S12 Electric machines · Practice
Synchronous machines in power systems
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A generator ( = 1.5 pu, = 0.8 pu) delivers 0.9231 pu to a 1 pu bus through 0.5 pu of external reactance.
(a)
What is its load angle?
(b)
What is its synchronizing power coefficient, in pu per radian?
Check
A 60 Hz generator with inertia constant 4 s has a synchronizing power coefficient of 0.4 pu per radian.
(a)
At what frequency does its rotor swing?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
Two generators share a 10 MW load increase on an isolated 50 Hz system: one rated 300 MW with 0.04 droop, the other 150 MW with 0.06 droop.
(a)
How much does the first pick up?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
By how much does the frequency fall?
Check
A generator is synchronized 10° out of phase at equal voltages, with a subtransient reactance of 0.15 pu and 0.15 pu of transformer reactance.
(a)
What voltage appears across the breaker as it closes, in per unit?
(b)
What current surge flows, in per unit?
Check
A generator ( = 1.3, = 1 pu) feeds a 1 pu bus through 0.6 pu.
(a)
What is the most power it can transfer?
Check
Load angle: = 1.2, = 0.9, = 0.4, P = 0.7385 pu?
Check
Swing frequency, 60 Hz, H = 3 s, = 0.5 pu/rad?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
Share of a 60 MW step: 200 MW at 0.05, 100 MW at 0.04?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S12