S1047 of 56
0 XP
  1. Hook
  2. Play
  3. Predict
  4. Name it
  5. Check
  6. Explain

S10 · Lesson 47 · Distribution systems and power quality

Radial feeders, voltage drop and loss with distributed load, voltage limits and regulation, distributed generation raising voltages, harmonics and total harmonic distortion, triplen currents in neutrals, capacitor resonance, and reliability indices

Transmission gets the attention, but most outages customers see start on the distribution system, and most of a utility's capital goes into it. Distribution feeders are radial, resistive and unbalanced, they now carry rooftop solar pushing power backward, and they serve loads, from LED drivers to motor drives, whose currents aren't sinusoidal. This lesson covers the calculations distribution engineers make daily: feeder voltage drop, the voltage rise from distributed generation, harmonic distortion and resonance, and how reliability is measured.

  • A load current with a 60 Hz fundamental of 100 A plus adjustable 3rd, 5th and 7th harmonics, in time and as a spectrum.
  • The readout is the total harmonic distortion: the RMS of all harmonics relative to the fundamental.
  • Odd harmonics like these come from rectifier front ends in electronics. The third harmonics of three phases are in step, so they add in the neutral instead of cancelling.

Predict

A 5 MW load is spread evenly along a feeder instead of sitting at its far end. How does the voltage drop at the end compare?

Name it

Feeders

Distribution feeders are radial: one source, power flowing outward. The drop along a feeder segment is about 3I(Rcos⁡ϕ+Xsin⁡ϕ) line to line, and R is comparable to X. For load spread uniformly along a feeder, the drop at the end is half and the loss a third of what the same total load lumped at the end would cause.

Voltage limits and control

ANSI C84.1 Range A holds service voltage within ±5% (114 to 126 V on a 120 V base). Substation load tap changers, line voltage regulators and switched capacitors keep feeders inside it.

Distributed generation

A generator exporting P and absorbing Q at the end of a feeder of impedance R + jX raises the voltage there by about (RP−XQ)/V2 in per unit. Rooftop solar on lightly loaded feeders can push voltages over the upper limit; smart inverters respond by absorbing vars (volt-var control) or curtailing.

Harmonics

Nonlinear loads draw harmonic currents. Total harmonic distortion

THD=∑h≥2Ih2I1

IEEE 519 limits harmonic currents at the point of common coupling and voltage THD (5% at most voltages). Triplen harmonics (3, 9, 15, ...) are zero sequence (lesson 37): their phase currents add in the neutral, which can carry more current than the phases. A shunt capacitor and the system's inductance resonate at the harmonic order hr=Ssc/QC; if that lands near a harmonic the loads produce, distortion is amplified.

Reliability

SAIFI is total customer interruptions divided by customers served (interruptions per customer per year); SAIDI is total customer-minutes of interruption divided by customers served (minutes per customer per year); CAIDI = SAIDI/SAIFI is the average outage length.

Worked example

A 12.47 kV feeder 5 km long (z = 0.3 + j0.4 Ω/km) serves 5 MW at 0.9 power factor. Compare the drop and loss with the load at the end and spread evenly.

Show the solution
  1. Current. I=5MW3×12.47kV×0.9=257A
  2. Drop with the load at the end. With R = 1.5 Ω and X = 2.0 Ω: ΔV=3I(Rcos⁡ϕ+Xsin⁡ϕ)=990V which is 7.9%.
  3. Loss with the load at the end. Ploss=3I2R=298kW
  4. Load spread evenly. The drop is 4.0% and the loss 99 kW.
  5. What it means. Uniform loading is why long rural feeders survive where a lumped analysis would fail.

Answer lumped at the end, a 7.9% drop and 298 kW of loss; spread evenly, 4.0% and 99 kW.

Worked example

A 3 Mvar capacitor bank is added at a bus with a 75 MVA short-circuit level that feeds many rectifier loads. Is there a problem?

Show the solution
  1. Resonant harmonic. hr=75/3=5 The bank and the system resonate exactly at the 5th harmonic, the strongest one six-pulse rectifiers produce.
  2. The problem. Harmonic voltages will be amplified, overheating the capacitors.
  3. The fix. The usual fix is to detune the bank with a series reactor so it resonates near the 4.7th harmonic, below the 5th.

Answer yes: the bank resonates with the system at the 5th harmonic, which the rectifiers produce most strongly.

Worked example

A 2 MW rooftop-solar aggregate at the end of a 12.47 kV feeder (R = 1.5 Ω, X = 2 Ω) exports at unity power factor. How much does it raise the voltage, and what does absorbing 0.75 Mvar do?

Show the solution
  1. Rise at unity power factor. ΔV=RP/V2=1.5×2×106124702=1.93%
  2. Effect of absorbing vars. Absorbing Q lowers it by XQ/V2=2×0.75×106124702=0.96% leaving 0.96%.
  3. Power factor. The inverters then run at power factor 0.94, which is how volt–var settings in modern interconnection rules let more solar onto a feeder.

Answer a 1.93% rise at unity power factor, cut to 0.96% by absorbing 0.75 Mvar.

Check

A current has a fundamental of 200 A with harmonics of 25, 5 and 10 A. What's its THD?

Check

Each phase of a balanced load carries 20 A of third harmonic. How much third-harmonic current flows in the neutral?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A 1 Mvar capacitor bank sits at a bus with a 150 MVA short-circuit level. At what harmonic order do they resonate?

Check

A generator exports 3 MW and absorbs 1 Mvar at the end of a feeder of 1 + j2 Ω at 12.47 kV. Estimate the voltage rise.

Check

A load lumped at the end of a feeder would cause a 6% drop. What's the drop if the same load is spread evenly along it?

Check

A utility serving 10000 customers had 4000 customer interruptions in a year, averaging 180 minutes each. What's its SAIDI?

Check

Solar inverters export 3 MW and absorb 1 Mvar at the end of a 12.47 kV feeder of 1.5 + j1 Ω.

(a)

By how much do they raise the voltage there?

(b)

At what power factor do they run?

Check

A current has fundamental I and harmonics a, b and c (all RMS).

Step 1

What is its THD (as a fraction)?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why does third-harmonic current add up in the neutral of a balanced three-phase system instead of cancelling?

Practice

Keep practicing

10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.