S10 · Problem set 9
Problem set 9: Z-bus fault studies, all four fault types, sequence-to-phase conversion, fault resistance and grounding, breaker asymmetry, relay coordination, swing frequencies, equal areas, critical clearing and mode damping
These problems cover lessons 42 and 49 with the fault and stability lessons behind them: the computations a fault study and a transient stability study run, from Z-bus columns and sequence connections to relay times, swing frequencies and critical clearing.
Check
Two buses are joined by j0.1 pu and each has a generator of j0.15 pu. A bolted three-phase fault occurs at bus 1.
(a)
What fault current flows, in per unit?
(b)
What voltage does bus 2 keep?
Check
A bus has = j0.2 and = j0.05 pu.
(a)
What is its bolted single line-to-ground fault current?
(b)
What ground current does a bolted double line-to-ground fault draw?
(c)
What phase current does a line-to-line fault draw?
Check
A three-phase fault through j0.02 pu occurs at a bus whose Z-bus diagonal is j0.2 pu.
(a)
What current flows?
(b)
What voltage remains at the faulted bus?
Check
A breaker interrupts a fault with X/R = 20 (60 Hz) when its contacts part 2 cycles after the fault starts.
(a)
By what factor does the worst-case offset raise the RMS current?
Check
A 4.16 kV system with = j0.15, = j0.2 pu (100 MVA) must limit ground faults to 800 A with a neutral resistor.
(a)
What resistance does it need?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A downstream very inverse relay (dial 1) sees 5 times its pickup during a fault; the upstream very inverse relay sees 4 times its pickup and must trail it by 0.4 s.
(a)
When does the downstream relay trip?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
What time dial does the upstream relay need?
Check
A differential relay with a 40% slope sees 15 A in and 7.4 A out of its zone.
(a)
What is the ratio of operating to restraint current?
Check
A unit with H = 6 s delivers 0.6 pu with = 1.8 pu on a 60 Hz system.
(a)
What is its rotor angle?
(b)
At what frequency does it swing?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A machine with H = 6 s at 0.6 pu ( = 1.8 pu before and after) has a fault that drops its output to zero.
(a)
What is the critical clearing angle?
(b)
What is the critical clearing time?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A machine at 0.8 pu has = 2 pu before a fault, 0.4 of that during it and 0.85 of it after clearing.
(a)
Where is the post-fault unstable equilibrium?
(b)
What is the critical clearing angle?
Check
Two machines (H = 3 and 2 s, E = 1.15 pu each) are joined by 1 pu and run 15° apart, on 60 Hz.
(a)
At what frequency do they swing against each other?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
An oscillation mode sits at s⁻¹.
(a)
What is its damping ratio?
(b)
How long does its amplitude take to halve?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A zero-output fault on a machine at 0.8 pu ( = 2 pu before and after) is cleared at 65°.
(a)
How much decelerating area is left over after absorbing the accelerating area (negative if it fails)?
Check
A fault study shows a bus's line-to-ground fault current exceeds its three-phase fault current. What does that say about the bus?
Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.
Practice
Keep practicing
13 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.