Problem set 5: synchronous generators, economic dispatch with losses, unit commitment, optimal power flow and locational prices, frequency control, and state estimation

These problems cover lessons 25 to 31: generator internal voltage, power angle and capability, equal-incremental-cost dispatch with limits, penalty factors and unit commitment, congestion and locational prices, inertia, droop and area control error, and weighted least-squares state estimation.

Check

A generator with Xs = 1.4 pu delivers 0.6 + j(0.4) pu at 1 pu.

(a)

|E|?

(b)

Power angle?

(c)

Steady-state limit at this excitation?

Check

A generator with E = 1.5 pu behind Xs = 1.1 pu on a 1 pu bus.

(a)

P at δ = 35°?

(b)

Q at δ = 35°?

(c)

Most Q at P = 0.8 if E is the field limit?

Check

Two units, b1 = 5, c1 = 0.003 and b2 = 6.5, c2 = 0.008 (costs a+bP+cP2 dollars per hour), share 300 MW.

(a)

λ, in dollars per MWh?

(b)

Unit 1's output?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(c)

Unit 2's output?

Check

A unit at 7.5 dollars per MWh with loss sensitivity 0.03; and a cheap unit pinned at 250 MW with a second unit (b = 6.5, c = 0.008) covering the rest of 550 MW.

(a)

First unit's effective incremental cost?

(b)

System λ in the second case?

Check

A 500 MW load at B, a cheap generator (10 dollars per MWh) at A behind a 250 MW line, and a costlier one (35) at B.

(a)

B's generator output?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

Total cost, dollars per hour?

(c)

Congestion rent, dollars per hour?

Check

A triangle of identical lines, generators at buses 1 (25) and 2 (55 dollars per MWh), 240 MW at bus 3, line 1–3 limited to 120 MW.

(a)

Bus 1's output?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

Bus 3's LMP?

Check

A 40 GW system with H = 6 s.

(a)

ROCOF after losing 0.6 GW?

Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.

(b)

Deficit if frequency falls at 0.3 Hz/s?

Check

Loss of 0.03 pu with droop 0.04 and load damping 1.5; a 600 MW unit at droop 0.04 during a 0.15 Hz dip.

(a)

Settling frequency deviation?

Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.

(b)

The unit's governor response?

Check

Units of 400 MW at 0.04 droop and 500 MW at 0.07 droop share 80 MW.

(a)

First unit's share?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

Frequency drop (no load damping)?

Check

An area: tie flow −40 MW off schedule, Δf = 0.04 Hz, bias −500 MW/0.1 Hz.

(a)

ACE?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

Generation change AGC will ask for?

Check

A unit with start cost 8000 dollars and no-load cost 600 dollars per hour; another with cost 300 + 6P + 0.006P² at 120 MW.

(a)

Breakeven idle time?

(b)

Second unit's hourly cost, in dollars?

(c)

Its incremental cost, dollars per MWh?

Check

A remote plant's incremental cost is 6 + 0.008P dollars per MWh, and its share of the losses is BP2 with B = 0.0003 per MW. The system λ is 12 dollars per MWh.

(a)

The plant's output?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

Its penalty factor there?

(c)

The losses it causes?