S12 · Lesson 3 · Transformer efficiency, regulation and inrush
Core and copper losses against load, the load at which a transformer is most efficient, all-day efficiency for a varying load, voltage regulation from the series impedance, and the inrush current when a transformer is switched on at the wrong instant
S10 used the transformer as a network element: an impedance, a tap and a phase shift. A machine designer asks different questions. How much energy does the transformer waste over a day when its load comes and goes? At what load is it most efficient? And why does the breaker sometimes trip when the transformer is switched on with nothing connected? The answers come from the same equivalent circuit, read with losses in mind.
- The efficiency of a 50 kVA transformer against load (as a fraction of rating), with 200 W of core loss and 600 W of copper loss at full load.
- Core loss is constant whenever the transformer is energized; copper loss grows with the square of the load. Efficiency peaks where the two are equal.
- Lowering the power factor lowers the real power delivered for the same current, so the whole curve drops.
Predict
A 50 kVA transformer has 200 W of core loss and 600 W of copper loss at full load. At what load is it most efficient?
Efficiency peaks where the copper loss, W at load fraction x, equals the fixed 200 W of core loss: = 0.577. Distribution transformers are designed this way on purpose, since they spend most of the day well below their rating.
Name it
Losses
The core loss (hysteresis and eddy currents, lesson 2) depends on the voltage and frequency and is constant whenever the transformer is energized; the open-circuit test measures it. The copper loss at load fraction x is , with the full-load value from the short-circuit test. At rated kVA S and power factor pf:
Maximum efficiency
Setting gives : the most efficient load is , where the two losses are equal.
All-day efficiency
For a load that varies over the day, the ratio of energy delivered to energy taken counts core loss for all 24 hours and copper loss according to each period's load.
Regulation
With the series impedance in per unit, the rise in secondary voltage from full load to no load is approximately for a lagging power factor (S10 lesson 3 gives the exact form).
Inrush
The flux is the integral of the voltage. Switched on at a voltage zero, the flux starts at zero (or at the residual flux) instead of at its negative peak, and climbs to twice its normal peak plus any residual. That drives the core deep into saturation, where only the air-core inductance limits the current, and the magnetizing current can reach many times rated current for a few cycles.
Worked example
Find the 50 kVA transformer's efficiency at full load and at its best load, both at 0.8 power factor.
Show the solution
- Efficiency at full load.
- Efficiency at the best load. At x = 0.577 the output is 23,094 W and the losses are 200 + 200 = 400 W, so
- Per-unit resistance.
- Regulation at 0.8 lagging. With 0.04 pu reactance it's about or 3.39% exactly.
Answer 98.04% at full load and 98.30% at its best load (x = 0.577). Its regulation at 0.8 lagging is about 3.36% (3.39% exactly).
Worked example
The same transformer runs 8 hours a day at full load and 16 at a quarter load, all at 0.8 power factor. Find its all-day efficiency.
Show the solution
- Energy out.
- Core loss. It's paid all 24 hours:
- Copper loss.
- All-day efficiency.
- A better match. A transformer designed with lower core loss and higher copper loss would do better on this cycle.
Answer the all-day efficiency is 97.92%.
Worked example
Two 100 kVA transformers are offered for a load that runs 6 hours a day at full load and 18 hours at 20%. A has 250 W of core loss and 1200 W of full-load copper loss; B has 400 W and 900 W. Which wastes less energy?
Show the solution
- Transformer A. 14.06 kWh a day in all.
- Transformer B. 15.65 kWh a day in all.
- Compare. A saves 1.58 kWh a day, 578 kWh a year, though B is more efficient at full load.
- What decides. For lightly loaded transformers the core loss, paid around the clock, decides.
Answer A wastes less: 14.06 kWh a day against B's 15.65 kWh, a saving of 1.58 kWh a day (578 kWh a year).
Check
A 100 kVA transformer has core loss 0.2% and full-load copper loss 1.5% of its rating. What's its efficiency at 0.75 of full load and power factor 0.8?
Check
A transformer has 200 W of core loss and 400 W of full-load copper loss. At what fraction of full load is it most efficient?
Check
A 25 kVA transformer with 100 W of core loss and 1200 W of full-load copper loss runs at power factor 1. What's its maximum efficiency?
Check
A 50 kVA transformer (core loss 0.3%, full-load copper loss 1.5%) runs 12 hours a day at full load and the rest at 0.2 of full load, all at 0.9 power factor. What's its all-day efficiency?
Check
A transformer's series impedance is 0.012 + j\given0.03 per unit. What's its approximate regulation at full load, power factor 0.95 lagging?
Check
A transformer runs at a peak flux density of 1.6 T. It's switched on at a voltage zero with residual flux 0.2 of its normal peak, in the direction the flux is about to go. What peak flux density does the core reach in the first cycle (ignoring saturation)?
Write units the way you normally would: 1.5 T, 1500 mT and 0.0015 kT are the same answer.
Check
A transformer has 0.2 kW of core loss and 0.9 kW of full-load copper loss. Each day it runs 12 hours at full load and the rest at 0.3 of full load.
(a)
How much energy does it lose per day?
Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.
(b)
And per year?
Check
A transformer rated S kVA has core loss c and full-load copper loss u, each as a fraction of S; it runs at load fraction x and power factor p.
Step 1
What is its efficiency?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
At what load fraction is it most efficient?
Explain why
Why is a distribution transformer designed to be most efficient well below its rated load?
A transformer's core loss is paid every hour it's energized, whether or not anything is drawing power, while its copper loss depends on the load squared. A distribution transformer on a residential street is energized all day but carries its rated load only during a few peak hours and runs lightly loaded the rest of the time. Its energy losses are dominated by the core, so the designer spends more on low-loss steel and accepts somewhat more copper loss, which puts the point where the two losses are equal, and the efficiency peak, at a fraction of the rating. That minimizes the energy wasted over a typical day, which is what the utility pays for.