S10 · Final exam
Final exam: power system analysis
Twelve problems from the whole course: complex power and per unit, transformers and lines, power transfer and compensation, network matrices and power flow, generators and their capability, generation adequacy, dispatch and prices, frequency control, HVDC, state estimation, faults and open conductors, protection, stability, inverter-based resources and distribution. Give yourself three hours and work without the lessons open. "Another set" deals a different exam.
Check
A 40 MW load at 0.75 lagging on a 138 kV line.
(a)
Line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Capacitor for 0.98?
(c)
Cut in line loss?
Check
A machine (30 MVA, 22 kV, X = 0.08) on a 100 MVA, 24 kV base; a transformer with R = 0.007, X = 0.05 pu at full load, 0.8 lagging.
(a)
Machine's X on the base?
(b)
Transformer regulation?
Check
A 230 kV line, = 7 m, two-conductor bundles 0.5 m apart, GMR 10 mm, radius 17 mm.
(a)
L per km?
Write units the way you normally would: 1.5 mH, 1500 µH and 0.0015 H are the same answer.
(b)
C per km?
(c)
SIL?
Check
An open 150 km, 345 kV line with B = 5 µS/km (wavelength 4940 km).
(a)
Ferranti rise?
(b)
Charging vars?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
Buses at 0.97 and 0.95 pu, 25° apart across X = 0.4; the line gets 0.3 series compensation.
(a)
Real power now?
(b)
Transfer limit with compensation?
Check
A two-bus case (X = 0.15, load 0.5 + j0.5); a 300-bus case with 30 PV buses.
(a)
Two-bus load voltage?
(b)
Unknowns in the second?
Check
A triangle ( = 0.1, = 0.15, = 0.4) with a generator j0.25 at bus 1.
(a)
PTDF of line 1–3 for a transfer 1 → 3?
(b)
?
Check
A generator with = 1 delivers 0.6 + j0.4 at 1 pu; its field limit is E = 2.3.
(a)
Power angle?
(b)
Most Q at that P?
Check
Two units (4.5, 0.003) and (6.5, 0.008) share 400 MW; separately, a binding triangle with generators at 15 and 40 dollars per MWh.
(a)
λ, dollars per MWh?
(b)
Triangle bus-3 LMP?
Check
A 30 GW system with H = 5 s loses 0.6 GW; a system with droop 0.04 and damping 0.5 loses 0.06 pu.
(a)
ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
(b)
Settling deviation in the second?
Check
A 400 MVA generator (X″ = 0.12) and transformer (X = 0.08) on the same base feed a 230 kV bus; X/R = 10 there.
(a)
Three-phase fault current?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(b)
Worst first peak?
Check
A bus with = j0.12, = j0.06.
(a)
Line-to-ground current?
(b)
Neutral reactance for 2.2 pu?
Check
A very inverse relay (dial 0.8) at 3 times pickup; a line of 90 Ω with CT ratio 400 and VT ratio 2000.
(a)
Relay time?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
Zone 1 (80%) in secondary ohms?
Check
A machine (H = 6 s) at 0.5 pu, = 1.8, zero-transfer fault cleared with the network intact.
(a)
Swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
Critical clearing angle?
(c)
Critical clearing time?
Check
Two machines (H = 4, 6 s), = 2.5; a mode at .
(a)
Swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
Halving time of the mode?
Check
A 150 MW inverter plant at a 500 MVA bus; a 100 A fundamental with 30, 15, 3 A harmonics.
(a)
SCR?
(b)
THD?
Check
An HVDC bipole's rectifiers each have 200 kV RMS on their valve sides, fire at α = 10° and carry 3 kA through = 14 Ω.
(a)
DC voltage of each pole?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
(b)
Power sent by the bipole?
Check
A line's flow is metered at both ends: 0.6 pu (σ = 0.02) and 0.62 pu (σ = 0.04), losses neglected.
(a)
Weighted least-squares estimate of the flow, in per unit?
(b)
J at the estimate?
Check
Two phases of a line carrying 0.8 pu break. Across the break = j0.5 pu and = j2 pu.
(a)
Each sequence current, in per unit?
(b)
Current in the phase still closed, in per unit?
Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.
Practice
Keep practicing
19 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.