S10 Power system analysis · Practice
Synchronous generators in the power system
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
0 solved
0 in a row
0 of 10 kinds solid
Check
A generator with = 1.2 pu delivers 0.5 + j(0.6) pu at 1 pu. What's its internal voltage magnitude?
Check
For the same machine, what's the power angle?
Check
A generator with E = 1.8 pu behind = 1 pu runs at δ = 50° on a 1 pu bus. How much real power does it deliver?
Check
And how much reactive power?
Check
What's the steady-state power limit of a generator with E = 1.6 pu behind = 0.8 pu on an infinite 1 pu bus?
Check
A generator's field limits E to 1.8 pu, with = 1 pu, on a 1 pu bus. What's the most reactive power it can supply at P = 0.9?
Check
A generator with = 1.2 pu delivers 0.5 pu and 0.4 pu of vars at 1 pu.
(a)
What is |E|?
(b)
What is δ?
Check
|E| for = 1, 0.3 + j0.5?
Check
P for E = 1.5, = 1.1, δ = 40°?
Check
Steady-state limit: E = 1.4, = 0.9?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10