S10 Power system analysis · Practice
The bus admittance and impedance matrices
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
0 solved
0 in a row
0 of 10 kinds solid
Check
Bus 1 has lines of reactance j\given0.1 and j\given0.08 pu and a generator of j\given0.3 pu to its source. What's the magnitude of the susceptance in ?
Check
A line has series reactance j\given0.08 pu and total charging susceptance 0.04 pu. What net susceptance magnitude does it add to each end's diagonal?
Check
A transformer of reactance j\given0.05 pu has an off-nominal tap a = 0.95 on bus i's side. What's the magnitude of ?
Check
A generator (j\given0.1) at bus 1 feeds bus 3 directly through j\given0.1 and through bus 2 by j\given0.3 then j\given0.4. What's ?
Check
A bus has = j0.15 pu and prefault voltage 0.95 pu. What's its bolted three-phase fault current?
Check
In a 10000-bus network each bus connects to 3 others on average. About how many nonzero entries does have?
Check
Two buses are joined by j0.1 pu, and each has a generator of j0.2 pu to ground.
(a)
What is ?
(b)
What is the bolted-fault current at bus 1, from 1 pu?
(c)
What voltage does bus 2 hold during that fault?
Check
for branches j\given0.04, j\given0.1 and a generator j\given0.35?
Check
Net diagonal susceptance from a line j\given0.03 with charging 0.1?
Check
Fault current at a bus with = j0.05, = 0.98?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10