S10 · Lesson 10 · The bus admittance and impedance matrices

Nodal equations for a power network, building the bus admittance matrix by inspection, line charging and off-nominal taps in it, its sparsity, and the bus impedance matrix whose diagonal gives each bus's Thevenin impedance

A real grid model has tens of thousands of buses, and every power-flow and fault program starts the same way: write the nodal equations I = YV for the whole network. The bus admittance matrix can be written down by inspection, one line at a time, and it's almost all zeros because each bus connects to only a few others. Its inverse, the bus impedance matrix, is full, but its diagonal holds something every protection engineer wants: the Thevenin impedance seen at each bus, and so its fault current.

  • A three-bus network: a generator behind j0.2 pu at bus 1, lines of j0.1 (1–2) and j0.2 (1–3), and a line of reactance x23 between buses 2 and 3.
  • The plot shows the Thevenin reactance at bus 3, Z33, against x23, and the three-phase fault current there (1/Z33).
  • With no 2–3 line (large x23) bus 3 is fed through 0.4 pu. Adding the parallel path lowers the impedance and raises the fault current: meshing a network makes it stiffer.

Predict

In a network's bus admittance matrix, what's the off-diagonal entry Yij for two buses joined by a line of series impedance zij?

Name it

Nodal equations

With bus voltages V (to ground) and currents I injected into the buses, I = YV.

Building Ybus by inspection

For each branch between buses i and j with series admittance yij=1/zij:

  • add yij to Yii and Yjj;
  • subtract yij from Yij and Yji.

Shunt elements (half of each line's charging susceptance at each end in the π model, capacitor banks, reactors, loads modeled as admittances, generator reactances to an internal source node) add only to their bus's diagonal. Without any connection to ground, Y is singular.

Off-nominal transformers

A transformer with series admittance y and a tap ratio a:1 on bus i's side contributes y/a2 to Yii, y to Yjj, and −y/a to Yij and Yji. Phase-shifting transformers make Y unsymmetric.

Sparsity

A bus typically connects to two to four others, so a 10,000-bus Y has about 99.97% zeros. Programs store only the nonzeros and factor with orderings that keep the factors sparse (lesson 43 of A13).

Zbus

Zbus=Ybus−1, full rather than sparse. Zkk is the Thevenin impedance at bus k with all sources shorted, so a bolted three-phase fault there draws Vpre/Zkk, and Zik gives how much the fault depresses bus i: ΔVi=−ZikIf (lesson 36).

Worked example

Build Ybus and Zbus for the three-bus network with x23 = 0.25.

Show the solution
  1. Branch admittances. They are −j10 (1–2), −j5 (1–3), −j4 (2–3) and −j5 (generator at bus 1).
  2. Build Ybus. Ybus=−j(20−10−5−1014−4−5−49)
  3. Invert it. Zbus=j(0.2000.2000.2000.2000.2820.2360.2000.2360.327)
  4. Read bus 1. Z11 is just the generator's 0.2, since bus 1 connects straight to it.
  5. Check bus 3. Z33 = 0.327 matches the series–parallel reduction 0.2+0.2∥0.35 and a fault at bus 3 draws 3.06 pu.

Answer Ybus and Zbus are the matrices above; Z33 = j0.327, so a fault at bus 3 draws 3.06 pu.

Worked example

A line has series impedance j0.1 pu and total charging susceptance 0.2 pu. What does it add to its end buses' diagonal entries?

Show the solution
  1. Series branch. 1/(j0.1)=−j10
  2. Charging. Half the charging, j0.1, goes at each end.
  3. Add them up. Each diagonal gets ΔYii=−j10+j0.1=−j9.9 and each off-diagonal gets +j10.
  4. When charging matters. For short lines the charging term is small; for long EHV lines it can be a third of the series term.

Answer −j9.9 added to each end bus's diagonal entry, and +j10 to each off-diagonal.

Worked example

Two buses are joined by a line of j0.2 pu, and each has a generator of j0.4 pu to ground. Find Zbus, the fault current for a bolted fault at bus 1, and bus 2's voltage during it.

Show the solution
  1. Admittance matrix. From the susceptances: Y=j(−7.555−7.5)
  2. Invert it. Zbus=j(0.240.160.160.24)
  3. Fault current. If=1/Z11=4.17pu
  4. Bus 2's voltage. V2=1−Z21If=1−0.16×4.17=0.33pu
  5. Why fault studies use it. Zbus gives the whole network's response to an injection at any bus.

Answer Zbus has j0.24 on the diagonal and j0.16 off it; the fault draws 4.17 pu, and bus 2 falls to 0.33 pu.

Check

Bus 1 has lines of reactance j\given0.1 and j\given0.08 pu and a generator of j\given0.3 pu to its source. What's the magnitude of the susceptance in Y11?

Check

A line has series reactance j\given0.08 pu and total charging susceptance 0.04 pu. What net susceptance magnitude does it add to each end's diagonal?

Check

A transformer of reactance j\given0.05 pu has an off-nominal tap a = 0.95 on bus i's side. What's the magnitude of Yij?

Check

A generator (j\given0.1) at bus 1 feeds bus 3 directly through j\given0.1 and through bus 2 by j\given0.3 then j\given0.4. What's Z33?

Check

A bus has Zkk = j0.15 pu and prefault voltage 0.95 pu. What's its bolted three-phase fault current?

Check

In a 10000-bus network each bus connects to 3 others on average. About how many nonzero entries does Ybus have?

Check

Two buses are joined by j0.1 pu, and each has a generator of j0.2 pu to ground.

(a)

What is |Z11|?

(b)

What is the bolted-fault current at bus 1, from 1 pu?

(c)

What voltage does bus 2 hold during that fault?

Check

Two buses joined by jx, each with a generator jg to ground.

Step 1

What is |B11|?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why is Zkk, a diagonal entry of the inverse of Ybus, the Thevenin impedance at bus k?

Practice

Keep practicing

10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.