Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
0 solved
0 in a row
0 of 10 kinds solid
Check
A 100 kVA transformer has core loss 0.2% and full-load copper loss 1.5% of its rating. What's its efficiency at 0.75 of full load and power factor 0.8?
Check
A transformer has 200 W of core loss and 400 W of full-load copper loss. At what fraction of full load is it most efficient?
Check
A 25 kVA transformer with 100 W of core loss and 1200 W of full-load copper loss runs at power factor 1. What's its maximum efficiency?
Check
A 50 kVA transformer (core loss 0.3%, full-load copper loss 1.5%) runs 12 hours a day at full load and the rest at 0.2 of full load, all at 0.9 power factor. What's its all-day efficiency?
Check
A transformer's series impedance is 0.012 + j\given0.03 per unit. What's its approximate regulation at full load, power factor 0.95 lagging?
Check
A transformer runs at a peak flux density of 1.6 T. It's switched on at a voltage zero with residual flux 0.2 of its normal peak, in the direction the flux is about to go. What peak flux density does the core reach in the first cycle (ignoring saturation)?
Write units the way you normally would: 1.5 T, 1500 mT and 0.0015 kT are the same answer.
Check
A transformer has 0.2 kW of core loss and 0.9 kW of full-load copper loss. Each day it runs 12 hours at full load and the rest at 0.3 of full load.
(a)
How much energy does it lose per day?
Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.
(b)
And per year?
Check
Efficiency: 10 kVA, core 0.15%, copper 2%, load 0.9, pf 0.75?
Check
Best load fraction: 50 W core, 300 W copper?
Check
Regulation: 0.008 + j\given0.04 pu at pf 0.9 lagging?