S10 · Lesson 38 · Unsymmetrical faults

Single line-to-ground, line-to-line and double line-to-ground faults by connecting sequence networks, fault impedance, neutral grounding to limit ground-fault current, and how the fault types compare

About four out of five faults on overhead lines are single line-to-ground: one conductor flashing over to a tower or a tree. Fewer than one in twenty involves all three phases. Symmetrical components (lesson 37) turn each unbalanced fault into a simple connection of the positive-, negative- and zero-sequence networks at the fault point, so the currents follow from Ohm's law. This lesson builds those connections and shows why the way a transformer's neutral is grounded can matter more than the size of the generator behind it.

  • Fault currents at a bus with Z1=Z2 = j0.25 and Z0 = j0.35 pu (before grounding), against a neutral reactance Xn in the grounding path.
  • With solid grounding the single line-to-ground fault (3.53 pu) is nearly as large as the three-phase one (4 pu). The neutral reactance adds 3Xn to the zero-sequence network, cutting the ground-fault current without touching the others.
  • Line-to-line faults don't involve ground at all, so they stay at 3/(Z1+Z2).

Predict

At a generator's terminals Z1 = Z2 = j0.25 pu and its solidly grounded neutral gives Z0 = j0.1 pu. Which fault draws the most current?

Name it

Connections at the fault (prefault voltage 1 pu, fault impedance Zf)

  • Single line-to-ground (phase a): the three sequence networks in series, Ia1=Ia2=Ia0=1Z1+Z2+Z0+3Zf, and the fault current is Ia=3Ia0.
  • Line-to-line (b to c): positive and negative networks in parallel through Zf, Ia1=−Ia2=1Z1+Z2+Zf, no zero sequence, and |Ib|=|Ic|=3|Ia1|.
  • Double line-to-ground (b and c to ground): the negative network in parallel with the zero network (plus 3Zf), the whole in series with the positive: Ia1=1Z1+Z2∥(Z0+3Zf), then current division gives Ia2 and Ia0; the ground carries 3Ia0.
  • Three-phase: positive network only, I=1/(Z1+Zf).

The Z's are the Thevenin impedances of each sequence network at the fault bus, found from the three sequence Zbus matrices.

Grounding

A neutral impedance Zn appears as 3Zn in the zero-sequence network only. Utilities ground transmission solidly (for fast, sure relaying and lower overvoltages on the healthy phases), and ground generators and some distribution through impedance to limit damage.

Which is worst

With Z1=Z2: line-to-line current is 3/2 = 0.87 of three-phase; line-to-ground exceeds three-phase if Z0<Z1. Breakers are sized for the largest.

Worked example

With Z1=Z2 = j0.25 and Z0 = j0.35 pu, find the current for each fault type.

Show the solution
  1. Three-phase. If=1/0.25=4.00pu
  2. Line-to-ground. If=3/0.85=3.53pu
  3. Line-to-line. If=3/0.5=3.46pu
  4. Double line-to-ground. Ia1=10.25+0.25∥0.35=1/0.396=2.53pu
  5. Its zero sequence. Ia0=−2.53×0.25/0.6=−1.05pu so the ground carries 3.16 pu and each faulted phase 3.81 pu.

Answer 4.00 pu for a three-phase fault, 3.53 pu line-to-ground, 3.46 pu line-to-line, and 3.81 pu in each faulted phase for double line-to-ground (3.16 pu in the ground).

Worked example

What neutral reactance limits the line-to-ground current at that bus to 3 pu?

Show the solution
  1. Set the current. Z1+Z2+Z0+3Xn=3/3=1
  2. Solve. 3Xn=1−0.85=0.15 so Xn = 0.05 pu.
  3. Fault resistance instead. A fault resistance does something similar but adds in quadrature: 0.1 pu of Rf gives If=3/|j0.85+0.3|=3.33pu

Answer Xn = 0.05 pu.

Worked example

A 13.8 kV bus has Z1=Z2 = j0.2 and Z0 = j0.1 pu on 100 MVA. What neutral resistor limits single line-to-ground faults to 400 A?

Show the solution
  1. Current in per unit. The base current is 4184 A, so If=400/4184=0.0956pu
  2. Impedance needed. |j0.5+3Rn|=3/0.0956=31.4pu so Rn = 10.46 pu.
  3. In ohms. With Zbase=13.82/100=1.904 Ω: Rn=10.46×1.904Ω=19.9Ω
  4. Why low-resistance grounding. Low-resistance grounding like this keeps ground-fault currents to hundreds of amperes, enough for relays to see but far too little to damage machine windings.

Answer a 19.9 Ω neutral resistor (10.46 pu).

Check

A bus has Z1 = j0.15, Z2 = j0.15 and Z0 = j0.6 pu. What's the bolted single line-to-ground fault current?

Check

With Z1 = j0.2 and Z2 = j0.12 pu, what's the current in phase b for a bolted b–c fault?

Check

A bus has Z1=Z2 = j0.15 and Z0 = j0.2 pu with solid grounding. What neutral reactance limits a line-to-ground fault to 2.2 pu?

Check

A bus has Z1=Z2 = j0.15 and Z0 = j0.1 pu. How much current flows into the ground for a bolted double line-to-ground fault?

Check

A line-to-ground fault through 0.2 pu of resistance occurs at a bus with Z1=Z2 = j0.15 and Z0 = j0.2. What's the fault current?

Check

A generator has Z1=Z2 = j0.15 and Z0 = j0.05, solidly grounded. What's the ratio of line-to-ground to three-phase fault current at its terminals?

Check

A 13.8 kV bus has Z1=Z2 = j0.1 and Z0 = j0.2 pu on 100 MVA. A neutral resistor must limit ground faults to 1000 A.

(a)

What resistance does it need?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

Check

A bus has Z1=Z2 = ja and Z0 = jc pu; a line-to-ground fault occurs through resistance r.

Step 1

What is the fault current in per unit?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why do the three sequence networks connect in series for a single line-to-ground fault?

Practice

Keep practicing

10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.