Problem set 1: three-phase and complex power, the per-unit system, transformer models and transmission line parameters

These problems cover lessons 1 to 4: three-phase currents, losses and power-factor correction, per-unit bases and base changes, transformer tests, regulation and connections, and the inductance, capacitance and natural loading of overhead lines.

Check

A three-phase line (12 Ω per phase) carries 80 MW at 115 kV, power factor 0.95.

(a)

Line current?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

(b)

Line loss?

(c)

Vars carried?

Check

An 8 MW load at 0.7 power factor lagging, corrected to 0.97.

(a)

Capacitor needed?

Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.

(b)

Percentage cut in line loss?

Check

Bases of 10 MVA and 34.5 kV.

(a)

Base impedance?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

(b)

Base current?

Check

A machine rated 20 MVA, 13.2 kV with X = 0.08 pu; a 138 kV line of 20 Ω. System base: 100 MVA, 14.4 kV on the machine's side.

(a)

Machine's X on the system base?

(b)

Line in per unit?

Check

A generator (X'' = 0.25 pu) and transformer (X = 0.08 pu) feed a 345 kV line of j120 Ω, all on 100 MVA. A three-phase short occurs at the line's far end.

(a)

Fault current in per unit?

(b)

In kA on the line?

Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.

Check

A 25 kVA transformer's short-circuit test on its 13800 V side reads 350 V, 3 A and 400 W.

(a)

Per-unit resistance?

(b)

Per-unit reactance?

Check

A transformer with R = 0.006 pu, X = 0.05 pu at full load.

(a)

Regulation at 0.9 lagging?

(b)

Regulation at 0.9 leading?

Check

A 40 kVA transformer rewired as an autotransformer from 66 kV to 66 + 33 kV; and an 80 kW transformer with core loss 120 W and full-load copper loss 300 W, at 0.6 of full load.

(a)

Autotransformer rating?

Write units the way you normally would: 1.5 kVA, 1500 VA and 0.0015 MVA are the same answer.

(b)

Second transformer's efficiency?

Check

Phases spaced 5, 6 and 16 m; two-conductor bundles 0.4 m apart with conductor GMR 12 mm.

(a)

GMD?

Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.

(b)

Bundle GMR?

(c)

Inductance per km?

Check

Two-conductor bundles 0.6 m apart, conductor radius 12 mm, Dm = 6 m.

(a)

Capacitance per km?

Write units the way you normally would: 1.5 nF, 1500 pF and 0.0015 µF are the same answer.

(b)

Capacitance per km without bundling?

Check

A 765 kV line with L = 0.85 mH/km and C = 9.5 nF/km.

(a)

Surge impedance?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

(b)

SIL?

Check

A line's voltage rises from 69 kV to 2 times that; separately, a Y bank serves 500 kV.

(a)

Factor by which the loss falls?

(b)

Voltage across each Y unit?

Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.

Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.