S10 · Lesson 39 · Sequence networks of a system and open-conductor faults

Assembling a system's positive-, negative- and zero-sequence networks, the zero-sequence paths of the five transformer connections, fault currents seen through a delta–wye transformer, and one or two broken conductors as series faults

A storm breaks one phase conductor of a loaded line, and the broken end falls clear without touching anything. No short circuit, no large current. Yet the generators at both ends start heating from negative-sequence current, and a ground relay three substations away sees current in the earth. And when a line-to-ground fault occurs on the low side of a delta–wye transformer, the relays on the high side see current in only two of the three phases. Both puzzles are sequence networks again, this time assembled for a whole system.

  • Phase a of a line opens while the line carries a balanced current. Looking into the break, each sequence network is an impedance: Z1′ and Z2′ (equal here) and Z0′. The x axis is the ratio Z0′/Z1′.
  • The curves are, in multiples of the prefault current: the current left in each healthy phase, the current returning through the ground (3I0) and the negative-sequence current.
  • With a weak zero-sequence path (large ratio), the healthy phases carry about 87% of the prefault current with little ground current. With a strong one, more current returns through the earth, and the negative sequence drops.

Predict

A bolted line-to-ground fault on the grounded-wye low side of a delta–wye transformer draws 3 pu. What do the high-side (delta) line currents look like?

Name it

Assembling the sequence networks

Each element contributes to each network:

  • Positive sequence: the ordinary per-phase network, with generators' internal voltages behind their reactances (X″ for faults).
  • Negative sequence: the same network with negative-sequence impedances and no sources. Lines and transformers have Z2=Z1; machines have their own Z2.
  • Zero sequence: no sources, and only the paths zero-sequence current can actually use. Lines have Z0 two to four times Z1. A neutral impedance Zn appears as 3Zn, because all three phases' zero-sequence currents flow through it.

Transformers in the zero-sequence network

Zero-sequence current needs a return path through a grounded neutral, and a delta can circulate it but never pass it to its lines:

ConnectionZero-sequence path
grounded wye to grounded wyethrough the transformer, side to side
grounded wye to deltafrom the wye side's lines to the reference; the delta side's lines are open
ungrounded wye to anythingopen on the wye side
delta to deltaopen on both sides
wye grounded through Zn to deltaas grounded wye to delta, with 3Zn in series

Phase shifts

A wye–delta transformer shifts positive-sequence quantities by 30° and negative-sequence quantities by −30° (in North American practice, the high side leads). Fault calculations solve the sequence networks ignoring the shift, then apply it when converting currents and voltages on the far side back to phases. That's why a line-to-ground fault on one side shows up as current in two phases on the other.

Open conductors

A broken conductor is a series fault: it acts between two points p and p′ along the line rather than from a bus to ground. Looking into the break, each sequence network presents the line itself in series with the rest of the network between the line's ends: Zi′=Zi,line+Zi,rest. The positive-sequence network also contains a source: the open-circuit voltage across the break is the prefault line current times Z1′.

  • One conductor open (Ia=0, equal sequence voltage drops across the break): the three networks connect in parallel at p–p′. The positive-sequence current is I1=IZ1′/(Z1′+Z2′∥Z0′).
  • Two conductors open (Ib=Ic=0): the three networks connect in series, I1=I2=I0=IZ1′/(Z1′+Z2′+Z0′), and the phase still closed carries 3I1.

Grainger and Stevenson derive the same results from the intact system's Zbus by adding −Z of the line between its buses and injecting compensating currents, which is how programs compute the voltage changes everywhere.

Worked example

A line carries 1 pu when phase a breaks. Looking into the break, Z1′=Z2′ = j0.8 pu (the line's j0.2 plus j0.6 through the rest of the network) and Z0′ = j1.6 pu. Find the sequence and phase currents.

Show the solution
  1. Connect the networks. One open conductor puts the networks in parallel: Z2′∥Z0′=j0.533
  2. Positive-sequence current. I1=1×0.8/(0.8+0.533)=0.6pu
  3. Voltage across the break. V=1×0.8×0.533/1.333=0.32pu
  4. Negative and zero sequences. That voltage drives I2=−0.32/0.8=−0.4puI0=−0.32/1.6=−0.2pu
  5. Check. I1+I2+I0 = 0: phase a carries nothing.
  6. Phases b and c. Ib=I0+a2I1+aI2=−0.3−j0.866pu and phase c carries −0.3 + j0.866 pu: 0.92 pu each, nearly the prefault current.
  7. Ground and negative sequence. The ground carries 3I0 = 0.6 pu, which ground relays may take for a fault, and 0.4 pu of negative-sequence current flows through the generators, heating their rotors.

Answer I1 = 0.6, I2 = −0.4 and I0 = −0.2 pu; phase a carries nothing, and phases b and c carry 0.92 pu each.

Worked example

In the same line, phases b and c break instead. What's left?

Show the solution
  1. Connect the networks. Two open conductors put the networks in series, so I1=I2=I0 with I1=1×0.80.8+0.8+1.6=0.25pu
  2. Phase a. It carries 3I1 = 0.75 pu, all of it returning through the ground.
  3. Negative sequence. The negative-sequence current is now 0.25 pu.
  4. Where this happens on purpose. Single-pole tripping schemes, which open only the faulted phase for a moment, create exactly these conditions on purpose, and the system must ride through them for the dead time before reclosing.

Answer phase a carries 0.75 pu, all of it returning through the ground, with 0.25 pu in each sequence.

Worked example

An ungrounded delta system gets a zigzag grounding transformer with a zero-sequence impedance of j0.05 pu. With Z1=Z2 = j0.2 pu at the bus, what single line-to-ground fault current can now flow?

Show the solution
  1. Without a ground path. Z0 is infinite and a ground fault draws almost no current.
  2. With the zigzag. It supplies a zero-sequence path, so If=3/(0.2+0.2+0.05)=6.67pu
  3. In normal operation. It carries no positive- or negative-sequence current, which is why it can ground a delta system without changing its load flow.

Answer 6.67 pu.

Check

A line of j0.2 pu runs between two buses that are also connected through the rest of the network by j0.3 pu. What impedance, in per unit, does one sequence network present across a break in the line?

Check

One conductor of a line carrying 1 pu opens. Across the break Z1′=Z2′ = j0.5 and Z0′ = j3 pu. What's the positive-sequence current, in per unit?

Check

Two conductors of a line carrying 1 pu open. Across the break Z1′=Z2′ = j0.5 and Z0′ = j3 pu. What current, in per unit, does the remaining conductor carry?

Check

One conductor of a line carrying 1 pu opens. Across the break Z1′=Z2′ and Z0′ is 1 times as large. How much current returns through the ground, in per unit?

Check

A bolted line-to-ground fault on the grounded-wye side of a delta–wye transformer draws 3 pu. How much current, in per unit, flows in each of the two faulted phases on the delta side?

Check

Which transformer connection lets zero-sequence current flow from one side's lines through to the other side's lines?

Check

An ungrounded delta system has Z1=Z2 = j0.2 pu at a bus; a zigzag grounding transformer adds a zero-sequence impedance of j0.02 pu.

(a)

What single line-to-ground fault current can flow?

(b)

How does it compare with the three-phase fault current, as a ratio?

Check

A solidly grounded bus has Z1=Z2 = ja and Z0 = jc.

Step 1

What is the line-to-ground fault current?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why do the sequence networks connect in parallel at the break for one open conductor, but in series for two?

Practice

Keep practicing

9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.