S10 · Lesson 21 · Regulating transformers in the power flow

Tap changers that push reactive power and phase shifters that push real power, their entries in the bus admittance matrix, circulating current between parallel paths, taps and angles as power-flow unknowns, and the studies planners run with them

Two identical 100 MVA transformers, each with 8% reactance, run in parallel at a substation. Someone left one of them on a tap that gives 4% more voltage than the other. With no load on the station at all, each transformer carries 25 Mvar, warming both and serving nobody. Where does that power come from, and how do operators use the same effect on purpose?

  • Two parallel paths join bus 1 to bus 2: path A with reactance xA and a phase-shifting transformer, path B with xB. A transfer P flows from bus 1 to bus 2 (DC power flow, 100 MVA base).
  • The plot shows the flow on each path against the phase shift φ the transformer adds to path A. Without it, the transfer splits inversely with reactance.
  • The shifter adds the same circulating flow φ/(xA+xB) to path A and takes it from path B, whatever the transfer. Move P and the lines shift up and down together; move φ and power moves from one path to the other.

Predict

An operator wants to move real power from an overloaded line onto a parallel one. Which device does the job?

Name it

Two kinds of regulators

A magnitude regulator (an on-load tap changer, or LTC) changes the turns ratio in small steps, typically ±10% in 32 steps of 0.625%. It holds a bus voltage as load changes, and it pushes reactive power toward the side it raises. A phase-angle regulator adds a voltage in quadrature, taken from another phase's winding, which shifts the angle by a few degrees to tens of degrees. It controls real power on its path.

In the bus admittance matrix

Lesson 10 put a real tap a:1 on bus i's side into Ybus. A complex ratio a=|a|ejφ covers both kinds:

ΔYii=y|a|2,Yij=−ya*,Yji=−ya,ΔYjj=y

where Δ marks what the transformer adds to a diagonal entry.

With a real a the matrix stays symmetric. A phase shift makes Yij≠Yji, so the matrix is no longer symmetric and no passive circuit of branches can represent it.

Circulating current

In a loop of parallel paths, a regulator in one path acts like a small voltage source ΔV inserted in the loop. By superposition its effect is a current ΔV/Zloop that circulates around the loop, added to the share of the load each path would carry anyway. A tap difference of Δt inserts ΔV≈ΔtV, in phase with V; driven through reactances, that current lags by 90° and is reactive. A phase shift φ inserts ΔV≈jφV, and its current is in phase with V: real power. In the DC power flow the shifted path's flow becomes (θi−θj+φ)/xA, and the circulating flow is φ/(xA+xB).

Regulators as power-flow unknowns

A tap can be a fixed input to the power flow. Or the program can hold the regulated bus's voltage at its setpoint and solve for the tap, which takes that voltage's place among the unknowns, with ∂P/∂t and ∂Q/∂t columns in the Jacobian. Real taps move in steps, so programs usually adjust them in an outer loop between Newton iterations, round to the nearest step and use a deadband so they don't hunt. A phase shifter can likewise hold its path's flow at a setpoint, with its angle as the unknown.

Power-flow studies

Planners run power flows for peak and light load, for each outage they plan for, and for future years' generation and load. They look for lines above their ratings, voltages outside about 0.95 to 1.05 pu, and generators near their reactive limits, and they test fixes: new lines, capacitors, regulator settings. One known hazard is in voltage collapse. As voltage sags, LTCs raise distribution voltage to restore load power, which draws more current through the weakened network and lowers transmission voltage further. Protection schemes block tap changes when transmission voltage falls too far.

Worked example

Two parallel transformers, each j0.08 pu, feed a load of 1.0 + j0.5 pu held at 1 pu. Transformer A's tap gives 4% more voltage than B's. How do they share the load?

Show the solution
  1. Matched taps. By superposition, each would carry half the load, 0.5 − j0.25 pu of current, if their taps matched.
  2. Circulating current. The 4% difference inserts about 0.04 pu of voltage in the loop of the two reactances, driving Ic=0.04/(j0.16)=−j0.25pu
  3. Add it in. It adds to A's current and subtracts from B's: A carries 0.5 − j0.5 and B carries 0.5 − j0.
  4. Exact solution. Solving the exact Ybus model with the 1.04 ratio gives A 0.510 − j0.500 and B 0.490 + j0.000, with the sending bus at 1.0008 pu.
  5. Read the result. Transformer A supplies all of the load's reactive power and B none, and A runs at 0.71 pu of current while B runs at 0.49.
  6. At no load. In the hook's no-load case the circulating 0.25 pu is all there is: 25 Mvar out of one transformer and back through the other.

Answer A carries 0.510 − j0.500 pu (0.71 pu of current, all of the load's vars) and B carries 0.490 pu (0.49 pu, no vars).

Worked example

A 1.5 pu transfer splits between path A (x = 0.1 pu, rated 0.8 pu) and path B (x = 0.2 pu). What phase shift on path A keeps it within its rating?

Show the solution
  1. Without a shifter. PA=1.5×0.2/0.3=1.0pu 25% over its rating.
  2. Shift needed. The shifter must take 0.2 pu off it: ϕ/(xA+xB)=−0.2ϕ=−0.06rad=−3.44°
  3. New flows. Path A then carries 0.8 pu and path B 0.7 pu. The total is unchanged; the shifter only redirects it.
  4. If B is near its limit too. Then the transfer itself would have to be reduced.

Answer a shift of −3.44° (−0.06 rad), leaving 0.8 pu on path A and 0.7 pu on path B.

Worked example

A phase-shifting transformer of x = 0.1 pu shifts by 10°. What entries does it add to Ybus?

Show the solution
  1. The branch. Here y = −j10 and a=ej10°.
  2. Diagonal entries. ΔYii=y/|a|2=−j10 and ΔYjj=−j10.
  3. Off-diagonal entries. Yij=−y/a*=j10ej10°=10∠100°Yji=−y/a=10∠80°
  4. No longer symmetric. The off-diagonal entries differ, so Ybus is no longer symmetric: no network of ordinary branches behaves like a phase shifter, which is why it can push power against the natural split.

Answer −j10 on both diagonals, 10∠100° at Yij and 10∠80° at Yji.

Check

Two parallel transformers with reactances j0.06 and j0.12 pu have taps 4% apart. About how much current circulates between them, in per unit?

Check

A phase shifter adds 5° to a path of x = 0.05 pu, in parallel with a path of x = 0.3 pu. How much real power does it move between them (100 MVA base)?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

Check

A transfer of 1.5 pu splits between path A (x = 0.1 pu, rated 0.75 pu) and path B (x = 0.3 pu). What phase shift on path A brings it to exactly its rating?

Check

A transformer of reactance j0.05 pu has a tap a = 0.975 (a:1) on bus i's side. What's the magnitude of its contribution to Yii?

Check

A tap changer covers ±10% in 32 steps. How many steps up does it take to raise a bus voltage by at least 3.5%?

Check

A transformer of reactance 0.05 pu joins two stiff 1 pu buses whose angles are equal. Its tap is raised to give 1.04 times the voltage toward bus 2. About how much reactive power flows into bus 2 (100 MVA base)?

Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.

Check

A phase shifter of x = 0.1 pu shifts by 5°.

(a)

What is the magnitude of its off-diagonal Ybus entries?

(b)

What is the angle of Yij, for the shift on bus i's side?

Check

A transformer of reactance x has a real tap a:1 on bus i's side.

Step 1

What susceptance magnitude does it add to Yii?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why does a tap changer move reactive power while a phase shifter moves real power?