S10 Power system analysis · Practice
Problem set 2: line models, power transfer, compensation and network matrices
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
An overhead line 350 km long (wavelength 4940 km), 230 kV, B = 5.5 µS/km.
(a)
Open-end voltage rise factor?
(b)
Charging vars at rated voltage?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A lossless line, L = 0.9 mH/km, C = 9.5 nF/km, 450 km, loaded resistively at 1.4 times SIL.
(a)
Electrical length βl?
(b)
Receiving voltage relative to sending?
Check
A medium line: x = 0.35 Ω/km, b = 3.5 µS/km, 220 km, lossless.
(a)
Nominal-π A?
(b)
No-load ?
Check
Buses at 0.97 and 0.95 pu, angle 30° apart, across X = 0.4 pu.
(a)
Real power?
(b)
Reactive power leaving bus 1?
(c)
Steady-state transfer limit?
Check
A 1 pu source feeds a unity-pf load of 0.3 pu through X = 0.2 pu; separately, a feeder R = 0.06, X = 0.2 carries 0.3 + j0.35 pu.
(a)
Receiving voltage on the upper branch?
(b)
Maximum deliverable power at unity pf?
(c)
Feeder voltage drop estimate?
Check
A line of X = 0.3 pu between 1 pu buses, with 0.3 series compensation, carries 1.5 pu.
(a)
Transfer limit?
(b)
Angle needed?
(c)
Angle without compensation?
Check
A 25 Mvar capacitor and a 25 Mvar STATCOM at a bus of 4000 MVA short-circuit level.
(a)
Capacitor's output at 0.8 pu?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(b)
STATCOM's output at 0.8 pu?
(c)
Voltage rise when the capacitor is switched on at 1 pu?
Check
A line of X = 0.3 pu between buses held at 0.98 pu.
(a)
Transfer limit?
(b)
Limit with the midpoint held at 0.98 pu?
Check
Bus 1 has lines of j\given0.06 and j\given0.1 pu (the first with total charging 0.3 pu) and a generator of j\given0.25.
(a)
ignoring charging?
(b)
Including the first line's charging?
(c)
Off-diagonal magnitude to the first line's far bus?
Check
A transformer j\given0.06 pu with tap a = 0.95 on bus i's side.
(a)
Its contribution to ?
(b)
?
Check
Generator j\given0.12 at bus 1; bus 3 fed directly by j\given0.15 and via bus 2 by j\given0.2 + j\given0.5. Prefault 1 pu.
(a)
?
(b)
Fault current at bus 3?
Check
A 2000-bus network with 2.5 connections per bus on average.
(a)
Nonzeros in ?
(b)
Fraction of entries that are nonzero?
Check
A 600 kV surge on an overhead line ( = 350 Ω) enters a substation through a short cable ( = 50 Ω) that ends at an open breaker.
(a)
Voltage entering the cable?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
(b)
Voltage at the open breaker when that wave first arrives?
(c)
Reflection coefficient, at the cable–line junction, for the wave returning up the cable?
Check
A rectifier has 220 kV RMS on its valve side, fires at α = 12° and carries 2.5 kA through = 12 Ω.
(a)
Ideal no-load DC voltage ?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
(b)
DC voltage at this operating point?
(c)
Power sent by this pole?
Check
Build branch by branch: a generator of j0.1 pu at bus 1, a line of j0.1 from bus 1 to new bus 2, a line of j0.25 from bus 1 to new bus 3, then a line of j0.4 between buses 2 and 3.
(a)
before the 2–3 line is added, in per unit?
(b)
after the 2–3 line, in per unit?
(c)
Bolted three-phase fault current at bus 3, in per unit?
Check
Bus 2 has no load or generation and connects only to bus 1 (j0.05 pu) and bus 3 (j0.1 pu). Buses 1 and 3 are also joined directly by j0.3 pu. Bus 2 is eliminated by Kron reduction.
(a)
Magnitude of the reduced network's susceptance between buses 1 and 3?
(b)
Equivalent reactance between buses 1 and 3, in per unit?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10