S10 · Lesson 8 · Reactive power compensation
Shunt capacitors and reactors, series capacitors that shorten a line electrically, midpoint voltage support, static var compensators, STATCOMs and synchronous condensers, and how each behaves when the voltage sags
Lesson 7 showed that vars control voltage and that a line's reactance limits the power it can carry. Utilities attack both with compensation: capacitor banks that supply vars near loads, reactors that soak up the charging of lightly loaded lines, series capacitors that cancel part of a long line's reactance, and power-electronic devices that adjust their vars every cycle. They differ most in what they do during a voltage sag, exactly when they're most needed.
- The power–angle curve of a line with reactance X = 0.5 pu between two 1 pu buses, with a series capacitor cancelling a fraction k of the reactance (dashed: uncompensated).
- The peak transfer is : 40% compensation raises it from 2 to 3.33 pu, and the same power flows at a smaller angle, with more stability margin.
- Series compensation is used on long lines in the western US, Brazil and Scandinavia; too much of it can excite subsynchronous resonance with turbine shafts.
Predict
A 50 Mvar capacitor bank and a 50 Mvar STATCOM are both on a bus whose voltage sags to 0.9 pu. Which supplies more vars?
A capacitor's vars go as (its current is proportional to voltage): = 40.5 Mvar. A STATCOM is a converter that can hold its rated current down to low voltage, so its output goes as V: 45 Mvar. At 0.7 pu the gap is 24.5 against 35. Capacitors fade just when voltage support is needed most.
Name it
Shunt devices
- Capacitor banks supply vars, in switched steps, with output .
- Shunt reactors absorb vars, mainly to cancel the charging of long or lightly loaded lines (lesson 6) and keep voltages down at night.
- Static var compensators (SVC): thyristor-switched capacitors and thyristor-controlled reactors, continuously variable. At their limits they behave like a fixed capacitor, with output ∝ .
- STATCOM: a voltage-source converter that can supply its rated current at any voltage in its range, so output ∝ V, and it responds within a cycle.
- Synchronous condensers: synchronous machines without a prime mover, which also add inertia and short-circuit strength (lessons 36 and 46).
A shunt device's effect on voltage is roughly in per unit, where is the bus's short-circuit level: weak buses swing more.
Series capacitors
A capacitor in series with a line cancels part of its reactance: for compensation degree k. The transfer limit rises and the angle for a given flow falls. Typical k is 25 to 70%.
Midpoint support
Holding the voltage at the middle of a line at 1 pu (with an SVC or STATCOM) splits it into two halves of X/2. Each can carry , so the limit doubles to , reached at δ = 180° across the whole line.
Worked example
A 30 Mvar capacitor bank is switched in at a bus with a 3000 MVA short-circuit level. Estimate the voltage rise.
Show the solution
- Voltage rise. a 1% rise.
- On a weak bus. On a weak 600 MVA bus the same bank would raise the voltage 5%, which is why capacitor banks on weak systems come in small steps.
Answer about 0.01 pu, a 1% rise.
Worked example
A line has X = 0.5 pu between 1 pu buses. What series compensation gives a 3 pu transfer limit?
Show the solution
- Set the limit.
- Solve for k. so k = 33%.
- Compare with midpoint support. Midpoint voltage support alone would give 2/0.5 = 4 pu; combining them gives more still.
Answer series compensation of 33%.
Worked example
A 400 km, 500 kV line has a shunt susceptance of 5 µS/km. How many vars does it generate when lightly loaded, and what reactor rating compensates 70% of it?
Show the solution
- Line charging.
- When unloaded. All of it must go somewhere, and the line's far end rises (the Ferranti effect).
- Reactor rating. Shunt reactors, usually split between the two ends, keep the voltage within limits at light load:
- At heavy load. The line's own absorbs the rest, and some reactors are switched out.
Answer the line generates 500 Mvar, and 350 Mvar of shunt reactors compensate 70% of it.
Check
A line of X = 0.5 pu between 1 pu buses gets 0.25 series compensation. What's its new transfer limit?
Check
A 50 Mvar capacitor bank sees its bus sag to 0.7 pu. What does it supply?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A 50 Mvar STATCOM at rated current sees its bus sag to 0.7 pu. What does it supply?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A 40 Mvar shunt bank is switched in at a bus with a 500 MVA short-circuit level. Estimate the voltage change.
Check
A line of X = 0.4 pu joins buses at 1 pu, and its midpoint voltage is held at 1 pu too. What's its transfer limit?
Check
What series compensation lets a line of X = 0.4 pu between 1 pu buses reach a 3 pu transfer limit?
Check
A 345 kV line 300 km long has a shunt susceptance of 3 µS/km.
(a)
How many vars does it generate at rated voltage?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(b)
What shunt reactor rating compensates 0.7 of it?
Check
A line of reactance X joins two buses at V pu.
Step 1
What is its transfer limit with a fraction k of series compensation?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is it uncompensated, but with the midpoint held at V by a shunt device?
Explain why
Why does a series capacitor raise a line's power transfer limit while a shunt capacitor at the receiving end mostly raises voltage?
The transfer limit between two held voltages is , set by the line's series reactance. A series capacitor sits in the current's path and its negative reactance cancels part of the line's, so the effective X falls and the limit rises in proportion, at every load. A shunt capacitor at the end leaves the series reactance unchanged; it supplies vars locally so the line doesn't have to carry them, which raises the receiving voltage and moves the nose of the P–V curve outward. It helps a load whose voltage was sagging, but it can't lift the angle-based limit between two buses whose voltages are already held.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.