S10 · Lesson 14 · Voltage stability

How much load a network can carry before its voltage collapses: P–V curves and the nose, loadability with power factor, Q–V curves and reactive margins, and the role of load behavior and tap changers

Several of the largest blackouts, Tokyo in 1987, the western United States in 1996, the northeastern United States and Canada in 2003, ended with voltages sliding down over seconds or minutes until protection tripped everything. No generator lost synchronism first; the network simply couldn't deliver the reactive power its loads demanded. Lesson 7 found that a line's power transfer has a maximum. This lesson follows that maximum: where it lies, how load power factor moves it, how to measure the distance to it, and why the loads themselves can drive a system over the edge.

  • The solid curve is the load bus voltage of the two-bus system (E = 1 pu behind X = 0.5 pu) against loading, as a fraction of the maximum, for a load at the power factor angle set by the slider (positive is lagging).
  • The dashed curve is the second, low-voltage solution. The two meet at the nose, where the loading is at its maximum and the voltage at its critical value.
  • Make the load leading (negative angle) and the nose moves up toward 1 pu: with compensated loads the voltage can look healthy almost all the way to collapse.

Predict

A load bus holds 0.97 pu, its loads heavily compensated with capacitors. What does that voltage say about its distance from voltage collapse?

Name it

The P–V curve

For a source E behind reactance X feeding a load P + jQ with Q = P tan φ, the load voltage solves

V4+(2QX−E2)V2+X2(P2+Q2)=0

which has two positive solutions up to a maximum loading and none beyond. At the nose,

Pmax⁡=E2cos⁡ϕ2X(1+sin⁡ϕ),Vcr=E2(1+sin⁡ϕ)

A lagging load (φ > 0) lowers both; a leading one raises both. The power flow's Jacobian becomes singular at the nose (lesson 19), so Newton's method fails there.

Margins

The loadability margin is the extra load, usually as a percentage, before the nose. The reactive margin comes from the Q–V curve: the reactive power a fictitious compensator at the bus must supply to hold each voltage. Its minimum, how much more the bus could absorb before no voltage is possible, is the margin. For the two-bus system at unity power factor,

Qmargin=E4/4−P2X2E2X

and dV/dQ, the slope of the curve, is positive and small on the stable side.

Load behavior

Loads aren't constant power. A constant-impedance load takes P∝V2, so falling voltage lowers its demand and helps; motors and electronic loads behave closer to constant power. Load tap changers restore distribution voltages over tens of seconds, which turns impedance-like loads back into constant-power ones, and a tap changer that keeps raising the secondary voltage at a weak bus can pull the transmission voltage down past the nose: the slow collapse seen in 1987 and 2003. Remedies are reactive reserves (generators, SVCs, STATCOMs), switched capacitors, blocking tap changers, and as a last resort undervoltage load shedding.

Worked example

A 1 pu source feeds a 0.9-power-factor-lagging load through X = 0.2 pu. Find the maximum loading, the critical voltage, and the voltage and margin at 1 pu of load.

Show the solution
  1. Maximum loading. With sin φ = 0.436: Pmax⁡=0.92×0.2×1.436=1.567pu
  2. Critical voltage. Vcr=1/2×1.436=0.590pu
  3. Voltage at 1 pu of load. At P = 1 (Q = 0.484) the quartic becomes V4−0.806V2+0.0494=0 so V2 = 0.739 and V = 0.860 pu.
  4. Margin. The loadability margin is 57%, though the voltage is already 14% low.

Answer Pmax⁡ = 1.567 pu at a critical voltage of 0.590 pu; at 1 pu of load the voltage is 0.860 pu, with a 57% margin.

Worked example

A tap changer raises a distribution bus by 5%. How much more power does a constant-impedance load there take, and why can that hurt?

Show the solution
  1. Extra power. P∝V2, so 1.052=1.1025 which is 10.25% more power.
  2. What the sag was doing. Right after a disturbance the sagging voltage had cut the load's demand, relieving the transmission system.
  3. What the tap changer does. Restoring the voltage brings that demand back, drawing more current through the weakened network, which lowers the transmission voltage further, and the tap changer responds again.
  4. The fix. Blocking tap changers during emergencies breaks the cycle.

Answer 10.25% more power, and restoring that demand after a disturbance drags the weakened transmission voltage further down.

Worked example

For the two-bus system with E = 1 pu, X = 0.2 pu and a 1 pu unity-power-factor load, find the reactive margin from the Q–V curve.

Show the solution
  1. The Q–V curve. The compensation needed to hold V is Qc=V2−E2V2−P2X2X
  2. Where it bottoms out. V=E2/4+P2X2/E2=0.539pu
  3. Compensation at the minimum. Qc=P2X2−E4/4E2X=−1.05pu
  4. Reactive margin. So the bus could absorb another 1.05 pu of reactive load before no operating point remained: its reactive margin.
  5. At nominal voltage. At V = 1 pu the curve says the bus needs 0.10 pu of support to hold nominal voltage.

Answer a reactive margin of 1.05 pu, from the curve's minimum at 0.539 pu.

Check

A source of 1 pu feeds a load at power factor 0.95 lagging through X = 0.1 pu.

(a)

What is the maximum load?

(b)

What is the critical voltage at the nose?

Check

A 1 pu source feeds 1 pu at power factor 0.95 lagging through X = 0.1 pu.

(a)

What is the load voltage?

(b)

What is the loadability margin?

Check

A 1 pu source feeds 1 pu at unity power factor through X = 0.05 pu.

(a)

What is the bus's reactive margin?

(b)

At what voltage is the Q–V curve's minimum?

Check

A tap changer raises a load bus by 5%; the load's power varies as Vn with n = 1.

(a)

By how much does the load's power rise?

Check

A load's power factor angle is −15° (negative is leading), fed from 1 pu.

(a)

What is the critical voltage at the nose?

Check

A 50 Mvar capacitor bank is switched at a bus whose short-circuit level is 2000 MVA.

(a)

Roughly how much does it raise the voltage?

(b)

If the voltage then sagged by that same fraction, how much of its output would the capacitor lose?

Check

Why can blocking on-load tap changers during a voltage emergency stop a slow voltage collapse?

Check

A source E behind X feeds a load whose power factor angle has sine s.

Step 1

What is the maximum load?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Check

Write load_voltage(P, Q, X, E): the operating (higher) load voltage of the two-bus system, or None beyond the nose, and max_load(pf, X, E): the largest P at the given lagging power factor, found by bisection on whether load_voltage has a solution.

Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.

Explain why

Why does voltage collapse often develop over minutes rather than instantly after a disturbance?