S10 · Lesson 9 · Surges, traveling waves and HVDC transmission

Lightning and switching surges as waves on a lossless line, reflection at open, shorted and matched ends, junctions with cables and other lines, lattice diagrams, closing resistors and surge arresters, and direct-current transmission with line-commutated converters

A 20 kA lightning stroke hits a phase conductor of a 230 kV line. The current splits, 10 kA running each way, and each half is a wave of current that the line can only carry with a wave of voltage beside it: 10 kA times the line's 400 Ω surge impedance is 4 MV, about five times what the insulators can hold. Lines are shielded against exactly this. But surges also start inside the system, every time a breaker closes onto a long line. What happens when such a wave reaches a transformer at the far end, and why do the arresters sit right at the transformer's terminals?

  • A lossless line is energized at t = 0 by a step of 1 pu through a source resistance Rs and ends in a resistance R. Time is in units of the one-way travel time T, and both resistances are in units of the line's surge impedance Zc.
  • The plot is the voltage at the receiving end. It changes only when a wave arrives, at T, 3T, 5T and so on, and climbs or rings toward the dashed steady value R/(R+Rs).
  • Set Rs near 0 and R large (an unloaded line closed from a stiff source): the end jumps to nearly 2 pu and rings. Set Rs=Zc (a closing resistor): one step to the final value.

Predict

A 300 kV surge travels along a 400 Ω line and reaches a breaker that is open. What voltage appears across the open contacts' line side?

Name it

Waves on a lossless line

For fast events a line is well described by its series inductance L and shunt capacitance C per meter alone. The telegrapher's equations ∂v/∂x=−L∂i/∂t and ∂i/∂x=−C∂v/∂t combine into a wave equation whose solutions are any shape moving either way, v=f(x−ut)+g(x+ut), at

u=1LC,Zc=LC

A forward wave carries current i+=v+/Zc, and a backward wave i−=−v−/Zc (current measured in the forward direction). Overhead lines run near the speed of light, about 300 m/µs, with Zc of 300 to 500 Ω. Cables have far more capacitance per meter: about half that speed and 30 to 60 Ω.

Reflections

Where a wave meets a resistance ZR, the voltage and current there must satisfy v=ZRi. That needs a reflected wave of

ρ=ZR−ZcZR+Zc

times the incident voltage. Current reflects with −ρ. An open end has ρ = 1, a short −1, and a line ended in Zc has no reflection at all. The voltage passed on is the sum of incident and reflected, (1+ρ) times the incident wave. At a junction, ZR is whatever the wave sees beyond it: a cable's Zc, or several lines in parallel.

At the sending end a source of resistance Rs first launches VZc/(Rs+Zc), and returning waves reflect from it with ρs=(Rs−Zc)/(Rs+Zc). A lattice diagram keeps track of the bouncing: time runs down the page, each wave is a slanted line, and each terminal's voltage is the running sum of the waves arriving and leaving there.

Surges in practice

Up to about 230 kV, lightning sets the insulation level of lines and equipment. Shield wires above the phases take most strokes, and towers carry the current to ground. Above about 700 kV, switching surges matter more. Closing a breaker onto an unloaded line from a stiff source doubles the voltage at the open far end, and charge trapped on the line from an earlier opening can push it toward 3 pu. Closing resistors briefly put about Zc in series so the first wave is half size and is absorbed when it returns. Surge arresters, today blocks of zinc oxide, conduct almost nothing at normal voltage and heavily above a set level. They sit at transformer terminals because that's where an arriving surge doubles. A device's basic insulation level (BIL) is the crest of a standard 1.2/50 µs impulse it must withstand.

Direct-current transmission

A line-commutated converter is a six-pulse thyristor bridge. With the thyristors fired at a delay angle α after their natural turn-on and a commutating reactance Xc per phase, its DC voltage is

Vd=32πVLLcos⁡α−3πXcId

where VLL is the RMS line voltage on the converter's AC side and 32/π≈1.35. The rectifier runs at small α. The inverter at the other end runs past 90°, which makes Vd negative there, so power flows from the AC system into the DC line at one end and out at the other. Both ends draw reactive power, roughly half the DC power, which shunt capacitors and filters supply, and they put harmonics of order 6k ± 1 into the AC system.

DC wins for long overhead links (a break-even near 600 to 800 km, set by converter cost against line savings), for undersea and underground cables (an AC cable's charging current uses up its rating within about 100 km), and for ties between grids that aren't synchronized. Its flow is set by the converters' controls rather than by network impedances.

Worked example

An 800 kV surge on an overhead line (Zc = 400 Ω) reaches the junction with an underground cable (Zc = 40 Ω). What enters the cable, and what goes back?

