S10 Power system analysis · Practice
Frequency control
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A 30 GW system with H = 5 s loses 1.2 GW of generation. What's the initial rate of change of frequency?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
A 500 MW unit with 0.05 droop sees frequency fall by 0.1 Hz. How much does its governor raise output?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A system (all generation at droop 0.04) loses 0.05 pu of generation, with load damping D = 2. Where does frequency settle?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A 300 MW unit at 0.04 droop and a 600 MW unit at 0.07 droop share a 50 MW load increase. How much does the first take?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
An area's tie-line flow is −50 MW from schedule, frequency is 0.03 Hz from 60, and its bias is −400 MW/0.1 Hz. What's its ACE?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A system of 50 MW with H = 5 s is falling at 1 Hz/s just after a disturbance. How large was the power deficit?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A 20 GW system with H = 2 s loses 2 GW. Load shedding begins at 59.3 Hz.
(a)
What is the initial ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
(b)
If that rate held, how soon would shedding begin?
Check
ROCOF: lose 0.3 GW from 20 GW with H = 6 s?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
Settling Δf: loss 0.03 pu, R = 0.04, D = 1.5?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
ACE: tie −120 MW, Δf 0.02 Hz, B = −300?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10