A plant sends its output over a line of resistance 0.02 pu at 0.95 pu and power factor 0.9. What's its loss coefficient B, in per unit?
Check
A plant's losses are with B = 0.0004 per MW. What's its penalty factor at P = 200 MW?
Check
A unit's incremental cost is 22 dollars per MWh and its penalty factor is 1.03. What incremental cost does the load see, in dollars per MWh?
Check
A unit's incremental cost is 6 + 0.01P dollars per MWh and its losses are with B = 0.0002 per MW. At λ = 12 dollars per MWh, how much does it produce?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A unit could run through an off-peak hour at its 60 MW minimum, costing 200 dollars per hour of no-load cost and 8 dollars per MWh more than the unit that would otherwise make that energy. How many dollars does keeping it on for the hour cost?
Check
A unit's cost is 600 + 18P dollars per hour. What's its full-load average cost at 500 MW, in dollars per MWh, the number a priority list sorts by?
Check
A remote plant's incremental cost is 18 dollars per MWh with penalty factor 1.03; a local plant's is 21 with penalty factor 1.
(a)
What is the remote plant's delivered incremental cost?
(b)
By how much is the remote plant cheaper at the margin (negative if dearer)?
Check
Penalty factor for , B = 0.00011, P = 64 MW?
Check
Output at λ = 14 with incremental cost 6.4 + 0.0061P and B = 0.00022?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Full-load average cost: 670 + 18P dollars per hour at 440 MW?