S1218 of 55
0 XP
  1. Hook
  2. Play
  3. Predict
  4. Name it
  5. Check
  6. Explain

S12 · Lesson 18 · Synchronous machines in power systems

A generator behind a transformer and line, its power-angle curve and stability margin, the synchronizing power coefficient and the electromechanical oscillation it sets, load sharing between generators by governor droop, and the surge from synchronizing out of phase

A generator in a power station never connects straight to an infinite bus. Between them are a step-up transformer and kilometers of line, whose reactance adds to the machine's own and lowers the power it can transfer. And the rotor isn't rigidly locked to the grid: it's held by a magnetic spring whose stiffness depends on the load angle, so it swings around its operating point at about a hertz whenever something disturbs it. This lesson puts the machine of lessons 10 to 17 into the system it serves.

  • The curves are a generator's real power against load angle when it reaches a 1 pu bus through an external reactance Xe on the slider, for Ef = 1.4 pu and Xs = 1.0 pu: P=EfVsin⁡δ/(Xs+Xe).
  • The dashed line is the mechanical input, 0.8 pu. Where it crosses the curve's rising side is the operating point.
  • More external reactance lowers the curve, pushing the operating point toward the 90° limit.

Predict

A 60 Hz generator with an inertia constant of 4 s runs at a load angle where its synchronizing power coefficient is 0.6 pu per radian. Disturbed, at about what frequency does its rotor swing?

Name it

The power-angle curve with an external network

A generator with excitation voltage Ef and synchronous reactance Xs, reaching an infinite bus V through a transformer and line of total reactance Xe, transfers

P=EfVXs+Xesin⁡δ

with δ measured from the bus voltage. The external reactance lowers the peak and raises the angle for a given load.

Synchronizing power

The slope of the curve at the operating angle, Ps=dPdδ=EfVXs+Xecos⁡δ, is the restoring power per radian of rotor displacement. It falls to zero at 90°, where the steady-state stability limit lies.

Swing

With inertia constant H (the rotor's kinetic energy at synchronous speed over its rating, in seconds), the rotor angle obeys

2Hωsd2δdt2=Pm−Pe

in per unit, with δ in electrical radians and ωs the electrical synchronous speed. For small swings around the operating point, ωn=ωsPs/2H.

Load sharing

Generators on the same system share a load change according to their governors' droops: a machine rated S with droop R (per unit change in frequency for a full-rating change in power) picks up ΔP=SRΔff0. The frequency settles where the pickups add up to the load change.

Synchronizing

Before closing its breaker, a generator must match the bus's voltage, frequency, phase sequence and phase angle. Closed with an angle error θ, the voltage difference 2Vsin⁡(θ/2) drives a surge through the subtransient reactance and the network, and a torque jolt on the shaft.

Worked example

A generator with Ef = 1.4 pu and Xs = 1.0 pu delivers 0.8 pu through 0.4 pu of transformer and line reactance to a 1 pu bus. Find its load angle, maximum power and synchronizing power coefficient.

Show the solution
  1. Maximum power. The machine and network reactances add to 1.4 pu: Pmax⁡=1.41.4=1.0pu
  2. Load angle. sin⁡δ=0.8, so δ = 53.1°.
  3. Synchronizing coefficient. Ps=1.0×cos⁡53.1°=0.6pu per radian
  4. Without the external reactance. The peak would be 1.4 pu, δ only 34.8° and the coefficient 1.15: the network halves the machine's stiffness, which is why long lines limit how much power a remote plant can send.

Answer δ = 53.1°, a maximum power of 1.0 pu, and a synchronizing power coefficient of 0.6 pu per radian.

Worked example

Two generators run in parallel on an island: A rated 500 MW with 5% droop and B rated 200 MW with 4% droop. The load steps up by 30 MW. How do they share it, and where does the frequency settle?

Show the solution
  1. Each machine's share. Each picks up power in proportion to S/R: SARA=5000.05=10000SBRB=2000.04=5000 MW per unit frequency, so A takes 20 MW and B 10 MW.
  2. Frequency drop. Δf=ΔPARASA×60=20500×0.05×60=0.12Hz the same 0.12 Hz from B's numbers.
  3. Restoring 60 Hz. Automatic generation control then restores 60 Hz by raising the governors' setpoints, sharing the 30 MW however the dispatch prefers.

Answer A takes 20 MW and B takes 10 MW, and the frequency settles 0.12 Hz low.

Worked example

A generator is synchronized 10° out of phase with the bus, at equal voltages. Its subtransient reactance is 0.2 pu and the transformer adds 0.1 pu. How large is the current surge?

Show the solution
  1. Voltage across the breaker. At closing it's ΔV=2×1×sin⁡5°=0.174pu
  2. Current surge. I=0.1740.3=0.58pu more than half rated, plus a jolt of torque as the rotor is pulled 10° into line.
  3. In practice. Synchronizers typically allow only a few degrees and close as the phase difference passes through zero.

Answer the surge is 0.58 pu of current, more than half rated.

Check

A generator (Ef = 1.5 pu, Xs = 0.8 pu) delivers 0.9231 pu to a 1 pu bus through 0.5 pu of external reactance.

(a)

What is its load angle?

(b)

What is its synchronizing power coefficient, in pu per radian?

Check

A 60 Hz generator with inertia constant 4 s has a synchronizing power coefficient of 0.4 pu per radian.

(a)

At what frequency does its rotor swing?

Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.

Check

Two generators share a 10 MW load increase on an isolated 50 Hz system: one rated 300 MW with 0.04 droop, the other 150 MW with 0.06 droop.

(a)

How much does the first pick up?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

By how much does the frequency fall?

Check

A generator is synchronized 10° out of phase at equal voltages, with a subtransient reactance of 0.15 pu and 0.15 pu of transformer reactance.

(a)

What voltage appears across the breaker as it closes, in per unit?

(b)

What current surge flows, in per unit?

Check

A generator (Ef = 1.3, Xs = 1 pu) feeds a 1 pu bus through 0.6 pu.

(a)

What is the most power it can transfer?

Check

Why does adding a second parallel line between a power station and the grid let it deliver more power stably?

Check

A generator with excitation E and reactance X feeds a 1 pu bus through e at load angle d degrees; its inertia constant is H and the electrical synchronous speed w.

Step 1

What power does it deliver?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Check

Write swing(Pm, Pmax, H, f, d0, w0, T, dt): integrate 2Hωsδ¨=Pm−Pmax⁡sin⁡δ (δ in radians, w the speed deviation in electrical rad/s) by RK4 from (d0, w0) for T seconds, returning the lists of δ; and swing_frequency(deltas, dt): the oscillation frequency from the mean spacing of its downward crossings of the mean.

Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.

Explain why

Why does a synchronous generator's rotor oscillate around its operating angle after a disturbance?

Practice

Keep practicing

8 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.