S10 · Lesson 37 · Symmetrical components
Splitting any set of three unbalanced phasors into positive-, negative- and zero-sequence sets, the operator a and the transformation matrix, sequence impedances of lines, machines and transformers, and why a delta winding blocks zero-sequence current
Per-phase analysis works only when the three phases are balanced. A single line touching ground isn't. In 1918 Charles Fortescue showed that any three unbalanced phasors are the sum of three balanced sets: one rotating in the normal order, one in reverse, and one with all three phases in step. Each set sees its own impedance and, in a symmetrical network, doesn't interact with the others. That turns an unbalanced three-phase problem into three balanced single-phase ones, and it's how every relay and fault program handles unbalance.
- Three phase voltages with phase a fixed at 1∠0°, and phase b's magnitude and phase c's angle adjustable, together with their positive-, negative- and zero-sequence components (computed with ).
- With balanced phases, only the positive sequence is present. Sag phase b and both a negative- and a zero-sequence component appear.
- The negative-sequence share, , is the voltage unbalance that heats induction motors: a few percent is enough to matter.
Predict
A single-phase load is connected between phases a and b, drawing A and A, with . How big are its sequence currents?
= 0, and = , magnitude = 5.77 A, with the same. A line-to-line load is half positive and half negative sequence, which is why large single-phase loads unbalance the voltages seen by three-phase motors nearby.
Name it
The transformation
With (, ):
The positive sequence (1) has phases in the order a, b, c; the negative sequence (2) in the order a, c, b; the zero sequence (0) has all three equal. The neutral current is .
Sequence impedances
Each component sees its own network:
- Lines: ; two to four times larger, because zero-sequence current returns through the ground and ground wires.
- Generators: is X″ for faults; ; small; a neutral grounding impedance appears as in the zero-sequence network only.
- Transformers: = leakage impedance; the zero-sequence path depends on the connection. A grounded Y passes zero-sequence current into its winding; a Δ winding circulates it internally but no zero-sequence current leaves on its lines; an ungrounded Y blocks it entirely.
Phase shifts
A Y–Δ transformer shifts positive-sequence quantities by +30° (high side leading, US standard) and negative-sequence quantities by −30°.
Worked example
Phase currents are 100∠0°, 80∠−120° and 90∠120° A. Find the sequence components and the neutral current.
Show the solution
- Zero sequence.
- Positive and negative sequences.
- Neutral current. even though no phase is far from its share.
Answer A, A and A, and the neutral carries 17.3 A.
Worked example
Phase b's voltage sags to 0.9 pu with angles still 120° apart. How much negative-sequence unbalance results?
Show the solution
- The phasors. Here and .
- Positive sequence.
- Negative sequence. magnitude 0.033 pu.
- Unbalance.
- Why it matters. Motor standards recommend derating above 1%, because negative-sequence voltage drives currents at nearly twice line frequency in the rotor.
Answer 3.4% negative-sequence unbalance.
Worked example
A single-phase load draws 300 A from phase a of a four-wire system, with phases b and c unloaded. Find the sequence currents and the neutral current.
Show the solution
- Sequence currents. With = 300 A and , each sequence component is so , and are all 100 A, in phase with .
- Neutral current. the whole load current returning.
- What it means. A single-phase load is one-third positive sequence, the part a balanced system can use, and two-thirds unbalance.
Answer , and are each 100 A, in phase with , and the neutral carries 300 A.
Check
A line-to-line load draws 20 A from phase a and returns it on phase b. How big is its positive-sequence current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Phase currents are 100∠0°, 70∠−120° and 110∠120° A. What's the neutral current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
For the same currents, what's the positive-sequence magnitude?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Phase b's voltage sags to 0.9 pu while phases a and c stay at 1 pu, all 120° apart. What's the negative-sequence unbalance ?
Check
A voltage has = 1 pu, = 0.3 pu (both at 0° in phase a) and no zero sequence. What's the magnitude of phase b?
Check
A negative-sequence voltage sits at 0° on the low side of a standard Y–Δ transformer. At what angle does it appear on the high side?
Check
A single-phase load draws 300 A from phase a only of a four-wire system.
(a)
What is the positive-sequence current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What flows in the neutral?
Check
Phase currents of magnitudes A, B and C sit at the nominal angles 0°, −120° and 120°.
Step 1
What is the positive-sequence magnitude?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is the zero-sequence magnitude?
Step 3
And the negative-sequence magnitude?
Explain why
Why does no zero-sequence current flow in the lines on the delta side of a transformer?
Zero-sequence currents are equal in all three phases at every instant. On a delta side, each line current is the difference between two winding currents, so three equal winding currents produce line currents of exactly zero: they circulate around the delta instead. If the other side is a grounded Y carrying zero-sequence current, the delta winding supplies the matching ampere-turns internally, but nothing leaves on its lines. That's why a grounded-Y–delta transformer isolates the ground faults on one side from the zero-sequence network on the other, and why it's the standard generator step-up connection.