S11 · Lesson 48 · Photovoltaic converters and MPPT
The solar cell as a current source with a diode, the maximum power point and fill factor, temperature and string sizing, perturb-and-observe and incremental-conductance tracking, and partial shading
A solar module isn't a voltage source or a current source but something in between: its current holds nearly constant up to a knee and then collapses toward zero as the voltage approaches open circuit. Somewhere on that knee lies the one operating point where it delivers the most power, and that point moves with sunlight and temperature. Every solar converter's first job is to find it and stay on it, while keeping the panel string's voltage within what its own switches can stand on the coldest morning.
- The curves are a 60-cell module's current and power against voltage, from the single-diode model with = 9 A, = 37.5 V and ideality factor 1.2, scaled by the irradiance on the slider.
- The power peaks at about 32.1 V and 8.5 A at full sun: 273 W, a fill factor of 0.81.
- Less sunlight scales the current almost proportionally, but the maximum-power voltage barely moves.
Predict
A string inverter accepts at most 1000 V. Modules have = 37.5 V at 25 °C, rising 0.3% per kelvin of cooling, and the site's coldest morning is −10 °C. How many modules can a string have?
At −10 °C, 35 K below the rating, rises 10.5% to 41.4 V, and an open string at sunrise reaches its full open-circuit voltage before the inverter starts drawing current. So the string is limited to ⌊1000/41.4⌋ = 24 modules (994 V). Sizing at 25 °C would allow 26 and overvoltage the inverter on cold, bright mornings.
Name it
The cell model
A cell is a photocurrent source in parallel with a diode: for a module of cells,
with = 25.7 mV at 25 °C. The maximum power point (MPP) sits on the knee, where ; the fill factor measures how square the curve is (0.75 to 0.85 for silicon).
Temperature and irradiance
The current scales with irradiance. Temperature lowers the voltage, about −0.3%/K for and −0.4%/K for , so power falls about 0.4%/K. Strings are sized so that N modules' cold stays below the inverter's maximum and their hot stays above its minimum tracking voltage.
Tracking
- Perturb and observe: step the operating voltage; if power rose, keep stepping the same way, otherwise reverse. Simple, but it oscillates around the MPP, and big steps trade speed against steady loss.
- Incremental conductance: at the MPP, , so . Comparing the measured incremental conductance with tells the tracker which way to move, and that it has arrived.
Partial shading
A shaded cell would be driven into reverse breakdown by its neighbors; bypass diodes across groups of cells let current go around it, which creates several local maxima on the string's power curve. Trackers then sweep the curve periodically to find the global peak.
The converter
A boost stage sets the module or string voltage to the MPP while feeding a higher bus; microinverters, working from a single module's 30 V, use isolated flyback or resonant stages instead of an extreme-duty boost.
Worked example
Find the maximum power point of the 60-cell module ( = 9 A, = 37.5 V, n = 1.2) and its fill factor.
Show the solution
- Thermal voltage for 60 cells.
- Saturation current. It follows from :
- Search for the peak. A search over V finds the power peaking at 32.1 V and 8.51 A:
- Fill factor.
Answer the maximum power point is 273 W, at 32.1 V and 8.51 A, and the fill factor is 0.81.
Worked example
The string of 24 modules must also stay above a 600 V minimum tracking voltage on a 70 °C summer afternoon, with = 32.1 V at 25 °C falling 0.4% per kelvin. Does it?
Show the solution
- Each module at 70 °C. That's 45 K above the rating, so falls 0.4% × 45 = 18%:
- The string. above 600 V, with 5% to spare.
- Both limits on string length. Hot strings set the lower bound on string length just as cold ones set the upper.
Answer yes: the string sits at 632 V, 5% above the 600 V minimum.
Worked example
A tracker measures I = 8.8 A at V = 30 V and an incremental conductance dI/dV = −0.12 S. Which way should it move?
Show the solution
- Slope of the power. positive: power still rises with voltage, so the MPP lies above 30 V.
- The same test by conductance. Equivalently, the measured dI/dV of −0.12 is shallower than
- The move. The tracker raises the voltage.
Answer up: dP/dV = +5.2 W/V, so the tracker raises the voltage.
Check
Modules with = 38 V at 25 °C (rising 0.28% per kelvin of cooling) must keep an open string below 1500 V at a site that reaches 35 °C below 25 °C.
(a)
What is each module's cold open-circuit voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
How many modules can a string have?
Check
A string of 24 modules has = 32 V each at 25 °C, falling 0.35% per kelvin; it runs 45 K above 25 °C.
(a)
What is the string's hot MPP voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A tracker measures 8 A at 25 V with incremental conductance −0.5 S.
(a)
What is dP/dV?
Write units the way you normally would: 1.5 W/V, 1500 mW/V and 0.0015 kW/V are the same answer.
(b)
What incremental conductance would mark the MPP?
Check
A module delivers 330 W at its MPP, with = 37 V and = 10.5 A.
(a)
What is its fill factor?
Check
A 300 W (at 25 °C) array runs 40 K hotter, with power falling 0.35% per kelvin.
(a)
What does it deliver?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A boost stage takes 12 module(s) in series at 30 V each up to a 200 V bus.
(a)
What duty cycle does it run at?
Check
Why can a perturb-and-observe tracker get stuck on the wrong peak when part of a string is shaded?
Check
A module's model has photocurrent S, saturation current I and thermal voltage a (= ).
Step 1
What is its open-circuit voltage?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What current does it give at voltage V?
Step 3
What is dP/dV there?
Check
Write mpp(Isc, Voc, a): the maximum power point (P, V, I) of the single-diode model with thermal voltage a, by golden-section search on V from 0 to Voc, and perturb_observe(Isc, Voc, a, V0, step, n): run n steps of perturb and observe from V0 and return the final voltage.
Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.
Explain why
Why is a string's length bounded both above and below, and what sets each bound?
The modules in a string add their voltages, and module voltage depends strongly on temperature. On the coldest, brightest morning the open-circuit voltage is at its highest, and since an inverter connects to an open string before it starts drawing power, that voltage must stay below the inverter's maximum input, which caps the number of modules. On the hottest afternoon the maximum-power voltage is at its lowest, and it must stay above the inverter's minimum tracking voltage or the inverter can't operate at the MPP, which sets a minimum number of modules. Both bounds come from the same temperature coefficients applied at the site's extreme temperatures.
Practice
Keep practicing
9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.