S10 · Lesson 21 · Regulating transformers in the power flow
Tap changers that push reactive power and phase shifters that push real power, their entries in the bus admittance matrix, circulating current between parallel paths, taps and angles as power-flow unknowns, and the studies planners run with them
Two identical 100 MVA transformers, each with 8% reactance, run in parallel at a substation. Someone left one of them on a tap that gives 4% more voltage than the other. With no load on the station at all, each transformer carries 25 Mvar, warming both and serving nobody. Where does that power come from, and how do operators use the same effect on purpose?
- Two parallel paths join bus 1 to bus 2: path A with reactance and a phase-shifting transformer, path B with . A transfer P flows from bus 1 to bus 2 (DC power flow, 100 MVA base).
- The plot shows the flow on each path against the phase shift φ the transformer adds to path A. Without it, the transfer splits inversely with reactance.
- The shifter adds the same circulating flow to path A and takes it from path B, whatever the transfer. Move P and the lines shift up and down together; move φ and power moves from one path to the other.
Predict
An operator wants to move real power from an overloaded line onto a parallel one. Which device does the job?
Real power across a reactance follows the angle difference (lesson 7), so a phase shifter that changes the angle driving one path moves real power between paths. A tap changer inserts a voltage in phase with the bus voltage, and across reactances that drives reactive current: it moves vars, and barely touches megawatts.
Name it
Two kinds of regulators
A magnitude regulator (an on-load tap changer, or LTC) changes the turns ratio in small steps, typically ±10% in 32 steps of 0.625%. It holds a bus voltage as load changes, and it pushes reactive power toward the side it raises. A phase-angle regulator adds a voltage in quadrature, taken from another phase's winding, which shifts the angle by a few degrees to tens of degrees. It controls real power on its path.
In the bus admittance matrix
Lesson 10 put a real tap a:1 on bus i's side into . A complex ratio covers both kinds:
where Δ marks what the transformer adds to a diagonal entry.
With a real a the matrix stays symmetric. A phase shift makes , so the matrix is no longer symmetric and no passive circuit of branches can represent it.
Circulating current
In a loop of parallel paths, a regulator in one path acts like a small voltage source ΔV inserted in the loop. By superposition its effect is a current that circulates around the loop, added to the share of the load each path would carry anyway. A tap difference of inserts , in phase with V; driven through reactances, that current lags by 90° and is reactive. A phase shift φ inserts , and its current is in phase with V: real power. In the DC power flow the shifted path's flow becomes , and the circulating flow is .
Regulators as power-flow unknowns
A tap can be a fixed input to the power flow. Or the program can hold the regulated bus's voltage at its setpoint and solve for the tap, which takes that voltage's place among the unknowns, with and columns in the Jacobian. Real taps move in steps, so programs usually adjust them in an outer loop between Newton iterations, round to the nearest step and use a deadband so they don't hunt. A phase shifter can likewise hold its path's flow at a setpoint, with its angle as the unknown.
Power-flow studies
Planners run power flows for peak and light load, for each outage they plan for, and for future years' generation and load. They look for lines above their ratings, voltages outside about 0.95 to 1.05 pu, and generators near their reactive limits, and they test fixes: new lines, capacitors, regulator settings. One known hazard is in voltage collapse. As voltage sags, LTCs raise distribution voltage to restore load power, which draws more current through the weakened network and lowers transmission voltage further. Protection schemes block tap changes when transmission voltage falls too far.
Worked example
Two parallel transformers, each j0.08 pu, feed a load of 1.0 + j0.5 pu held at 1 pu. Transformer A's tap gives 4% more voltage than B's. How do they share the load?
Show the solution
- Matched taps. By superposition, each would carry half the load, 0.5 − j0.25 pu of current, if their taps matched.
- Circulating current. The 4% difference inserts about 0.04 pu of voltage in the loop of the two reactances, driving
- Add it in. It adds to A's current and subtracts from B's: A carries 0.5 − j0.5 and B carries 0.5 − j0.
- Exact solution. Solving the exact model with the 1.04 ratio gives A 0.510 − j0.500 and B 0.490 + j0.000, with the sending bus at 1.0008 pu.
- Read the result. Transformer A supplies all of the load's reactive power and B none, and A runs at 0.71 pu of current while B runs at 0.49.
- At no load. In the hook's no-load case the circulating 0.25 pu is all there is: 25 Mvar out of one transformer and back through the other.
Answer A carries 0.510 − j0.500 pu (0.71 pu of current, all of the load's vars) and B carries 0.490 pu (0.49 pu, no vars).
Worked example
A 1.5 pu transfer splits between path A (x = 0.1 pu, rated 0.8 pu) and path B (x = 0.2 pu). What phase shift on path A keeps it within its rating?
Show the solution
- Without a shifter. 25% over its rating.
- Shift needed. The shifter must take 0.2 pu off it:
- New flows. Path A then carries 0.8 pu and path B 0.7 pu. The total is unchanged; the shifter only redirects it.
- If B is near its limit too. Then the transfer itself would have to be reduced.
Answer a shift of −3.44° (−0.06 rad), leaving 0.8 pu on path A and 0.7 pu on path B.
Worked example
A phase-shifting transformer of x = 0.1 pu shifts by 10°. What entries does it add to ?
Show the solution
- The branch. Here y = −j10 and .
- Diagonal entries. and .
- Off-diagonal entries.
- No longer symmetric. The off-diagonal entries differ, so is no longer symmetric: no network of ordinary branches behaves like a phase shifter, which is why it can push power against the natural split.
Answer −j10 on both diagonals, at and at .
Check
Two parallel transformers with reactances j0.06 and j0.12 pu have taps 4% apart. About how much current circulates between them, in per unit?
Check
A phase shifter adds 5° to a path of x = 0.05 pu, in parallel with a path of x = 0.3 pu. How much real power does it move between them (100 MVA base)?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A transfer of 1.5 pu splits between path A (x = 0.1 pu, rated 0.75 pu) and path B (x = 0.3 pu). What phase shift on path A brings it to exactly its rating?
Check
A transformer of reactance j0.05 pu has a tap a = 0.975 (a:1) on bus i's side. What's the magnitude of its contribution to ?
Check
A tap changer covers ±10% in 32 steps. How many steps up does it take to raise a bus voltage by at least 3.5%?
Check
A transformer of reactance 0.05 pu joins two stiff 1 pu buses whose angles are equal. Its tap is raised to give 1.04 times the voltage toward bus 2. About how much reactive power flows into bus 2 (100 MVA base)?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A phase shifter of x = 0.1 pu shifts by 5°.
(a)
What is the magnitude of its off-diagonal entries?
(b)
What is the angle of , for the shift on bus i's side?
Check
A transformer of reactance x has a real tap a:1 on bus i's side.
Step 1
What susceptance magnitude does it add to ?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is ?
Step 3
What does it add to ?
Explain why
Why does a tap changer move reactive power while a phase shifter moves real power?
Both act like a small voltage inserted in series with the path, and the extra current that voltage drives around a loop flows through reactance, so it lags the inserted voltage by 90°. A tap changer's inserted voltage is in phase with the bus voltage, so the extra current lags the bus voltage by 90°: it is reactive current, and the path carries more vars. A phase shifter inserts a voltage at 90° to the bus voltage, so the extra current, lagging that by another 90°, is in phase with or opposite to the bus voltage: real current, and real power moves between paths. That's lesson 7's decoupling again: angle differences drive real power and magnitude differences drive reactive power across reactive networks.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.