S10 · Lesson 38 · Unsymmetrical faults
Single line-to-ground, line-to-line and double line-to-ground faults by connecting sequence networks, fault impedance, neutral grounding to limit ground-fault current, and how the fault types compare
About four out of five faults on overhead lines are single line-to-ground: one conductor flashing over to a tower or a tree. Fewer than one in twenty involves all three phases. Symmetrical components (lesson 37) turn each unbalanced fault into a simple connection of the positive-, negative- and zero-sequence networks at the fault point, so the currents follow from Ohm's law. This lesson builds those connections and shows why the way a transformer's neutral is grounded can matter more than the size of the generator behind it.
- Fault currents at a bus with = j0.25 and = j0.35 pu (before grounding), against a neutral reactance in the grounding path.
- With solid grounding the single line-to-ground fault (3.53 pu) is nearly as large as the three-phase one (4 pu). The neutral reactance adds to the zero-sequence network, cutting the ground-fault current without touching the others.
- Line-to-line faults don't involve ground at all, so they stay at .
Predict
At a generator's terminals = = j0.25 pu and its solidly grounded neutral gives = j0.1 pu. Which fault draws the most current?
The line-to-ground current is , which exceeds the three-phase whenever . Generators have small zero-sequence reactance, so their neutrals are usually grounded through a resistor or reactor (or a distribution transformer and resistor) to keep ground-fault currents below the three-phase value.
Name it
Connections at the fault (prefault voltage 1 pu, fault impedance )
- Single line-to-ground (phase a): the three sequence networks in series, , and the fault current is .
- Line-to-line (b to c): positive and negative networks in parallel through , , no zero sequence, and .
- Double line-to-ground (b and c to ground): the negative network in parallel with the zero network (plus ), the whole in series with the positive: , then current division gives and ; the ground carries .
- Three-phase: positive network only, .
The 's are the Thevenin impedances of each sequence network at the fault bus, found from the three sequence matrices.
Grounding
A neutral impedance appears as in the zero-sequence network only. Utilities ground transmission solidly (for fast, sure relaying and lower overvoltages on the healthy phases), and ground generators and some distribution through impedance to limit damage.
Which is worst
With : line-to-line current is = 0.87 of three-phase; line-to-ground exceeds three-phase if . Breakers are sized for the largest.
Worked example
With = j0.25 and = j0.35 pu, find the current for each fault type.
Show the solution
- Three-phase.
- Line-to-ground.
- Line-to-line.
- Double line-to-ground.
- Its zero sequence. so the ground carries 3.16 pu and each faulted phase 3.81 pu.
Answer 4.00 pu for a three-phase fault, 3.53 pu line-to-ground, 3.46 pu line-to-line, and 3.81 pu in each faulted phase for double line-to-ground (3.16 pu in the ground).
Worked example
What neutral reactance limits the line-to-ground current at that bus to 3 pu?
Show the solution
- Set the current.
- Solve. so = 0.05 pu.
- Fault resistance instead. A fault resistance does something similar but adds in quadrature: 0.1 pu of gives
Answer = 0.05 pu.
Worked example
A 13.8 kV bus has = j0.2 and = j0.1 pu on 100 MVA. What neutral resistor limits single line-to-ground faults to 400 A?
Show the solution
- Current in per unit. The base current is 4184 A, so
- Impedance needed. so = 10.46 pu.
- In ohms. With Ω:
- Why low-resistance grounding. Low-resistance grounding like this keeps ground-fault currents to hundreds of amperes, enough for relays to see but far too little to damage machine windings.
Answer a 19.9 Ω neutral resistor (10.46 pu).
Check
A bus has = j0.15, = j0.15 and = j0.6 pu. What's the bolted single line-to-ground fault current?
Check
With = j0.2 and = j0.12 pu, what's the current in phase b for a bolted b–c fault?
Check
A bus has = j0.15 and = j0.2 pu with solid grounding. What neutral reactance limits a line-to-ground fault to 2.2 pu?
Check
A bus has = j0.15 and = j0.1 pu. How much current flows into the ground for a bolted double line-to-ground fault?
Check
A line-to-ground fault through 0.2 pu of resistance occurs at a bus with = j0.15 and = j0.2. What's the fault current?
Check
A generator has = j0.15 and = j0.05, solidly grounded. What's the ratio of line-to-ground to three-phase fault current at its terminals?
Check
A 13.8 kV bus has = j0.1 and = j0.2 pu on 100 MVA. A neutral resistor must limit ground faults to 1000 A.
(a)
What resistance does it need?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A bus has = ja and = jc pu; a line-to-ground fault occurs through resistance r.
Step 1
What is the fault current in per unit?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What would it be for a bolted fault?
Explain why
Why do the three sequence networks connect in series for a single line-to-ground fault?
A bolted fault from phase a to ground with the other phases open imposes three conditions: , and . Transforming the two current conditions into sequence quantities shows that the three sequence currents must be equal, , and the voltage condition says the three sequence voltages at the fault must add to zero. Equal currents through three elements whose voltages sum to zero is exactly a series loop, so the positive network's source drives one current through all three networks' Thevenin impedances in turn. The phase current is the sum of the three equal sequence currents, three times each.