S10 · Problem set 3
Problem set 3: conductor heat balances and dynamic ratings, sag and clearance, P–V noses and reactive margins, load recovery under tap changers, exact long-line constants and traveling-wave lattices
These problems cover lessons 13 to 15: the thermal limits of lines and the sag that comes with heat, how far a network can be loaded before its voltage collapses and how to measure the margin, and the computations of the line lab, from parameters and exact ABCD constants to surges bouncing between the ends.
Check
A conductor of diameter 28 mm with 0.06 Ω/km at 100 °C is rated in 35 °C air with h = 20 W/m²K, ε = α = 0.5 and 900 W/m² of sun.
(a)
What is its ampacity?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What share of the cooling is convective?
Check
At its rating a conductor sheds 60 W/m by convection and 12 W/m by radiation and absorbs 15 W/m of sun. The wind changes convection by a factor of 3.
(a)
What fraction of its static rating may it now carry?
Check
A span of 250 m carries a conductor of 16 N/m at 35 kN tension; it then heats by 70 °C ( = 19 × 10⁻⁶/°C, ignore elastic stretch).
(a)
What is the initial sag?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
(b)
How much does the sag grow?
Check
A source of 1 pu feeds 0.8 pu at power factor 0.95 lagging through X = 0.15 pu.
(a)
What is the loadability margin?
(b)
At what voltage would collapse occur?
Check
A 1 pu slack feeds 1 + j0.1 pu through lossless X = 0.15 pu.
(a)
What is the operating voltage?
(b)
What angle does the load bus sit behind the slack?
Check
A 1 pu source supplies 1 pu at unity power factor through X = 0.05 pu.
(a)
What reactive margin does its Q–V curve show?
(b)
How many vars must be supplied at the bus to hold it at 1 pu?
Check
After a disturbance a distribution bus sags to 0.9 pu; its load's power varies as with n = 1. Tap changers then restore it to 1 pu.
(a)
By what percentage did the sag cut the load's power?
(b)
By what percentage does restoring the voltage raise it again from the sagged level?
Check
A transposed line has phase spacings 6, 6 and 16 m and two-conductor bundles 0.4 m apart, each conductor with GMR 0.012 m.
(a)
What is the geometric mean distance?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
(b)
What is its inductance?
Check
A lossless line with x = 0.35 Ω/km and b = 4.5 µS/km is 500 km long.
(a)
What is βl?
(b)
How much does its open far end rise?
Check
A step of 1 pu through source resistance 0 Ω energizes an open-ended line with = 300 Ω.
(a)
What voltage first appears at the far end?
(b)
What is the source's reflection coefficient?
Check
A 30 kA lightning stroke hits a phase conductor of a 50 km line ( = 250 Ω, wave speed 300 m/µs) and splits both ways.
(a)
How long does a surge take to travel the line's length and back?
Write units the way you normally would: 1.5 µs, 1500 ns and 0.0015 ms are the same answer.
(b)
What voltage does the stroke raise on the conductor?
Check
A 345 kV line of 100 km (b = 4.5 µS/km) is energized unloaded, and shunt reactors absorb 0.8 of its charging.
(a)
How many vars does the source still have to absorb?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A conductor with 1.6 kg/m (specific heat 900 J/kg·K) gains 3 W/m of net cooling per kelvin near its operating point.
(a)
What is its thermal time constant?
(b)
What fraction of its final temperature rise does a step in current produce after 10 minutes?
Check
Two buses look alike in a power flow: both at 0.97 pu. One has mostly motor loads and little reactive reserve nearby; the other has resistive loads and a large synchronous condenser. Which is closer to voltage collapse, and how would you show it?
Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.
Practice
Keep practicing
13 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.