S10 Power system analysis · Practice
Sequence networks of a system and open-conductor faults
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
0 solved
0 in a row
0 of 9 kinds solid
Check
A line of j0.2 pu runs between two buses that are also connected through the rest of the network by j0.3 pu. What impedance, in per unit, does one sequence network present across a break in the line?
Check
One conductor of a line carrying 1 pu opens. Across the break = j0.5 and = j3 pu. What's the positive-sequence current, in per unit?
Check
Two conductors of a line carrying 1 pu open. Across the break = j0.5 and = j3 pu. What current, in per unit, does the remaining conductor carry?
Check
One conductor of a line carrying 1 pu opens. Across the break and is 1 times as large. How much current returns through the ground, in per unit?
Check
A bolted line-to-ground fault on the grounded-wye side of a delta–wye transformer draws 3 pu. How much current, in per unit, flows in each of the two faulted phases on the delta side?
Check
An ungrounded delta system has = j0.2 pu at a bus; a zigzag grounding transformer adds a zero-sequence impedance of j0.02 pu.
(a)
What single line-to-ground fault current can flow?
(b)
How does it compare with the three-phase fault current, as a ratio?
Check
One open: I = 0.73, = 0.43, = 2.9. ?
Check
Two open: I = 0.73, = 0.43, = 2.9. Current in the closed phase?
Check
LG fault of 1.5 pu on the wye side of a delta–wye. Delta-side current in each faulted phase?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10