S10 · Lesson 40 · Power system protection
Zones of protection, current and voltage transformers, inverse-time overcurrent relays and their coordination, distance relays and their zones, differential protection, and what makes protection selective, fast and secure
A fault must be cleared in a fraction of a second, but only the breakers nearest it should open: trip too much and a single tree branch blacks out a city; trip too little and equipment burns. Protective relays make that decision automatically from currents and voltages scaled down by instrument transformers. This lesson covers the three workhorse schemes, overcurrent, distance and differential, and the arithmetic of setting and coordinating them.
- Operating time against fault current (as a multiple M of the relay's pickup) for the three standard IEEE inverse-time overcurrent curves, at a chosen time dial.
- Inverse-time relays trip faster for bigger currents, so a relay close to a fault (seeing a large current) beats one farther upstream.
- "Extremely inverse" falls steepest, which coordinates well with fuses; the time dial shifts every curve up or down in proportion.
Predict
A feeder relay operates in 0.69 s for a 4000 A fault. The relay one breaker upstream sees the same fault current. What's the earliest it should operate?
The upstream relay is the backup. It must wait long enough for the feeder breaker to clear (a few cycles) plus margins for relay overtravel and errors: a coordination time interval of 0.2 to 0.4 s. With 0.3 s, the upstream relay should take at least 0.99 s at 4000 A, but it must still trip if the feeder breaker fails.
Name it
Principles
Protection divides the system into overlapping zones (each generator, transformer, bus and line), each with relays that open only its breakers. The goals are selectivity (only the faulted zone), speed, sensitivity (catch high-resistance faults) and security (no false trips), with backup if the primary scheme or breaker fails.
Instrument transformers
CTs step currents down, typically to 5 A or 1 A at rated primary current (a 600:5 CT turns 6000 A into 50 A). They must not saturate during faults. VTs step voltages to 115 or 120 V line to line.
Overcurrent relays
A relay picks up above a set current and operates after a time that falls with the multiple M of pickup. IEEE standard curves:
| Curve | A | B | p |
|---|---|---|---|
| Moderately inverse | 0.0515 | 0.114 | 0.02 |
| Very inverse | 19.61 | 0.491 | 2 |
| Extremely inverse | 28.2 | 0.1217 | 2 |
Coordination: at every fault current a downstream relay could see, the upstream relay must be slower by the coordination time interval.
Distance relays
On transmission lines, a relay measures the apparent impedance V/I. A fault on the line makes it fall to the impedance from the relay to the fault, proportional to distance. Zone 1 covers about 80% of the line and trips instantly; zone 2 covers about 120% with a delay of 0.3 to 0.5 s, backing up the remote end; zone 3 reaches into the next lines as remote backup. Relay settings are in secondary ohms: .
Differential protection
For transformers, generators and buses: compare the currents entering and leaving the zone. Through-current balances out; an internal fault doesn't. Percentage restraint trips only when the difference exceeds a slope (often 20 to 40%) times the through current, so CT mismatch during heavy external faults doesn't cause a false trip.
Worked example
A very inverse relay with time dial 2 sees a fault at 10 times pickup. When does it trip, and how do the other curves compare?
Show the solution
- Very inverse.
- The other curves. The moderately inverse curve gives 2.41 s and the extremely inverse 0.81 s at the same dial and multiple.
Answer it trips in 1.38 s; the moderately inverse curve would take 2.41 s and the extremely inverse 0.81 s.
Worked example
A feeder relay (very inverse, dial 1, pickup 400 A) and the upstream relay (very inverse, pickup 600 A) must coordinate with 0.3 s at 4000 A. What dial does the upstream relay need?
Show the solution
- Feeder relay. It sees M = 10 and operates in
- Upstream relay's target. It sees M = 6.67 and must take 0.989 s.
- Its dial.
- Other fault levels. Coordination must then be checked at the other fault levels too, especially the largest.
Answer a time dial of 1.05.
Worked example
A transformer differential relay has a 25% slope. During a through-fault, 10 A enters and 9.2 A leaves (CT errors); during an internal fault, 10 A enters and 2 A leaves. What does the relay do?
Show the solution
- What the relay compares. It compares the operating current |I₁ − I₂| with the restraint current (|I₁| + |I₂|)/2.
- Through-fault. 0.8 A against 9.6 A: below 25%: no trip.
- Internal fault. 8 A against 6 A: so it trips.
- Why the slope. The restraint grows with the current, so the CT mismatch that's inevitable during heavy through-faults never causes a false trip.
Answer it doesn't trip for the through-fault (8.3%) and trips for the internal fault (133%).
Check
A 400:1 CT carries 8000 A of fault current. What flows in its secondary?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
An IEEE very inverse relay with time dial 0.5 sees 5 times pickup. When does it operate?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A downstream relay operates in 0.4 s for a fault. With a coordination interval of 0.2 s, how fast may the upstream relay operate for the same fault?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A line's impedance is 60 Ω primary. With CT ratio 120 and VT ratio 3000, what's it in secondary ohms?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A 200 km line has 40 Ω of positive-sequence impedance. Zone 1 is set to 0.8 of the line. What's its reach in primary ohms?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A transformer differential relay sees 10 A in and 9.2 A out (secondary, after ratio correction) during an external fault. What's the operating current as a percentage of the restraint current?
Check
A differential relay with a 30% slope sees 10 A entering and 1 A leaving its zone (secondary, after ratio correction).
(a)
What is the operating current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What is its ratio to the restraint current (the relay trips above 30%)?
Check
An IEEE very inverse relay has time dial T and sees M times its pickup current.
Step 1
When does it operate, in seconds?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
When would an extremely inverse relay with the same dial operate?
Explain why
Why do distance relays protect only about 80% of a line instantaneously instead of all of it?
A distance relay judges where a fault is from the apparent impedance it measures, and that measurement has errors: CT and VT ratio errors, the line's impedance not being known exactly, fault resistance, and infeed from other sources. A fault just beyond the remote bus, on the next line, produces almost the same impedance as one just before it. If zone 1 reached 100%, small errors would make it trip for faults on the next line, taking out the wrong circuit. Setting it short guarantees it only ever trips for faults on its own line, and the remaining 20% is covered by zone 2 with a short delay, or by the relay at the other end, whose zone 1 covers that portion instantly.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.