Problem set 11: choosing a transmission voltage, correcting power factor, sizing series and shunt compensation, limiting fault levels, rating breakers, setting relays, detuning capacitor banks, regulating feeders and sizing fast frequency response

Each problem here is a small design decision of the kind a transmission or distribution engineer makes: a voltage, a rating, a setting or a size, worked from the requirement to a number you could put in a specification.

Check

A 500 MW load at power factor 0.95 is to be supplied over 300 km of line with 0.05 Ω/km per phase, losing at most 3%.

(a)

What is the lowest line voltage that meets the loss limit?

Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.

Check

A 20 MW plant at power factor 0.7 is to be corrected to 0.98.

(a)

How large a capacitor bank?

Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.

(b)

By how much does the supply current fall?

Check

A line of X = 0.6 pu between 1 pu buses must carry 1.8 pu at an angle of no more than 40°.

(a)

What series compensation does that require?

Check

A 34.5 kV substation transformer fed from a 5000 MVA source must keep the fault level on its secondary below 2000 MVA.

(a)

What is the least transformer reactance, in per unit on 100 MVA?

Check

A breaker at a 13.8 kV bus with a 2000 MVA fault level must interrupt with an asymmetry factor of 1.15.

(a)

What symmetrical fault current must it handle?

Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.

(b)

And its asymmetrical interrupting current?

Check

A feeder carries at most 450 A of load. Its overcurrent relay picks up at 1.5 times that, through a CT with 1 A secondary rating, chosen as the smallest standard ratio of 100, 200, 400, 600, 800, 1200 or 1600 to 1 that covers the maximum load.

(a)

What primary pickup current is set?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

(b)

What secondary pickup current does the relay see?

Check

A line has 45 Ω of positive-sequence impedance; CT ratio 120, VT ratio 2000. Zone 1 covers 80% and zone 2 120% of the line.

(a)

What zone 1 reach, in secondary ohms?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

(b)

And zone 2?

Check

A 5 Mvar capacitor bank at a bus with a 250 MVA fault level is to be detuned to the 4.3th harmonic.

(a)

Where would it resonate without detuning?

(b)

What series reactor, as a percentage of the capacitor's reactance, tunes it to 4.3?

Check

A feeder's far end runs 7% low at peak. A regulator at the substation steps 0.625% per tap.

(a)

How many steps up bring the far end within 1% of nominal?

Check

A 10 GW system with H = 2 s must keep ROCOF below 0.5 Hz/s after losing 2 GW.

(a)

What ROCOF does the loss cause without help?

Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.

(b)

How much fast frequency response must act at once to meet the limit (zero if none)?

Check

A radial line of X = 0.2 pu from a 1 pu source supplies load at power factor 0.9 lagging, with a required loadability margin of 30%.

(a)

What is the most load it may carry?

Check

A unit loses 200 dollars per hour running at 500 MW through a night of off-peak prices; restarting costs 400 dollars per start plus 60 dollars per MW of minimum output to warm up.

(a)

Above how many off-peak hours is shutting down cheaper?

Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.