Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
Modules with = 38 V at 25 °C (rising 0.28% per kelvin of cooling) must keep an open string below 1500 V at a site that reaches 35 °C below 25 °C.
(a)
What is each module's cold open-circuit voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
How many modules can a string have?
Check
A string of 24 modules has = 32 V each at 25 °C, falling 0.35% per kelvin; it runs 45 K above 25 °C.
(a)
What is the string's hot MPP voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A tracker measures 8 A at 25 V with incremental conductance −0.5 S.
(a)
What is dP/dV?
Write units the way you normally would: 1.5 W/V, 1500 mW/V and 0.0015 kW/V are the same answer.
(b)
What incremental conductance would mark the MPP?
Check
A module delivers 330 W at its MPP, with = 37 V and = 10.5 A.
(a)
What is its fill factor?
Check
A 300 W (at 25 °C) array runs 40 K hotter, with power falling 0.35% per kelvin.
(a)
What does it deliver?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A boost stage takes 12 module(s) in series at 30 V each up to a 200 V bus.
(a)
What duty cycle does it run at?
Check
Modules per string: 40 V, 20 K below 25 °C, limit 1500 V?
Check
dP/dV at 6 A, 28 V, dI/dV = −0.4 S?
Write units the way you normally would: 1.5 W/V, 1500 mW/V and 0.0015 kW/V are the same answer.
Check
Fill factor: 280 W, 38 V, 11 A?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S11