Show the solution
  1. Reflection coefficient. The wave sees the cable's 40 Ω: ρ=40−40040+400=−0.818
  2. Reflected wave. This travels back up the line: Vr=800×(−0.818)=−655kV
  3. Transmitted wave. This enters the cable: Vt=800(1+ρ)=800×0.182=145kV
  4. Check with currents. The incident wave carries 800/400 = 2 kA, and the reflected one 1.64 kA forward (current reflects with −ρ), so 3.64 kA enters the cable.
  5. Compare with the cable. The transmitted voltage drives the same current through 40 Ω: It=Vt/40Ω=3.64kA
  6. What it means. A short cable section at a substation entrance knocks a surge down hard, though the wave then doubles when it reaches an open end of the cable.

Answer 145 kV enters the cable, and −655 kV travels back up the line.

Worked example

A breaker closes a stiff 1 pu source onto a 300 km unloaded line (wave speed 295 km/ms). What happens at the far end, and what does a closing resistor equal to Zc do?

Show the solution
  1. Travel time. T=300/295=1.02ms
  2. Reflection coefficients. With no source resistance, ρs=−1, and the open end has ρ = +1.
  3. First arrival. The first 1 pu wave reaches the far end at T and doubles it to 2 pu.
  4. The trip back. Its reflection returns at 2T and reflects from the source as −1 pu, which arrives at the far end at 3T and takes the end back to 0.
  5. It repeats. On a lossless line this repeats: 2, 0, 2, 0 pu every 2T. Losses damp it in practice, but the 2 pu crest is real.
  6. With a closing resistor. With a resistor of Zc in series, the source launches only 0.5 pu. It doubles to 1 pu at the far end.
  7. Nothing comes back. The reflection returns and meets ρs=0 at the source, so the end steps once to its final value. The resistor is shorted out a few milliseconds later.

Answer without the resistor the far end jumps to 2 pu and swings between 2 and 0 pu every 2T; with a resistor of Zc it steps once to 1 pu and stays there.

Worked example

A rectifier's valve-side line voltage is 200 kV RMS. It fires at α = 15° and carries 2 kA through a commutating reactance of 10 Ω. Find its DC voltage and the power one pole sends.

Show the solution
  1. Ideal DC voltage. Vd0=1.3505×200=270.1kV
  2. Firing delay. It reduces that to Vd0cos⁡α=270.1cos⁡15°=260.9kV
  3. Commutation overlap. It costs ΔV=(3/π)(10)(2000)=19.1kV leaving Vd = 241.8 kV.
  4. Power per pole. P=241.8kV×2kA=484MW A bipole, one pole positive and one negative, sends twice that over two conductors.

Answer Vd = 241.8 kV, and one pole sends 484 MW.

Worked example

Surges reach a transformer (BIL 1300 kV) with fronts rising at 1000 kV/µs. Its arrester clamps at 800 kV, and a 20% margin is wanted. How far from the transformer may the arrester sit?

Show the solution
  1. How the voltage builds. The voltage at the transformer exceeds the arrester's by about twice the front's rise during the travel time from arrester to transformer: Vt=Va+2Sd/v
  2. Allowed voltage. With the 20% margin: Vt≤1300/1.2=1083kV
  3. Solve for the distance. With v = 300 m/µs: 2×1000×d/300≤283d≤42.5m
  4. In practice. That's why arresters are mounted at the transformer's bushings, not at the substation fence.

Answer no more than 42.5 m from the transformer.

Check

An overhead line has L = 1 mH/km and C = 9 nF/km. What's its surge impedance?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

Check

How long does a surge take to travel 200 km along a line with L = 0.9 mH/km and C = 12 nF/km?

Write units the way you normally would: 1.5 µs, 1500 ns and 0.0015 ms are the same answer.

Check

A line with Zc = 300 Ω ends in 200 Ω. What's the voltage reflection coefficient there?

Check

A 600 kV surge arrives at a substation bus where the line continues into 2 other lines, all with the same surge impedance. What voltage leaves along each of them?

Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.

Check

A 20 kA stroke hits a phase conductor of a line with Zc = 300 Ω. What's the voltage of the surge on each side?

Write units the way you normally would: 1.5 MV, 1500 kV and 0.0015 GV are the same answer.

Check

A 1 pu source with 100 Ω of internal resistance is switched onto an unloaded line with Zc = 300 Ω. What's the far end's voltage, in per unit, when the first wave arrives?

Check

A rectifier has 200 kV RMS on its valve side, fires at α = 10° and carries 3 kA through Xc = 12 Ω. What's its DC voltage?

Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.

Check

Equipment with a BIL of 1050 kV is protected by an arrester clamping at 900 kV; surges rise at 2000 kV/µs and travel at 300 m/µs. A margin of 1.15 is wanted.

(a)

How far from the equipment may the arrester be?

Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.

Check

A surge of V kV on a line of surge impedance Z reaches a termination of R ohms.

Step 1

What is the voltage reflection coefficient?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why does a surge double when it reaches an open breaker or a transformer, and how does that decide where arresters go?

Practice

Keep practicing

13 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.