S11 · Lesson 29 · Power and harmonics in nonsinusoidal systems
Average power from same-frequency voltage and current components only, RMS values of distorted waveforms, total harmonic distortion, distortion and displacement factors, and the poor power factor of peak-detecting rectifiers
A computer power supply with a plain diode bridge and a big capacitor draws current from the outlet only in short spikes near the peaks of the voltage. It uses the right real power, but its RMS current is far higher than a resistor's would be, so wiring and transformers heat up as if it drew much more. Fourier analysis makes this precise: only the harmonic of the current that matches the voltage's frequency delivers power, and the rest only adds to the RMS. This lesson defines the measures, and the next three show how rectifiers and PFC circuits produce or cure them.
- A line current made of pulses centered on the voltage peaks, conducting for a total angle θ in each half cycle, with its spectrum: odd harmonics only.
- A full square wave (θ = 180°) has a distortion factor of 0.90. Narrow pulses (small θ) have rich harmonics and a much lower factor.
- With the voltage sinusoidal and the pulses in phase with it, the power factor equals the distortion factor.
Predict
A load's current has a THD of 100%, and its fundamental is in phase with the sinusoidal voltage. What's its power factor?
With a sinusoidal voltage, only the fundamental current delivers power, so PF = , the distortion factor, which is = 0.707. Peak-detecting rectifiers often have THD above 100% and power factors of 0.5 to 0.65.
Name it
Average power
With and , the average power is
Only voltage and current components at the same frequency contribute. With a sinusoidal voltage, current harmonics deliver no power.
RMS
: harmonics add in RMS.
Distortion and power factor
With a sinusoidal voltage, the power factor is the product of the distortion factor and the displacement factor :
Standard waveforms
A square wave (single-phase bridge with a large DC inductor) has distortion factor = 0.900 and THD 48.3%. A six-pulse three-phase bridge's line current has 3/π = 0.955 and 31.1%. Narrow peak-charging pulses do much worse.
Worked example
A current is made of pulses conducting 60° in each half cycle, centered on a sinusoidal voltage's peaks. Find its power factor.
Show the solution
- RMS and fundamental of the pulses. For pulses of unit height and total width θ per half cycle:
- Distortion factor. With θ = 60°:
- Displacement factor. The pulses are centered on the voltage, so the displacement factor is 1 and
Answer the power factor is 0.78, all of it from the distortion factor since the displacement factor is 1.
Worked example
A load draws 5 A of fundamental at 30° lag plus 2 A of 3rd and 1.5 A of 5th harmonic, from 120 V. Find P, S and PF.
Show the solution
- RMS current.
- Apparent power.
- Real power.
- Power factor. a distortion factor of 5/5.59 = 0.894 times a displacement factor of 0.866.
Answer P = 520 W, S = 671 VA and PF = 0.775.
Worked example
A power supply without power-factor correction draws current with 120% THD, its fundamental lagging the line voltage by 5°. What is its power factor?
Show the solution
- Distortion factor.
- Displacement factor.
- Power factor.
- Where the shortfall comes from. Nearly all of it comes from distortion, since cos 5° is so close to 1: the peaky current carries no power at its harmonics, and only active power-factor correction removes them.
Answer the power factor is 0.638.
Check
A current has 10 A RMS fundamental, 1 A RMS 3rd harmonic and 2 A RMS 5th. What's its total RMS value?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A current's THD is 48%. What's its distortion factor?
Check
A load has THD 60% and its fundamental lags the sinusoidal voltage by 0°. What's its power factor?
Check
A sinusoidal 120 V source supplies 2 A of fundamental at 35° lag and 4 A of 3rd harmonic. What real power flows?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A rectifier draws unit-height current pulses conducting 90° in each half cycle, centered on the voltage peaks. What's its power factor?
Check
A 120 V sinusoidal source supplies a fundamental of 4 A at 10° lag plus 3 A and 2 A of harmonics. What's the power factor?
Check
A load's current has THD 80%, and its fundamental lags the sinusoidal voltage by 0°.
(a)
What is its distortion factor?
(b)
What is its power factor?
Check
A sinusoidal V (RMS) supplies a fundamental of a A RMS lagging by p radians, plus b and c A RMS of harmonics.
Step 1
What real power?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What apparent power?
Step 3
What power factor?
Explain why
Why do current harmonics lower the power factor even though they deliver no power?
Power factor compares the real power delivered with the product of RMS voltage and RMS current, the apparent power that the wiring, transformers and generators must be sized for. With a sinusoidal voltage, current at harmonic frequencies averages to zero power against it, so it contributes nothing to P. But it still flows in every conductor and adds to the RMS current in quadrature, so it raises the apparent power and the losses. The result is a ratio of real to apparent power below one even when the current's fundamental is exactly in phase with the voltage. That's why regulations limit the harmonics that equipment may draw.