S12 · Lesson 27 · Speed control of induction motors
Variable frequency with constant volts per hertz, the constant-torque region below base speed and the constant-power region above it, low-speed voltage boost, and the older methods (pole changing, rotor resistance, slip-power recovery) with their efficiencies
An induction motor on a fixed 60 Hz supply runs at nearly fixed speed. For most of the twentieth century, varying it meant wasting power in rotor resistors or building complicated machine sets. Then the inverter of S11 made frequency adjustable, and today most new industrial motors run from a variable-frequency drive. The rule that makes it work is simple: change voltage in proportion to frequency, and the motor's whole torque–speed curve slides along the speed axis unchanged.
- The 460 V motor's torque–speed curve at drive frequency f, with constant volts per hertz up to 60 Hz and constant voltage above (dashed: the 60 Hz curve).
- Below 60 Hz the curve shifts left, keeping its shape near synchronous speed, so rated torque is available at any speed. At low frequency the stator resistance takes a bigger share of the voltage and the peak sags.
- Above 60 Hz the voltage can't rise, the flux falls as 1/f, and the breakdown torque falls roughly as .
Predict
The 4-pole motor runs at 1764 rpm at full load on 60 Hz. With a drive at 30 Hz and half the voltage, about how fast does it run at the same torque?
With constant volts per hertz the air-gap flux is unchanged, and the rotor needs the same slip frequency, and so the same slip speed, to carry the same current and make the same torque: 36 rpm below the new synchronous speed of 900 rpm, so about 864 rpm. (The equivalent circuit gives 127 N·m at 864 rpm against 133 N·m at 60 Hz, since the stator resistance matters more at low frequency.)
Name it
Constant volts per hertz
The air-gap flux is proportional to . Holding at its rated value keeps the flux, and with it the torque per ampere, constant. The slip speed needed for a given torque, , is then roughly independent of frequency, so the torque–speed curve shifts with .
- Below base speed (rated frequency): constant torque capability.
- Low frequencies: the drop is no longer negligible against the shrinking voltage, so drives add a voltage boost to restore the flux.
- Above base speed: voltage is held at its maximum, flux falls as , and the available torque at rated current falls as , so power stays constant (field weakening). Breakdown torque falls as , which eventually limits the speed range.
Other methods
- Pole changing: windings reconnected for, say, 4 or 8 poles: two fixed speeds.
- Rotor resistance (wound rotor): raising raises the slip at a given torque. The rotor can be no more than efficient, so running at half speed wastes half the air-gap power.
- Slip-power recovery: a converter in the rotor circuit returns slip power to the line instead of burning it. The doubly fed induction generator of most wind turbines uses this, with a converter rated only for the slip power, typically ±30% of the machine.
Worked example
A drive runs the motor at 90 Hz with voltage held at 460 V. How does its torque capability change?
Show the solution
- Flux. With the voltage held at 460 V, the flux falls to 60/90 of rated.
- Torque at rated current. The torque falls in proportion, so a motor rated 133 N·m at 60 Hz can carry about at 2700 rpm: the same power.
- Breakdown torque. It falls further, to about ignoring resistance; the equivalent circuit gives 211 N·m.
Answer at rated current it carries about 89 N·m at 2700 rpm, the same power as at 60 Hz, and its breakdown torque falls to about 198 N·m (211 N·m from the equivalent circuit).
Worked example
A wound-rotor motor (4-pole, 60 Hz) is slowed to 1200 rpm with rotor resistors while delivering 20 kW. Where does the power go?
Show the solution
- Slip.
- Air-gap power. The mechanical power is , so = 30 kW.
- Rotor loss. The rotor circuit dissipates 10 kW, a third of the air-gap power, mostly in the external resistors.
- Compare with a drive. A drive at 40 Hz would deliver the same 20 kW at 1200 rpm with roughly rated slip.
Answer of the 30 kW crossing the air gap, 20 kW reaches the shaft and 10 kW is burned in the rotor circuit, mostly in the external resistors.
Worked example
The 460 V motor is driven at 6 Hz with its rated slip speed of 36 rpm. What voltage holds its air-gap flux at the rated value, compared with strict V/f?
Show the solution
- Air-gap voltage. At 60 Hz and rated load the air-gap voltage is 251 V per phase, so at 6 Hz it must be 25.1 V.
- Rotor branch at 6 Hz. Every reactance shrinks tenfold, and the slip is so = 0.75 Ω: the rotor carries the same 33.4 A and makes the same 133 N·m.
- Terminal voltage. The stator's 0.2 Ω now drops a large share of the voltage: the terminals need 32.5 V per phase, 56.4 V line to line.
- Compare with strict V/f. A constant 460/60 V/Hz would give 46.0 V. That 23% extra is the drive's low-speed voltage boost.
Answer 56.4 V line to line (32.5 V per phase), 23% more than the 46.0 V that strict V/f would give.
Check
A 2-pole motor needs 60 rpm of slip speed at its load. With constant V/f at 40 Hz, how fast does it run?
Check
A 460 V, 60 Hz motor runs from a drive at 10 Hz with constant volts per hertz (no boost). What voltage does the drive apply?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A motor's breakdown torque is 400 N·m at its base frequency of 50 Hz. Above base speed the voltage is held constant. About what is its breakdown torque at 120 Hz (ignoring resistance)?
Write units the way you normally would: 1.5 N·m, 1500 mN·m and 0.0015 kN·m are the same answer.
Check
At base speed (50 Hz) a motor is rated 200 N·m. In field weakening at 120 Hz, what torque can it carry at rated current?
Write units the way you normally would: 1.5 N·m, 1500 mN·m and 0.0015 kN·m are the same answer.
Check
A 4-pole, 50 Hz wound-rotor motor is slowed to 750 rpm with rotor resistance. What's the highest possible rotor efficiency?
Check
A 3 MW doubly fed induction generator runs over a slip range of ±0.2. About what power must its rotor converter handle?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A motor rated 50 N·m at its 50 Hz base frequency, with 450 N·m of breakdown torque, is driven at 90 Hz with its voltage held at rated.
(a)
About how much torque can it carry at rated current?
Write units the way you normally would: 1.5 N·m, 1500 mN·m and 0.0015 kN·m are the same answer.
(b)
About what breakdown torque does it have, ignoring stator resistance?
Check
A wound-rotor induction motor with P poles on f hertz runs at n rpm, with air-gap power A.
Step 1
What is its slip?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
How much power does the rotor circuit dissipate?
Explain why
Why does keeping volts per hertz constant give an induction motor the same torque capability at any speed below base speed?
The induced voltage in the stator is proportional to the frequency times the air-gap flux, so with the stator resistance neglected the flux is set by V/f. Holding V/f constant holds the flux constant. The torque is the flux times the rotor current that it acts on, and the rotor current depends on the slip frequency, the rate at which the field sweeps past the rotor bars, not on the supply frequency itself. So at any supply frequency, the same slip speed gives the same rotor current and the same torque, and the torque–speed curve just slides along the speed axis. Below a few hertz the stator resistance's drop becomes a large fraction of the reduced voltage and the flux sags, so drives boost the voltage there.