S10 · Problem set 4
Problem set 4: setting up power flow, Gauss–Seidel, Newton–Raphson, the fast decoupled and DC approximations, regulating transformers and contingency analysis
These problems cover lessons 17 to 22: bus types and unknowns, exact two-bus solutions, branch flows and losses, Gauss–Seidel and Newton–Raphson steps and convergence, the DC power flow with its distribution factors, regulating transformers and phase shifters, and predicting flows after outages.
Check
A case with 118 buses: one slack, 12 PV and the rest PQ.
(a)
Unknowns?
(b)
PQ buses?
Check
A slack at 1∠0° feeds 0.6 + j0.5 pu through a lossless X = 0.1.
(a)
Load bus voltage?
(b)
Its angle?
(c)
Slack's vars?
Check
A branch 2 − j\given5 pu joins 1.01∠0° to 0.97∠−10°; a branch of R = 0.01 delivers 0.8 + j0.2 at 0.96 pu.
(a)
Real power leaving the first branch's sending end?
(b)
The second branch's loss?
Check
Gauss–Seidel and Newton on the two-bus case: X = 0.12, load 0.5 + j0.45, flat start.
(a)
Magnitude of the first Gauss–Seidel iterate?
(b)
Angle after Newton's first step?
(c)
Voltage after Newton's first step?
Check
A PV bus at 1.05 pu injects 0.4 pu into a slack at 1∠0° through X = 0.1; its generator is limited to 0.2 pu of vars.
(a)
Angle?
(b)
Vars needed to hold 1.05 pu?
(c)
Vars it actually supplies?
Check
Linear convergence at rate 0.4 from 0.03; quadratic convergence with C = 4 from 0.05.
(a)
Linear: iterations to reach 1 × 10⁻⁷?
(b)
Quadratic: error after two steps?
Check
A two-bus guess: load bus at 0.92∠−4° behind X = 0.25, load 0.9 + j0.1.
(a)
ΔP?
(b)
ΔQ?
Check
DC power flow on a 100 MVA base.
(a)
Flow on a line of x = 0.08 with 0.03 rad across it?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Angle of a bus drawing 1.3 pu radially through x = 0.08?
Check
A triangle: = 0.1, = 0.2, = 0.4 pu; a transfer of 200 MW from bus 1 to bus 3.
(a)
PTDF of line 1–3?
(b)
MW on line 2–3?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A bus with lines of x = 0.05, 0.1 and 0.4 pu; an angle difference of 20°.
(a)
Its B-matrix diagonal?
(b)
DC model's overstatement at 20°?
Check
A Newton Jacobian of size 500 with about 10 nonzeros per row.
(a)
Dense LU operation count?
(b)
Fraction of entries that are nonzero?
Check
Two parallel lines, x = 0.08 and 0.12 pu, carry 1.5 pu between two buses.
(a)
Flow on the 0.08 pu line?
(b)
Increase on the 0.12 pu line if the 0.08 pu line trips?
Check
A transfer of 1.6 pu splits between path A (x = 0.1 pu, rated 0.85 pu) and path B (x = 0.3 pu). A phase shifter can be installed on path A (100 MVA base, DC model).
(a)
Path A's flow without the shifter?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Shift that brings path A to exactly its rating?
(c)
Path B's flow with that shift?
Check
Line ℓ carries 0.4 pu and line k 0.6 pu. For a transfer between line k's ends, line k carries 0.7 of it and line ℓ carries 0.3. Line ℓ is rated 0.8 pu (100 MVA base).
(a)
Line ℓ's outage distribution factor for line k?
(b)
Line ℓ's flow after line k trips?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(c)
That flow as a percentage of line ℓ's rating?
Check
Two identical parallel transformers, each j0.06 pu, serve a load drawing 0.6 pu of reactive power at 1 pu (100 MVA base). One transformer's tap gives 4% more voltage than the other's.
(a)
Circulating current, in per unit?
(b)
Reactive power supplied by the higher-tapped transformer?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(c)
Reactive power supplied by the other one (negative means it absorbs)?
Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.
Practice
Keep practicing
15 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.