S10 · Lesson 37 · Symmetrical components

Splitting any set of three unbalanced phasors into positive-, negative- and zero-sequence sets, the operator a and the transformation matrix, sequence impedances of lines, machines and transformers, and why a delta winding blocks zero-sequence current

Per-phase analysis works only when the three phases are balanced. A single line touching ground isn't. In 1918 Charles Fortescue showed that any three unbalanced phasors are the sum of three balanced sets: one rotating in the normal order, one in reverse, and one with all three phases in step. Each set sees its own impedance and, in a symmetrical network, doesn't interact with the others. That turns an unbalanced three-phase problem into three balanced single-phase ones, and it's how every relay and fault program handles unbalance.

  • Three phase voltages with phase a fixed at 1∠0°, and phase b's magnitude and phase c's angle adjustable, together with their positive-, negative- and zero-sequence components (computed with a=1∠120°).
  • With balanced phases, only the positive sequence is present. Sag phase b and both a negative- and a zero-sequence component appear.
  • The negative-sequence share, |V2|/|V1|, is the voltage unbalance that heats induction motors: a few percent is enough to matter.

Predict

A single-phase load is connected between phases a and b, drawing Ia=10 A and Ib=−10 A, with Ic=0. How big are its sequence currents?

Name it

The transformation

With a=1∠120°=−12+j32 (a3=1, 1+a+a2=0):

(VaVbVc)=(1111a2a1aa2)(V0V1V2),(V0V1V2)=13(1111aa21a2a)(VaVbVc)

The positive sequence (1) has phases in the order a, b, c; the negative sequence (2) in the order a, c, b; the zero sequence (0) has all three equal. The neutral current is In=Ia+Ib+Ic=3I0.

Sequence impedances

Each component sees its own network:

  • Lines: Z1=Z2; Z0 two to four times larger, because zero-sequence current returns through the ground and ground wires.
  • Generators: Z1 is X″ for faults; Z2≈X′′; Z0 small; a neutral grounding impedance Zn appears as 3Zn in the zero-sequence network only.
  • Transformers: Z1=Z2 = leakage impedance; the zero-sequence path depends on the connection. A grounded Y passes zero-sequence current into its winding; a Δ winding circulates it internally but no zero-sequence current leaves on its lines; an ungrounded Y blocks it entirely.

Phase shifts

A Y–Δ transformer shifts positive-sequence quantities by +30° (high side leading, US standard) and negative-sequence quantities by −30°.

Worked example

Phase currents are 100∠0°, 80∠−120° and 90∠120° A. Find the sequence components and the neutral current.

Show the solution
  1. Zero sequence. I0=13(100+80∠−120°+90∠120°)=5.77∠30°A
  2. Positive and negative sequences. I1=90∠0°AI2=5.77∠−30°A
  3. Neutral current. In=3|I0|=17.3A even though no phase is far from its share.

Answer I0=5.77∠30° A, I1=90∠0° A and I2=5.77∠−30° A, and the neutral carries 17.3 A.

Worked example

Phase b's voltage sags to 0.9 pu with angles still 120° apart. How much negative-sequence unbalance results?

Show the solution
  1. The phasors. Here Vb=0.9a2 and Vc=a.
  2. Positive sequence. V1=(1+0.9a3+a3)/3=(1+0.9+1)/3=0.967pu
  3. Negative sequence. V2=(1+0.9a4+a2)/3=(1+0.9a+a2)/3=−0.1a/3 magnitude 0.033 pu.
  4. Unbalance. V2/V1=0.033/0.967=3.4%
  5. Why it matters. Motor standards recommend derating above 1%, because negative-sequence voltage drives currents at nearly twice line frequency in the rotor.

Answer 3.4% negative-sequence unbalance.

Worked example

A single-phase load draws 300 A from phase a of a four-wire system, with phases b and c unloaded. Find the sequence currents and the neutral current.

Show the solution
  1. Sequence currents. With Ia = 300 A and Ib=Ic=0, each sequence component is Ia/3=100A so I0, I1 and I2 are all 100 A, in phase with Ia.
  2. Neutral current. In=3I0=300A the whole load current returning.
  3. What it means. A single-phase load is one-third positive sequence, the part a balanced system can use, and two-thirds unbalance.

Answer I0, I1 and I2 are each 100 A, in phase with Ia, and the neutral carries 300 A.

Check

A line-to-line load draws 20 A from phase a and returns it on phase b. How big is its positive-sequence current?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

Phase currents are 100∠0°, 70∠−120° and 110∠120° A. What's the neutral current?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

For the same currents, what's the positive-sequence magnitude?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

Phase b's voltage sags to 0.9 pu while phases a and c stay at 1 pu, all 120° apart. What's the negative-sequence unbalance |V2|/|V1|?

Check

A voltage has V1 = 1 pu, V2 = 0.3 pu (both at 0° in phase a) and no zero sequence. What's the magnitude of phase b?

Check

A negative-sequence voltage sits at 0° on the low side of a standard Y–Δ transformer. At what angle does it appear on the high side?

Check

A single-phase load draws 300 A from phase a only of a four-wire system.

(a)

What is the positive-sequence current?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

(b)

What flows in the neutral?

Check

Phase currents of magnitudes A, B and C sit at the nominal angles 0°, −120° and 120°.

Step 1

What is the positive-sequence magnitude?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why does no zero-sequence current flow in the lines on the delta side of a transformer?

Practice

Keep practicing

10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.