S10 Power system analysis · Practice
Gauss–Seidel power flow
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
0 solved
0 in a row
0 of 10 kinds solid
Check
A slack at 1∠0° feeds a load of 0.5 + j0.5 pu through X = 0.2. What's the magnitude of the first Gauss–Seidel iterate for the load bus, from a flat start?
Check
A PV bus at 1.05 pu injects 0.8 pu into a slack at 1∠0° through X = 0.1. What angle does Gauss–Seidel converge to?
Check
For the same PV bus, how many vars does its generator inject at the solution?
Check
Each iteration multiplies the error by 0.3, starting from 0.05. How many iterations until it's below 1 × 10⁻⁶?
Check
An iteration moves a voltage from 0.95 to 0.9. With an acceleration factor of 1.5, what value is kept?
Check
A PV bus's generator can supply at most 0.3 pu of vars. An iteration computes that it would need 0.2 pu. What Q does the next update use?
Check
A PV bus set to 1.02 pu would need 0.5 pu of vars, but its generator is limited to 0.4 pu. The bus's short-circuit level is 10 pu.
(a)
How many vars short is it?
(b)
Roughly where does its voltage settle?
Check
First GS iterate magnitude: X = 0.15, load 0.4 + j0.6?
Check
Iterations to go from 0.1 to 1 × 10⁻⁸ at rate 0.5?
Check
PV-bus angle for 0.2 pu through X = 0.05, both at 1 pu?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10