S10 · Lesson 36 · Symmetrical faults
Three-phase short circuits, the subtransient, transient and steady-state currents of a faulted generator, the DC offset and asymmetrical peak, short-circuit MVA, fault calculations with the bus impedance matrix, and breaker ratings
When lightning flashes over an insulator or a tree falls across a line, currents ten to twenty times normal flow until a breaker opens, a few cycles later. The breaker has to survive and interrupt that current, the bus bars have to survive its magnetic forces, and the protection has to see it and act. A three-phase fault is the rarest kind, but it's usually the most severe, and because it's balanced it can be computed with the per-phase tools already in hand.
- The current in one phase after a fault in an RL circuit, for a given X/R ratio and the point on the voltage wave at which the fault occurs.
- The current is a steady sine plus a decaying DC offset, whose size depends on the switching instant. Faults at a voltage zero give the largest offset.
- High X/R (close to generators and big transformers) makes the offset decay slowly, raising the first peak toward 2.8 times the symmetrical RMS.
Predict
A 100 MVA, 13.8 kV generator with X″ = 0.15 pu is shorted at its terminals. What's the initial symmetrical fault current?
= 6.67 pu, and the base current at 13.8 kV is 4184 A, so I″ = 27.9 kA RMS. It decays over a few cycles toward the transient value and then, if the fault stayed, the much smaller steady value set by .
Name it
A faulted generator
A short at a generator's terminals draws a current that decays through three stages as the rotor's windings react: subtransient for the first few cycles (time constant around 0.03 s), transient (time constant around 1 s), and finally steady state . Fault studies for breakers and relays use X″ with E″ ≈ 1 pu.
DC offset
Shorting an RL circuit forces the current to start from its prefault value, so a decaying DC term appears: with and τ = L/R. The worst first peak is about : 2.56 times the symmetrical RMS at X/R = 15.
Short-circuit level
The short-circuit MVA at a bus is in per unit, a measure of the bus's stiffness used for breaker selection and for the voltage sensitivity of lesson 8.
With the bus impedance matrix
For a bolted fault at bus k, with prefault voltages all about 1 pu:
so one column of gives every bus voltage during the fault, and the branch currents follow from them.
Breakers
Breakers are rated for the symmetrical current they can interrupt at rated voltage, and for the asymmetrical peak they can close onto and withstand. Modern EHV breakers interrupt 40 to 80 kA in two to three cycles.
Worked example
The generator above feeds a 13.8/138 kV transformer with X = 0.1 pu. What's the fault current for a short on the 138 kV side?
Show the solution
- Fault current in per unit.
- On the line side. The 138 kV base current is 418.4 A:
- In the generator's windings. One per-unit current, two values in amperes.
Answer 4 pu, which is 1.67 kA on the 138 kV side and 16.7 kA in the generator's windings.
Worked example
In the three-bus network of lesson 10 ( = j0.327, = j0.200, = j0.236), find the fault current and the bus voltages for a fault at bus 3.
Show the solution
- Fault current. a short-circuit level of 306 MVA on 100 MVA.
- Bus voltages during the fault.
- What loads see. Loads all over the network see deep sags until the fault clears.
Answer 3.06 pu (306 MVA), with bus 1 at 0.389 pu and bus 2 at 0.278 pu during the fault.
Worked example
A fault where X/R = 15 is interrupted by a breaker whose contacts part 3 cycles (50 ms) after it begins. By how much does the DC offset raise the RMS current the breaker must interrupt?
Show the solution
- Decay of the offset. It decays with time constant
- Asymmetrical current. With the worst-case offset, the asymmetrical RMS current is
- At 50 ms. Here , so the factor is
- Why contact-parting time matters. A breaker opening a cycle sooner, or one on a circuit with higher X/R, faces a larger factor, which is why breaker ratings specify the contact-parting time.
Answer by a factor of 1.078.
Check
A 50 MVA, 22 kV generator with X″ = 0.2 pu is shorted at its terminals. What's the subtransient current?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A generator (X″ = 0.15) and transformer (X = 0.08, both on 100 MVA) feed a 230 kV bus that's shorted. What's the fault current there?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A bus has a Thevenin impedance of 0.15 pu on a 100 MVA base. What's its short-circuit level?
Write units the way you normally would: 1.5 MVA, 1500 kVA and 0.0015 GVA are the same answer.
Check
A fault at bus k has = j0.35; another bus has = j0.1. What's that bus's voltage during the fault, prefault voltages 1 pu?
Check
A fault of 10 kA RMS symmetrical occurs where X/R = 15. Estimate the worst first peak.
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A bus is fed by two sources whose Thevenin reactances to it are 0.1 and 0.15 pu. What's the fault current at the bus in per unit?
Check
A fault with X/R = 15 at 60 Hz is interrupted when the breaker's contacts part 2 cycles after it starts.
(a)
What is the DC offset's time constant?
Write units the way you normally would: 1.5 ms, 1500 µs and 0.0015 s are the same answer.
(b)
By what factor is the worst-case RMS current raised at that moment?
Check
A fault has ratio X/R = r at 60 Hz.
Step 1
What is the DC time constant, in seconds?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What asymmetry factor applies at time t?
Explain why
Why does a fault close to a generator have a large DC offset that decays slowly, while one far out on a distribution feeder has little?
The DC offset appears because the current in an inductive circuit can't jump: right after the fault, the current must still equal its prefault value, so a decaying DC term makes up the difference between that and the new sinusoidal steady state. It decays with the circuit's time constant L/R, which is (X/R)/ω. Near generators and large transformers the impedance is almost pure reactance, with X/R of 30 or more, so the offset lasts many cycles and raises the first peaks close to twice the symmetrical value. A distribution feeder has much more resistance per unit of reactance, so X/R is a few and the offset is gone within a cycle.