S10 Power system analysis · Practice
Final exam
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A 40 MW load at 0.75 lagging on a 138 kV line.
(a)
Line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Capacitor for 0.98?
(c)
Cut in line loss?
Check
A machine (30 MVA, 22 kV, X = 0.08) on a 100 MVA, 24 kV base; a transformer with R = 0.007, X = 0.05 pu at full load, 0.8 lagging.
(a)
Machine's X on the base?
(b)
Transformer regulation?
Check
A 230 kV line, = 7 m, two-conductor bundles 0.5 m apart, GMR 10 mm, radius 17 mm.
(a)
L per km?
Write units the way you normally would: 1.5 mH, 1500 µH and 0.0015 H are the same answer.
(b)
C per km?
(c)
SIL?
Check
An open 150 km, 345 kV line with B = 5 µS/km (wavelength 4940 km).
(a)
Ferranti rise?
(b)
Charging vars?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
Buses at 0.97 and 0.95 pu, 25° apart across X = 0.4; the line gets 0.3 series compensation.
(a)
Real power now?
(b)
Transfer limit with compensation?
Check
A two-bus case (X = 0.15, load 0.5 + j0.5); a 300-bus case with 30 PV buses.
(a)
Two-bus load voltage?
(b)
Unknowns in the second?
Check
A triangle ( = 0.1, = 0.15, = 0.4) with a generator j0.25 at bus 1.
(a)
PTDF of line 1–3 for a transfer 1 → 3?
(b)
?
Check
A generator with = 1 delivers 0.6 + j0.4 at 1 pu; its field limit is E = 2.3.
(a)
Power angle?
(b)
Most Q at that P?
Check
Two units (4.5, 0.003) and (6.5, 0.008) share 400 MW; separately, a binding triangle with generators at 15 and 40 dollars per MWh.
(a)
λ, dollars per MWh?
(b)
Triangle bus-3 LMP?
Check
A 30 GW system with H = 5 s loses 0.6 GW; a system with droop 0.04 and damping 0.5 loses 0.06 pu.
(a)
ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
(b)
Settling deviation in the second?
Check
A 400 MVA generator (X″ = 0.12) and transformer (X = 0.08) on the same base feed a 230 kV bus; X/R = 10 there.
(a)
Three-phase fault current?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(b)
Worst first peak?
Check
A bus with = j0.12, = j0.06.
(a)
Line-to-ground current?
(b)
Neutral reactance for 2.2 pu?
Check
A very inverse relay (dial 0.8) at 3 times pickup; a line of 90 Ω with CT ratio 400 and VT ratio 2000.
(a)
Relay time?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
Zone 1 (80%) in secondary ohms?
Check
A machine (H = 6 s) at 0.5 pu, = 1.8, zero-transfer fault cleared with the network intact.
(a)
Swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
Critical clearing angle?
(c)
Critical clearing time?
Check
Two machines (H = 4, 6 s), = 2.5; a mode at .
(a)
Swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
Halving time of the mode?
Check
A 150 MW inverter plant at a 500 MVA bus; a 100 A fundamental with 30, 15, 3 A harmonics.
(a)
SCR?
(b)
THD?
Check
An HVDC bipole's rectifiers each have 200 kV RMS on their valve sides, fire at α = 10° and carry 3 kA through = 14 Ω.
(a)
DC voltage of each pole?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
(b)
Power sent by the bipole?
Check
A line's flow is metered at both ends: 0.6 pu (σ = 0.02) and 0.62 pu (σ = 0.04), losses neglected.
(a)
Weighted least-squares estimate of the flow, in per unit?
(b)
J at the estimate?
Check
Two phases of a line carrying 0.8 pu break. Across the break = j0.5 pu and = j2 pu.
(a)
Each sequence current, in per unit?
(b)
Current in the phase still closed, in per unit?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10