S10 · Problem set 6
Problem set 6: generator capability limits and their dependence on voltage, underexcitation limits, voltage regulators and reactive sharing, outage probabilities and loss-of-load expectation, reserve margins, lambda dispatch with limits and losses, and congested markets
These problems cover lessons 26, 33 and 34: what a generator can deliver and absorb, how voltage regulators share the vars, whether a fleet of imperfect units can be trusted to cover the peak, and the dispatch and pricing calculations of the dispatch lab.
Check
A generator rated 1 pu ( = 1.4 pu, field limit E = 2 pu) runs at 0.9 pu and 1.05 pu terminal voltage.
(a)
How many vars can it supply?
Check
A machine ( = 1.6 pu) reaches a stiff 1 pu bus through = 0.15 pu and delivers 0.8 pu.
(a)
How many vars can it absorb before the steady-state stability limit?
Check
A 250 MVA generator, rated at power factor 0.85, delivers its rated real power while the terminal voltage sags to 0.96 pu; its armature limit binds.
(a)
How many vars can it still supply?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(b)
By what percentage has its reactive capability fallen?
Check
Three equal generators with reactive droops of 2%, 5% and 6% share a 150 Mvar rise in demand.
(a)
How much does the first one take?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A proportional AVR with gain 100 holds a generator's terminal voltage; a load change would shift the uncontrolled voltage by 0.02 pu.
(a)
How much does the regulated voltage shift?
Check
6 identical units, each with forced outage rate 0.03.
(a)
What is the probability that three or more are out at once?
Check
Six 100 MW units (FOR 0.04) see 80 days a year with a 420 MW peak and the rest at 360 MW.
(a)
What LOLE do the high days contribute?
(b)
And the other days?
Check
A system of a 150 MW unit (FOR 0.05) and a 250 MW unit (FOR 0.08) serves 260 MW.
(a)
What is its loss-of-load probability?
Check
A system with 1000 MW installed and an 820 MW peak adds a 400 MW wind farm whose capacity credit is 25%.
(a)
What was its reserve margin?
(b)
What is it counting the wind at its capacity credit?
Check
Two units with incremental costs 8 + 2(0.004)P and 10 + 2(0.008)P share 700 MW; the first is limited to 300 MW.
(a)
What does the first unit produce?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A remote plant sends 300 MW with losses , B = 0.0001 per MW; the system λ is 15 dollars per MWh.
(a)
What is its penalty factor?
(b)
What incremental cost should it run at?
Check
An 18 dollars per MWh unit at A and a 40 dollars per MWh unit at B serve 500 MW at B through a 350 MW line.
(a)
What is the price at B?
(b)
What congestion rent accrues per hour?
Check
A unit costs 5000 dollars to start and loses 300 dollars per hour running at its minimum through off-peak hours.
(a)
For how many off-peak hours is it cheaper to keep it running than to shut it down and restart?
Check
A planner adds a 400 MW unit with a 10% forced outage rate to a system of eight 100 MW units with 5% outage rates. Why might that improve the loss-of-load expectation less than four more 100 MW units would?
Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.
Practice
Keep practicing
13 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.