S10 Power system analysis · Practice
Distribution systems and power quality
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
0 solved
0 in a row
0 of 10 kinds solid
Check
A current has a fundamental of 200 A with harmonics of 25, 5 and 10 A. What's its THD?
Check
Each phase of a balanced load carries 20 A of third harmonic. How much third-harmonic current flows in the neutral?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A 1 Mvar capacitor bank sits at a bus with a 150 MVA short-circuit level. At what harmonic order do they resonate?
Check
A generator exports 3 MW and absorbs 1 Mvar at the end of a feeder of 1 + j2 Ω at 12.47 kV. Estimate the voltage rise.
Check
A load lumped at the end of a feeder would cause a 6% drop. What's the drop if the same load is spread evenly along it?
Check
A utility serving 10000 customers had 4000 customer interruptions in a year, averaging 180 minutes each. What's its SAIDI?
Check
Solar inverters export 3 MW and absorb 1 Mvar at the end of a 12.47 kV feeder of 1.5 + j1 Ω.
(a)
By how much do they raise the voltage there?
(b)
At what power factor do they run?
Check
THD: 150 A with 6, 4, 12 A of harmonics?
Check
Resonant order: 2 Mvar at 60 MVA?
Check
DG voltage change: 0.5 + j1 Ω, 2 MW out, 0.8 Mvar in, 12.47 kV?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10