S10 · Problem set 2

Problem set 2: short, medium and long lines, real and reactive power flow, compensation, surges and HVDC, and the bus admittance and impedance matrices

These problems cover lessons 6 to 11: line models with the Ferranti rise and charging vars, power transfer, voltage drop and the nose curve, series and shunt compensation, surges on lines and cables and HVDC converters, and building, reducing and using the bus admittance and impedance matrices.

Check

An overhead line 350 km long (wavelength 4940 km), 230 kV, B = 5.5 µS/km.

(a)

Open-end voltage rise factor?

(b)

Charging vars at rated voltage?

Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.

Check

A lossless line, L = 0.9 mH/km, C = 9.5 nF/km, 450 km, loaded resistively at 1.4 times SIL.

(a)

Electrical length βl?

(b)

Receiving voltage relative to sending?

Check

A medium line: x = 0.35 Ω/km, b = 3.5 µS/km, 220 km, lossless.

(a)

Nominal-π A?

(b)

No-load VR/VS?

Check

Buses at 0.97 and 0.95 pu, angle 30° apart, across X = 0.4 pu.

(a)

Real power?

(b)

Reactive power leaving bus 1?

(c)

Steady-state transfer limit?

Check

A 1 pu source feeds a unity-pf load of 0.3 pu through X = 0.2 pu; separately, a feeder R = 0.06, X = 0.2 carries 0.3 + j0.35 pu.

(a)

Receiving voltage on the upper branch?

(b)

Maximum deliverable power at unity pf?

(c)

Feeder voltage drop estimate?

Check

A line of X = 0.3 pu between 1 pu buses, with 0.3 series compensation, carries 1.5 pu.

(a)

Transfer limit?

(b)

Angle needed?

(c)

Angle without compensation?

Check

A 25 Mvar capacitor and a 25 Mvar STATCOM at a bus of 4000 MVA short-circuit level.

(a)

Capacitor's output at 0.8 pu?

Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.

(b)

STATCOM's output at 0.8 pu?

(c)

Voltage rise when the capacitor is switched on at 1 pu?

Check

A line of X = 0.3 pu between buses held at 0.98 pu.

(a)

Transfer limit?

(b)

Limit with the midpoint held at 0.98 pu?

Check

Bus 1 has lines of j\given0.06 and j\given0.1 pu (the first with total charging 0.3 pu) and a generator of j\given0.25.

(a)

|B11| ignoring charging?

(b)

Including the first line's charging?

(c)

Off-diagonal magnitude to the first line's far bus?

Check

A transformer j\given0.06 pu with tap a = 0.95 on bus i's side.

(a)

Its contribution to |Yii|?

(b)

|Yij|?

Check

Generator j\given0.12 at bus 1; bus 3 fed directly by j\given0.15 and via bus 2 by j\given0.2 + j\given0.5. Prefault 1 pu.

(a)

Z33?

(b)

Fault current at bus 3?

Check

A 2000-bus network with 2.5 connections per bus on average.

(a)

Nonzeros in Ybus?

(b)

Fraction of entries that are nonzero?

Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.