Power and harmonics in nonsinusoidal systems
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
0 solved
0 in a row
0 of 10 kinds solid
Check
A current has 10 A RMS fundamental, 1 A RMS 3rd harmonic and 2 A RMS 5th. What's its total RMS value?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A current's THD is 48%. What's its distortion factor?
Check
A load has THD 60% and its fundamental lags the sinusoidal voltage by 0°. What's its power factor?
Check
A sinusoidal 120 V source supplies 2 A of fundamental at 35° lag and 4 A of 3rd harmonic. What real power flows?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A rectifier draws unit-height current pulses conducting 90° in each half cycle, centered on the voltage peaks. What's its power factor?
Check
A 120 V sinusoidal source supplies a fundamental of 4 A at 10° lag plus 3 A and 2 A of harmonics. What's the power factor?
Check
A load's current has THD 80%, and its fundamental lags the sinusoidal voltage by 0°.
(a)
What is its distortion factor?
(b)
What is its power factor?
Check
Distortion factor at THD 80%?
Check
RMS of 3, 0.5 and 3 A components?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Power factor: THD 40%, 10° displacement?