S10 · Lesson 10 · The bus admittance and impedance matrices
Nodal equations for a power network, building the bus admittance matrix by inspection, line charging and off-nominal taps in it, its sparsity, and the bus impedance matrix whose diagonal gives each bus's Thevenin impedance
A real grid model has tens of thousands of buses, and every power-flow and fault program starts the same way: write the nodal equations I = YV for the whole network. The bus admittance matrix can be written down by inspection, one line at a time, and it's almost all zeros because each bus connects to only a few others. Its inverse, the bus impedance matrix, is full, but its diagonal holds something every protection engineer wants: the Thevenin impedance seen at each bus, and so its fault current.
- A three-bus network: a generator behind j0.2 pu at bus 1, lines of j0.1 (1–2) and j0.2 (1–3), and a line of reactance between buses 2 and 3.
- The plot shows the Thevenin reactance at bus 3, , against , and the three-phase fault current there (1/).
- With no 2–3 line (large ) bus 3 is fed through 0.4 pu. Adding the parallel path lowers the impedance and raises the fault current: meshing a network makes it stiffer.
Predict
In a network's bus admittance matrix, what's the off-diagonal entry for two buses joined by a line of series impedance ?
In the nodal equation for bus i, the line contributes , so the coefficient of is , and adds to the diagonal . Buses not directly connected have = 0, which is why the matrix is sparse.
Name it
Nodal equations
With bus voltages V (to ground) and currents I injected into the buses, I = YV.
Building by inspection
For each branch between buses i and j with series admittance :
- add to and ;
- subtract from and .
Shunt elements (half of each line's charging susceptance at each end in the π model, capacitor banks, reactors, loads modeled as admittances, generator reactances to an internal source node) add only to their bus's diagonal. Without any connection to ground, Y is singular.
Off-nominal transformers
A transformer with series admittance y and a tap ratio a:1 on bus i's side contributes to , y to , and to and . Phase-shifting transformers make Y unsymmetric.
Sparsity
A bus typically connects to two to four others, so a 10,000-bus Y has about 99.97% zeros. Programs store only the nonzeros and factor with orderings that keep the factors sparse (lesson 43 of A13).
, full rather than sparse. is the Thevenin impedance at bus k with all sources shorted, so a bolted three-phase fault there draws , and gives how much the fault depresses bus i: (lesson 36).
Worked example
Build and for the three-bus network with = 0.25.
Show the solution
- Branch admittances. They are −j10 (1–2), −j5 (1–3), −j4 (2–3) and −j5 (generator at bus 1).
- Build .
- Invert it.
- Read bus 1. is just the generator's 0.2, since bus 1 connects straight to it.
- Check bus 3. = 0.327 matches the series–parallel reduction and a fault at bus 3 draws 3.06 pu.
Answer and are the matrices above; = j0.327, so a fault at bus 3 draws 3.06 pu.
Worked example
A line has series impedance j0.1 pu and total charging susceptance 0.2 pu. What does it add to its end buses' diagonal entries?
Show the solution
- Series branch.
- Charging. Half the charging, j0.1, goes at each end.
- Add them up. Each diagonal gets and each off-diagonal gets +j10.
- When charging matters. For short lines the charging term is small; for long EHV lines it can be a third of the series term.
Answer −j9.9 added to each end bus's diagonal entry, and +j10 to each off-diagonal.
Worked example
Two buses are joined by a line of j0.2 pu, and each has a generator of j0.4 pu to ground. Find , the fault current for a bolted fault at bus 1, and bus 2's voltage during it.
Show the solution
- Admittance matrix. From the susceptances:
- Invert it.
- Fault current.
- Bus 2's voltage.
- Why fault studies use it. gives the whole network's response to an injection at any bus.
Answer has j0.24 on the diagonal and j0.16 off it; the fault draws 4.17 pu, and bus 2 falls to 0.33 pu.
Check
Bus 1 has lines of reactance j\given0.1 and j\given0.08 pu and a generator of j\given0.3 pu to its source. What's the magnitude of the susceptance in ?
Check
A line has series reactance j\given0.08 pu and total charging susceptance 0.04 pu. What net susceptance magnitude does it add to each end's diagonal?
Check
A transformer of reactance j\given0.05 pu has an off-nominal tap a = 0.95 on bus i's side. What's the magnitude of ?
Check
A generator (j\given0.1) at bus 1 feeds bus 3 directly through j\given0.1 and through bus 2 by j\given0.3 then j\given0.4. What's ?
Check
A bus has = j0.15 pu and prefault voltage 0.95 pu. What's its bolted three-phase fault current?
Check
In a 10000-bus network each bus connects to 3 others on average. About how many nonzero entries does have?
Check
Two buses are joined by j0.1 pu, and each has a generator of j0.2 pu to ground.
(a)
What is ?
(b)
What is the bolted-fault current at bus 1, from 1 pu?
(c)
What voltage does bus 2 hold during that fault?
Check
Two buses joined by jx, each with a generator jg to ground.
Step 1
What is ?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is ?
Step 3
What is ?
Explain why
Why is , a diagonal entry of the inverse of , the Thevenin impedance at bus k?
Since V = ZI, the k-th column of Z gives the bus voltages when one unit of current is injected at bus k and none anywhere else. With every source replaced by its internal impedance (shorted voltage sources), that's exactly the experiment that measures a Thevenin impedance: inject a current at the port and see what voltage it produces there. is that voltage per unit of current. The other entries in the column, , say how much each other bus's voltage moves, which is how a fault program finds the voltages all over the network during a fault at bus k.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.