S10 · Lesson 25 · Synchronous generators in the power system
The round-rotor generator as an internal voltage behind synchronous reactance, how the turbine sets real power and the field sets reactive power, the steady-state limit, the capability curve, and the reactances used for faults
A power plant operator has two controls: the turbine's steam or water valve and the generator's field current. Open the valve and the rotor advances a few degrees, pushing out more real power. Raise the field and the internal voltage rises, pushing out more reactive power and propping up the voltage of the surrounding grid. This lesson models the generator just well enough to see both effects, the limits on each, and the different reactances that matter in steady state and in the first cycles of a fault.
- The phasor diagram of a round-rotor generator connected to a 1 pu bus: terminal voltage V, the drop across the synchronous reactance, and the internal voltage .
- Raise P with Q fixed and E swings forward: the power angle δ grows. Raise Q with P fixed and E grows longer, nearly in line with V.
- Real power goes with δ and reactive power with |E|, the same decoupling as on a line (lesson 7), since the generator is a voltage behind a reactance.
Predict
A generator with = 1.2 pu delivers 0.8 + j0.6 pu at 1 pu terminal voltage. The operator then lowers the field until Q = 0, keeping P at 0.8. What happens to the power angle?
With Q = 0.6, E = 1.72 + j0.96 (|E| = 1.97, δ = 29.2°). With Q = 0, E = 1 + j0.96 (|E| = 1.39, δ = 43.8°). Since , a smaller E needs a larger angle for the same power, leaving less margin before the 90° limit. Under-excited operation is less stable.
Name it
The model
In steady state a round-rotor generator is an internal voltage E, set by the field current, behind the synchronous reactance (typically 1 to 2 pu on its own rating). With terminal voltage V and current I:
δ, the power angle, is the angle by which E leads V.
Controls
- Turbine (governor) sets mechanical power and so P and δ (lesson 30).
- Field (exciter, with an automatic voltage regulator) sets E and so Q: over-excited (E cos δ > V) the machine supplies vars; under-excited it absorbs them.
Limits
- Steady-state stability: P can't exceed , at δ = 90°.
- Capability curve in the P–Q plane: the armature current limit is a circle of radius rated MVA about the origin; the field current limit is a circle centered at with radius , which caps Q at high output; an under-excitation limit keeps δ and the core-end heating in check when absorbing vars; the turbine limits P.
Reactances for faults
Right after a short circuit the field and damper windings resist changes in flux, so the machine looks like a voltage behind a much smaller reactance: subtransient X″ (0.1 to 0.25 pu) for the first few cycles, then transient X′ (0.2 to 0.4 pu), and finally . Breaker duties use X″ (lesson 36); transient stability uses X′ (lesson 43).
Worked example
Find E and δ for = 1.2 pu delivering 0.8 + j0.6 pu at 1 pu, and the steady-state limit at that excitation.
Show the solution
- Armature current.
- Internal voltage. so |E| = 1.970 pu at δ = 29.2°.
- Check.
- Steady-state limit. At this field current it's about twice the present output.
Answer E = 1.970 pu at δ = 29.2°, and the steady-state limit is 1.64 pu.
Worked example
With = 2.2 pu and = 1.2, how many vars can the machine supply at P = 0.8?
Show the solution
- The field limit. with = 0.96.
- The cosine term.
- Reactive power.
- Beyond it. Asking for more would overheat the field winding.
Answer 0.816 pu.
Worked example
A generator with = 1.2 pu delivers 0.8 pu while absorbing 0.2 pu of vars at 1 pu terminal voltage. Find E, δ and how close it is to its steady-state limit.
Show the solution
- Armature current. With Q = −0.2:
- Internal voltage. so |E| = 1.22 pu at δ = 51.6°.
- Steady-state limit. only 28% above the 0.8 pu being delivered.
- Why it matters. Running underexcited lowers E, raises δ and eats the stability margin, which is why the capability curve has an underexcitation limit.
Answer E = 1.22 pu at δ = 51.6°, with a limit of 1.02 pu, only 28% above its output.
Check
A generator with = 1.2 pu delivers 0.5 + j(0.6) pu at 1 pu. What's its internal voltage magnitude?
Check
For the same machine, what's the power angle?
Check
A generator with E = 1.8 pu behind = 1 pu runs at δ = 50° on a 1 pu bus. How much real power does it deliver?
Check
And how much reactive power?
Check
What's the steady-state power limit of a generator with E = 1.6 pu behind = 0.8 pu on an infinite 1 pu bus?
Check
A generator's field limits E to 1.8 pu, with = 1 pu, on a 1 pu bus. What's the most reactive power it can supply at P = 0.9?
Check
A generator with = 1.2 pu delivers 0.5 pu and 0.4 pu of vars at 1 pu.
(a)
What is |E|?
(b)
What is δ?
Check
A generator with internal voltage E behind = X runs at power angle d on a 1 pu bus.
Step 1
What real power does it deliver?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What reactive power?
Step 3
What's its steady-state limit at this excitation?
Explain why
Why does raising a generator's field current increase its reactive output but barely change its real output?
Real power is set by the turbine: in steady state the electrical output must equal the mechanical input, or the rotor would speed up or slow down. Raising the field increases the internal voltage E, and since must stay the same, the power angle shrinks a little to compensate. Meanwhile the reactive output, , rises substantially because E cos δ grows. The extra internal voltage drives current nearly in phase with the drop across the synchronous reactance, which is 90° from the terminal voltage, so it shows up as vars. That's why the exciter is the generator's voltage control and the governor its power control.