b)
Swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A 12.47 kV feeder 4 km long (z = 0.2 + j0.45 Ω/km) with 5 MW of evenly spread unity-pf load; a 1 Mvar capacitor at a 60 MVA bus.
(a)
Voltage drop at the end?
(b)
Capacitor's resonant harmonic?
Check
A line of 30 Ω (CT ratio 200, VT ratio 3000), with L = 1.2 mH/km and C = 10 nF/km over 200 km.
(a)
Zone 1 setting at 80%, secondary ohms?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
Open-end Ferranti rise?
Check
A 118-bus case with 12 PV buses; and a two-bus case with X = 0.2, load 1.2 + j0.2.
(a)
Jacobian size?
(b)
Angle after Newton's first step?
(c)
Voltage after Newton's first step?
Check
A 1 pu source feeds a load at power factor 0.85 lagging through X = 0.25 pu.
(a)
What is the most it can deliver?
(b)
At what voltage?
Check
A generator rated 1 pu ( = 1.1, field limit 2 pu) runs at 0.85 pu and 1 pu.
(a)
What vars does its armature limit allow?
(b)
And its field limit?
Check
Two 100 MW units with outage rates 0.04 and 0.05 serve a 150 MW load.
(a)
What is the loss-of-load probability?
Check
A 500 MW load at power factor 0.95 is to be supplied over 300 km of line with 0.05 Ω/km per phase, losing at most 3%.
(a)
What is the lowest line voltage that meets the loss limit?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
Check
A 20 MW plant at power factor 0.7 is to be corrected to 0.98.
(a)
How large a capacitor bank?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(b)
By how much does the supply current fall?
Check
A line of X = 0.6 pu between 1 pu buses must carry 1.8 pu at an angle of no more than 40°.
(a)
What series compensation does that require?
Check
A 34.5 kV substation transformer fed from a 5000 MVA source must keep the fault level on its secondary below 2000 MVA.
(a)
What is the least transformer reactance, in per unit on 100 MVA?
Check
A breaker at a 13.8 kV bus with a 2000 MVA fault level must interrupt with an asymmetry factor of 1.15.
(a)
What symmetrical fault current must it handle?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(b)
And its asymmetrical interrupting current?
Check
A feeder carries at most 450 A of load. Its overcurrent relay picks up at 1.5 times that, through a CT with 1 A secondary rating, chosen as the smallest standard ratio of 100, 200, 400, 600, 800, 1200 or 1600 to 1 that covers the maximum load.
(a)
What primary pickup current is set?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What secondary pickup current does the relay see?
Check
A line has 45 Ω of positive-sequence impedance; CT ratio 120, VT ratio 2000. Zone 1 covers 80% and zone 2 120% of the line.
(a)
What zone 1 reach, in secondary ohms?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
And zone 2?
Check
A 5 Mvar capacitor bank at a bus with a 250 MVA fault level is to be detuned to the 4.3th harmonic.
(a)
Where would it resonate without detuning?
(b)
What series reactor, as a percentage of the capacitor's reactance, tunes it to 4.3?
Check
A feeder's far end runs 7% low at peak. A regulator at the substation steps 0.625% per tap.
(a)
How many steps up bring the far end within 1% of nominal?
Check
A 10 GW system with H = 2 s must keep ROCOF below 0.5 Hz/s after losing 2 GW.
(a)
What ROCOF does the loss cause without help?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
(b)
How much fast frequency response must act at once to meet the limit (zero if none)?
Check
A radial line of X = 0.2 pu from a 1 pu source supplies load at power factor 0.9 lagging, with a required loadability margin of 30%.
(a)
What is the most load it may carry?
Check
A unit loses 200 dollars per hour running at 500 MW through a night of off-peak prices; restarting costs 400 dollars per start plus 60 dollars per MW of minimum output to warm up.
(a)
Above how many off-peak hours is shutting down cheaper?
Check
A 345 kV line of 200 km (b = 5 µS/km) gets shunt reactors at both ends that together absorb 75% of its charging, split equally.
(a)
What rating does each end's reactor need?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
An area's tie-line flow is 50 MW from schedule, frequency is −0.04 Hz from 60, and its bias is −400 MW/0.1 Hz.
(a)
What is its area control error?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
An interconnection of 50 GW (all generation at droop 0.04, load damping D = 1.5) loses 2.5 GW.
(a)
Where does its frequency settle, relative to 60 Hz?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
What is its frequency response, in MW per 0.1 Hz (negative)?
Check
A 40 GW system's synchronous units have H = 4 s, and 0.6 of its generation is inverter-based without inertia. It loses 3 GW.
(a)
What is the initial ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
Two meters on one flow read 0.95 pu (σ = 0.01) and 1.12 pu (σ = 0.05).
(a)
What is the WLS estimate?
(b)
What is the normalized difference between the readings (above 3 suggests bad data)?
Check
A monitored line carries 0.4 pu; line k carries 0.6 pu. For a transfer between line k's ends, line k itself takes 0.6 and the monitored line 0.35.
(a)
What is the outage distribution factor?
(b)
What does the monitored line carry if line k trips?
Check
A line's PTDF for a 100 MW transaction is 0.25; it already carries 500 MW against a 600 MW rating.
(a)
What will it carry with the transaction?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
What's the largest such transaction its rating allows?
