S10 · Lesson 30 · Frequency control
Frequency as the measure of the balance between generation and load, inertia and the rate of change of frequency, governor droop and load damping, the frequency nadir, sharing among units, and automatic generation control with area control error
There's no storage tank on the grid. Every instant, generation must equal load plus losses, and the only thing that absorbs a mismatch is the kinetic energy of the spinning machines, whose speed is the system frequency. When a large plant trips, frequency starts falling within milliseconds; within seconds, every governor on the system opens its valves a little; within minutes, the control center's automatic generation control restores frequency to 60 Hz. This lesson quantifies each of those layers.
- The frequency of an interconnection after losing 5% of its load-serving generation, with inertia constant H, governor and turbine time constant T, 5% droop and load damping D = 1.
- Frequency falls at first at a rate set by inertia alone, bottoms out at the nadir as the governors catch up, then settles at a lower steady value set by droop.
- Halve H (more inverter-based generation, lesson 46) and the initial fall doubles in speed and the nadir deepens; slower governors deepen it too.
Predict
An interconnection with 60 GW of synchronous generation (H = 5 s on that rating) suddenly loses a 1.2 GW plant. How fast does frequency start to fall?
Before any control acts, the missing power comes out of the rotors' kinetic energy: = 1.2 × 60/(2 × 5 × 60) = 0.12 Hz/s. Governors need a second or more to respond, so inertia alone sets the first moments, which is why falling system inertia worries grid operators.
Name it
Inertia
A machine's inertia constant H is its stored kinetic energy at synchronous speed divided by its rating (2 to 9 s for turbine generators). For a whole system of rating S with total H, a power deficit ΔP gives
the rate of change of frequency (ROCOF).
Primary control: droop
A governor with droop R (typically 5%) raises output in proportion to the frequency drop: a fall of R in per-unit frequency drives the unit from no load to full load. Loads also fall a little with frequency, by D percent per percent (load damping, about 1 to 2). In steady state after a loss (per unit on the system base):
Units share the change in proportion to rating/R. The combined is the frequency response characteristic.
Dynamics and the nadir
With a governor-turbine lag T: and (per unit). The lowest point, the nadir, must stay above the threshold where under-frequency load shedding starts (59.3 Hz in much of North America).
Secondary control: AGC
Droop leaves a frequency error and changes tie-line flows. Each balancing area's automatic generation control computes its area control error
with frequency bias B in MW/0.1 Hz (negative), and moves its generators to drive ACE to zero over minutes, restoring 60 Hz and scheduled interchange. Tertiary control (economic dispatch, lesson 27) then reshuffles units for cost.
Worked example
A system rated 10 GW has 5% droop on all its generation and load damping D = 1. It loses 500 MW. Where does frequency settle, and how low does it dip with H = 5 s and T = 4 s?
Show the solution
- Per unit. On the 10 GW base, = 0.05 and
- Settling frequency.
- The dip. The frequency falls at 0.30 Hz/s at first, reaches its nadir of −0.41 Hz at 2.4 s, then recovers to −0.143 Hz.
- With half the inertia. The initial rate doubles and the nadir deepens to −0.54 Hz at 1.6 s.
Answer it settles 0.143 Hz low, after dipping to −0.41 Hz at 2.4 s.
Worked example
A 600 MW unit with 5% droop and a 400 MW unit with 4% droop pick up a 100 MW load increase. How do they share it?
Show the solution
- Each unit's response. It's rating/R, in MW per unit frequency:
- Share the load. The 600 MW unit takes and the 400 MW unit 45.5 MW.
- Frequency drop. Ignoring load damping:
Answer the 600 MW unit takes 54.5 MW and the 400 MW unit 45.5 MW, and the frequency falls 0.27 Hz.
Worked example
A 10 GW system with H = 4 s loses 1 GW. How fast does frequency fall, and how soon would it reach an underfrequency load-shedding threshold of 59.3 Hz if the initial rate held?
Show the solution
- Initial rate of fall.
- Time to the threshold. From 60 Hz, 0.7 Hz of fall at that rate takes before governors have done much.
- Less inertia. Less inertia, as inverter-based generation replaces turbines, makes the fall faster and leaves less time, which is why ROCOF limits and fast frequency response now appear in grid codes.
Answer 0.75 Hz/s, reaching 59.3 Hz in 0.93 s.
Check
A 30 GW system with H = 5 s loses 1.2 GW of generation. What's the initial rate of change of frequency?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
A 500 MW unit with 0.05 droop sees frequency fall by 0.1 Hz. How much does its governor raise output?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A system (all generation at droop 0.04) loses 0.05 pu of generation, with load damping D = 2. Where does frequency settle?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A 300 MW unit at 0.04 droop and a 600 MW unit at 0.07 droop share a 50 MW load increase. How much does the first take?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
An area's tie-line flow is −50 MW from schedule, frequency is 0.03 Hz from 60, and its bias is −400 MW/0.1 Hz. What's its ACE?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A system of 50 MW with H = 5 s is falling at 1 Hz/s just after a disturbance. How large was the power deficit?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A 20 GW system with H = 2 s loses 2 GW. Load shedding begins at 59.3 Hz.
(a)
What is the initial ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
(b)
If that rate held, how soon would shedding begin?
Check
A system loses L pu of generation; all generation has droop R and the load damping is D; inertia H.
Step 1
What is the initial ROCOF, in Hz/s?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
Where does frequency settle, in Hz from 60?
Explain why
Why does frequency drop at the same rate everywhere in an interconnection after a generator trips?
All the synchronous machines in an interconnection are locked together electrically: if one tried to slow down relative to the others, the power angle between them would change and synchronizing power would flow to pull it back into step. So after a disturbance the whole interconnection decelerates together, apart from small oscillations between groups of machines, and the power deficit is shared among all the rotors in proportion to their inertia. That's why a plant tripping in one state is seen as a frequency dip by every generator on the continent within a second or two, and why every governor contributes to the recovery.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.