Problem set 7: three-phase faults, symmetrical components, unsymmetrical and open-conductor faults, and protective relaying

These problems cover lessons 36 to 40: subtransient fault currents, DC offset and short-circuit levels, fault calculations with the bus impedance matrix, sequence components, the four fault types and neutral grounding, faults seen through delta–wye transformers, open conductors, and setting overcurrent, distance and differential relays.

Check

A 300 MVA, 18 kV generator (X″ = 0.12 pu) with an 18/138 kV transformer (X = 0.08 pu on 300 MVA).

(a)

Terminal fault current?

Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.

(b)

Fault current on the 138 kV side?

(c)

Short-circuit level there?

Check

A fault at bus k (Zkk = j0.25) with Zik = j0.1 and Zjk = j0.15, prefault 1 pu.

(a)

Fault current?

(b)

Bus i voltage?

(c)

Voltage difference between buses j and i?

Check

A 15 kA symmetrical fault where X/R = 20; and a bus fed by sources of 0.3 and 0.5 pu.

(a)

Worst first peak?

Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.

(b)

Fault current at the bus in pu?

Check

Phase currents 90∠0°, 60∠−120°, 120∠120° A; and a line-to-line load of 60 A.

(a)

Neutral current?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

(b)

Positive-sequence magnitude?

(c)

Line-to-line load's negative-sequence current?

Check

Phase b sags to 0.88 pu; separately, V1 = 1 and V2 = 0.15 pu; and a negative-sequence voltage at 10° on a Y–Δ low side.

(a)

Unbalance from the sag?

(b)

|V_b| for the second case?

(c)

Its angle on the high side?

Check

A bus with Z1=Z2 = j0.2 and Z0 = j0.08 pu.

(a)

Three-phase fault current?

(b)

Line-to-ground?

(c)

Line-to-line?

Check

A bus with Z1=Z2 = j0.15, Z0 = j0.15.

(a)

Ground current for a double line-to-ground fault?

(b)

Line-to-ground current through 0.15 pu of fault resistance?

Check

Neutral grounding for a bus with Z1=Z2 = j0.15, Z0 = j0.1.

(a)

Reactance limiting ground faults to 2 pu?

(b)

Ground-to-three-phase ratio when solidly grounded?

Check

A 300:1 CT on a feeder with a very inverse relay (dial 1.5) picking up at 1.2 A secondary; fault current 2500 A.

(a)

CT secondary current?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

(b)

Multiple of pickup?

(c)

Operating time?

Check

A downstream relay operates in 0.25 s; an upstream very inverse relay sees 4 times pickup for the same fault; coordination interval 0.4 s.

(a)

Required upstream time?

Write units the way you normally would: 1.5 s and 1500 ms are the same answer.

(b)

Upstream time dial?

Check

A line of 25 Ω, CT ratio 200, VT ratio 3000.

(a)

Line in secondary ohms?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

(b)

Zone 1 setting (0.85 of the line), secondary?

(c)

Zone 2 setting (1.2 of the line), secondary?

Check

A differential relay with slope 0.35 sees 8 A in and 7 A out.

(a)

Operating current?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

(b)

As a percentage of the restraint?

Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.