Check
A line rated 800 A at static conditions sheds 45 W/m by convection, 15 W/m by radiation and absorbs 14 W/m of sun. Measured wind raises convection 2.5 times.
(a)
What is its dynamic rating?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A 2 pu transfer splits between path A (x = 0.05 pu, rated 1 pu) and path B (x = 0.15 pu). A phase shifter on A may be used.
(a)
What does A carry naturally?
(b)
What phase shift (negative relieves A) brings A to its rating, if it's over?
Check
A remote generator priced 20 dollars per MWh sends 400 MW with losses (B = 0.0001 per MW) to a bus where congestion adds 15 dollars per MWh.
(a)
What is the receiving bus's LMP?
Check
A utility serving 20000 customers had 15000 customer interruptions in a year, averaging 120 minutes each.
(a)
What is its SAIFI?
(b)
What is its SAIDI?
Check
Inverters export 4 MW and absorb 1.5 Mvar at the end of a 12.47 kV feeder of 1 + j2 Ω.
(a)
How much do they change the voltage there?
(b)
How many vars would cancel the rise completely?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
Each phase of a balanced four-wire load draws 50 A of fundamental, 10 A of third harmonic and 15 A of fifth.
(a)
What is each phase's current THD?
(b)
What flows in the neutral?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A rectifier's valve-side line voltage is 200 kV RMS; it fires at α = 10° and carries 3 kA through a commutating reactance of 15 Ω.
(a)
What is its DC voltage?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
(b)
What power does it deliver?
Check
A 40 MW load at 0.75 lagging on a 138 kV line.
(a)
Line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Capacitor for 0.98?
(c)
Cut in line loss?
Check
A machine (30 MVA, 22 kV, X = 0.08) on a 100 MVA, 24 kV base; a transformer with R = 0.007, X = 0.05 pu at full load, 0.8 lagging.
(a)
Machine's X on the base?
(b)
Transformer regulation?
Check
A 230 kV line, = 7 m, two-conductor bundles 0.5 m apart, GMR 10 mm, radius 17 mm.
(a)
L per km?
Write units the way you normally would: 1.5 mH, 1500 µH and 0.0015 H are the same answer.
(b)
C per km?
(c)
SIL?
Check
An open 150 km, 345 kV line with B = 5 µS/km (wavelength 4940 km).
(a)
Ferranti rise?
(b)
Charging vars?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
Buses at 0.97 and 0.95 pu, 25° apart across X = 0.4; the line gets 0.3 series compensation.
(a)
Real power now?
(b)
Transfer limit with compensation?
Check
A two-bus case (X = 0.15, load 0.5 + j0.5); a 300-bus case with 30 PV buses.
(a)
Two-bus load voltage?
(b)
Unknowns in the second?
Check
A triangle ( = 0.1, = 0.15, = 0.4) with a generator j0.25 at bus 1.
(a)
PTDF of line 1–3 for a transfer 1 → 3?
(b)
?
Check
A generator with = 1 delivers 0.6 + j0.4 at 1 pu; its field limit is E = 2.3.
(a)
Power angle?
(b)
Most Q at that P?
Check
Two units (4.5, 0.003) and (6.5, 0.008) share 400 MW; separately, a binding triangle with generators at 15 and 40 dollars per MWh.
(a)
λ, dollars per MWh?
(b)
Triangle bus-3 LMP?
Check
A 30 GW system with H = 5 s loses 0.6 GW; a system with droop 0.04 and damping 0.5 loses 0.06 pu.
(a)
ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
(b)
Settling deviation in the second?
Check
A 400 MVA generator (X″ = 0.12) and transformer (X = 0.08) on the same base feed a 230 kV bus; X/R = 10 there.
(a)
Three-phase fault current?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(b)
Worst first peak?
Check
A bus with = j0.12, = j0.06.
(a)
Line-to-ground current?
(b)
Neutral reactance for 2.2 pu?
Check
A very inverse relay (dial 0.8) at 3 times pickup; a line of 90 Ω with CT ratio 400 and VT ratio 2000.
(a)
Relay time?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
Zone 1 (80%) in secondary ohms?
Check
A machine (H = 6 s) at 0.5 pu, = 1.8, zero-transfer fault cleared with the network intact.
(a)
Swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
Critical clearing angle?
(c)
Critical clearing time?
Check
Two machines (H = 4, 6 s), = 2.5; a mode at .
(a)
Swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
Halving time of the mode?
Check
A 150 MW inverter plant at a 500 MVA bus; a 100 A fundamental with 30, 15, 3 A harmonics.
(a)
SCR?
(b)
THD?
Check
An HVDC bipole's rectifiers each have 200 kV RMS on their valve sides, fire at α = 10° and carry 3 kA through = 14 Ω.
(a)
DC voltage of each pole?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
(b)
Power sent by the bipole?
Check
A line's flow is metered at both ends: 0.6 pu (σ = 0.02) and 0.62 pu (σ = 0.04), losses neglected.
(a)
Weighted least-squares estimate of the flow, in per unit?
(b)
J at the estimate?
Check
Two phases of a line carrying 0.8 pu break. Across the break = j0.5 pu and = j2 pu.
(a)
Each sequence current, in per unit?
(b)
Current in the phase still closed, in per unit?