S12 · Lesson 10 · The synchronous machine and its equivalent circuit
A DC-excited rotor turning in step with the stator field, the excitation voltage set by field current, armature reaction and the synchronous reactance, the equivalent circuit and phasor diagram for generating and motoring, the load angle, and power transfer
Nearly every large generator in the world is a synchronous machine: a rotor carrying DC field current (or magnets), turned by a turbine at exactly the speed of the stator's rotating field. Its armature current sets up a field of its own that adds to the rotor's, and that reaction shows up in the equivalent circuit as a single, large reactance. With it, a machine that weighs hundreds of tons reduces to a voltage source behind a reactance, the same model S10 used for the grid.
- The phasor diagram of a synchronous generator: terminal voltage V (on the real axis), armature current I at power factor angle φ, the drop across the synchronous reactance, and the excitation voltage (resistance neglected), all in per unit.
- Lagging current (positive φ) needs a much larger , so more field current; leading current needs less.
- The angle δ between and V is the load angle; the real power is .
Predict
A generator with 0.84 pu synchronous reactance delivers rated current at 0.9 power factor lagging. What excitation voltage does it need?
= 1 + j0.84(0.9 − j0.436) = 1.366 + j0.756, which has magnitude 1.56 at δ = 29°. The reactance drop is nearly perpendicular to the current, so with lagging current it adds almost directly to V: a generator supplying reactive power needs a lot of field current.
Name it
Excitation voltage
The rotor's DC field current produces a rotating flux that induces in each phase the excitation voltage (or internal voltage) , proportional to field current and speed.
Synchronous reactance
The armature current's own rotating field induces a further voltage in the armature, proportional to the current and 90° behind it: a reactance (armature reaction), plus the leakage reactance . Together , typically 1 to 2 pu in large machines.
The equivalent circuit
Per phase, with armature resistance (often neglected):
Load angle and power
The angle δ by which leads V (positive for a generator, negative for a motor) measures how far the rotor is ahead of the resultant field. With neglected, three-phase power is
with a maximum of at 90°: the pull-out power.
Worked example
A 50 MVA, 13.8 kV, Y-connected generator has = 3.2 Ω per phase. Find and δ at rated load, 0.9 power factor lagging.
Show the solution
- Phase voltage and current. at −25.8°.
- Reactance drop. = 6694 V at 64.2°.
- Excitation voltage. at δ = 29.0°.
- In per unit. That's 1.56 pu, with = 3.2/3.809 = 0.84 pu.
- Check. which is 50 MVA × 0.9. The pull-out power at this excitation is 92.9 MW.
Answer = 12,441 V per phase (1.56 pu) at δ = 29.0°.
Worked example
A 460 V synchronous motor with = 2.5 Ω takes 15 kW at unity power factor. Find its excitation voltage and load angle.
Show the solution
- Phase voltage and current. V = 265.6 V per phase, and in phase with it.
- Excitation voltage.
- Magnitude and angle. = 269.7 V at δ = −10.0°: the rotor lags the resultant field, pulled along by it.
Answer = 269.7 V per phase, at a load angle of −10.0°.
Worked example
Run the 50 MVA, 13.8 kV generator ( = 3.2 Ω) at rated current and unity power factor instead. How do its excitation and load angle change?
Show the solution
- The reactance drop. The current, 2092 A, is now in phase with the 7967 V phase voltage, so = j6694 V adds at right angles.
- Excitation voltage. at δ = 40.0°.
- Compare with 0.9 lagging. Delivering 50 MW instead of 45 MW, the machine needs less field current (1.31 pu against 1.56 pu) but runs 11° closer to pull-out, because it no longer supplies reactive power.
- Why ratings are lagging. Generators are usually rated at 0.85 or 0.9 lagging so that they can supply vars at full load.
Answer falls to 10,406 V (1.31 pu, down from 1.56 pu) and δ rises to 40.0° (from 29.0°).
Check
A generator with = 1 pu delivers 0.5 pu current at power factor 0.95 lagging, at 1 pu terminal voltage. What's ?
Check
For the same generator ( = 1 pu, 0.5 pu current at power factor 0.95 lagging), what's the load angle?
Check
A generator's phase voltage is 2400 V and its excitation voltage 1.2 times that, with = 5 Ω, at δ = 45°. What three-phase power does it deliver?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A synchronous motor on 460 V (line to line) with = 8 Ω per phase takes 10 kW at unity power factor. What's its excitation voltage per phase?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
An 800 MVA, 4.16 kV, Y-connected generator has = 1.2 pu. How many ohms per phase is that?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
What's the pull-out power of a generator with 2400 V per phase, = 1.1 times that, and = 6 Ω?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A generator with a synchronous reactance of 1.2 per unit delivers rated current at rated voltage and power factor 0.8 lagging.
(a)
What is its excitation voltage, in per unit?
(b)
What is its load angle?
Check
A synchronous machine with phase voltage V, excitation voltage E and synchronous reactance X runs at load angle d degrees.
Step 1
What three-phase real power does it deliver?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What reactive power does it deliver?
Step 3
What is its pull-out power?
Explain why
Why must a generator's field current rise when it supplies more reactive power at the same real power?
With the terminal voltage held by the grid, the excitation voltage is . The real-power part of the current, in phase with V, produces a reactance drop perpendicular to V, which mostly rotates forward and opens the load angle. The reactive part of a lagging current lags V by 90°, so its drop points along V and adds directly to its length. Supplying more lagging reactive power therefore needs a longer , and since is proportional to field current, more field current. Underexcited, with smaller than V, the same machine absorbs reactive power instead.