S10 Power system analysis · Practice
Problem set 3: ampacity, voltage stability and line computations
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A conductor of diameter 28 mm with 0.06 Ω/km at 100 °C is rated in 35 °C air with h = 20 W/m²K, ε = α = 0.5 and 900 W/m² of sun.
(a)
What is its ampacity?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What share of the cooling is convective?
Check
At its rating a conductor sheds 60 W/m by convection and 12 W/m by radiation and absorbs 15 W/m of sun. The wind changes convection by a factor of 3.
(a)
What fraction of its static rating may it now carry?
Check
A span of 250 m carries a conductor of 16 N/m at 35 kN tension; it then heats by 70 °C ( = 19 × 10⁻⁶/°C, ignore elastic stretch).
(a)
What is the initial sag?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
(b)
How much does the sag grow?
Check
A source of 1 pu feeds 0.8 pu at power factor 0.95 lagging through X = 0.15 pu.
(a)
What is the loadability margin?
(b)
At what voltage would collapse occur?
Check
A 1 pu slack feeds 1 + j0.1 pu through lossless X = 0.15 pu.
(a)
What is the operating voltage?
(b)
What angle does the load bus sit behind the slack?
Check
A 1 pu source supplies 1 pu at unity power factor through X = 0.05 pu.
(a)
What reactive margin does its Q–V curve show?
(b)
How many vars must be supplied at the bus to hold it at 1 pu?
Check
After a disturbance a distribution bus sags to 0.9 pu; its load's power varies as with n = 1. Tap changers then restore it to 1 pu.
(a)
By what percentage did the sag cut the load's power?
(b)
By what percentage does restoring the voltage raise it again from the sagged level?
Check
A transposed line has phase spacings 6, 6 and 16 m and two-conductor bundles 0.4 m apart, each conductor with GMR 0.012 m.
(a)
What is the geometric mean distance?
Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.
(b)
What is its inductance?
Check
A lossless line with x = 0.35 Ω/km and b = 4.5 µS/km is 500 km long.
(a)
What is βl?
(b)
How much does its open far end rise?
Check
A step of 1 pu through source resistance 0 Ω energizes an open-ended line with = 300 Ω.
(a)
What voltage first appears at the far end?
(b)
What is the source's reflection coefficient?
Check
A 30 kA lightning stroke hits a phase conductor of a 50 km line ( = 250 Ω, wave speed 300 m/µs) and splits both ways.
(a)
How long does a surge take to travel the line's length and back?
Write units the way you normally would: 1.5 µs, 1500 ns and 0.0015 ms are the same answer.
(b)
What voltage does the stroke raise on the conductor?
Check
A 345 kV line of 100 km (b = 4.5 µS/km) is energized unloaded, and shunt reactors absorb 0.8 of its charging.
(a)
How many vars does the source still have to absorb?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A conductor with 1.6 kg/m (specific heat 900 J/kg·K) gains 3 W/m of net cooling per kelvin near its operating point.
(a)
What is its thermal time constant?
(b)
What fraction of its final temperature rise does a step in current produce after 10 minutes?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10