Problem set 7: faults and protection
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A 300 MVA, 18 kV generator (X″ = 0.12 pu) with an 18/138 kV transformer (X = 0.08 pu on 300 MVA).
(a)
Terminal fault current?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(b)
Fault current on the 138 kV side?
(c)
Short-circuit level there?
Check
A fault at bus k ( = j0.25) with = j0.1 and = j0.15, prefault 1 pu.
(a)
Fault current?
(b)
Bus i voltage?
(c)
Voltage difference between buses j and i?
Check
A 15 kA symmetrical fault where X/R = 20; and a bus fed by sources of 0.3 and 0.5 pu.
(a)
Worst first peak?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(b)
Fault current at the bus in pu?
Check
Phase currents 90∠0°, 60∠−120°, 120∠120° A; and a line-to-line load of 60 A.
(a)
Neutral current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Positive-sequence magnitude?
(c)
Line-to-line load's negative-sequence current?
Check
Phase b sags to 0.88 pu; separately, = 1 and = 0.15 pu; and a negative-sequence voltage at 10° on a Y–Δ low side.
(a)
Unbalance from the sag?
(b)
|V_b| for the second case?
(c)
Its angle on the high side?
Check
A bus with = j0.2 and = j0.08 pu.
(a)
Three-phase fault current?
(b)
Line-to-ground?
(c)
Line-to-line?
Check
A bus with = j0.15, = j0.15.
(a)
Ground current for a double line-to-ground fault?
(b)
Line-to-ground current through 0.15 pu of fault resistance?
Check
Neutral grounding for a bus with = j0.15, = j0.1.
(a)
Reactance limiting ground faults to 2 pu?
(b)
Ground-to-three-phase ratio when solidly grounded?
Check
A 300:1 CT on a feeder with a very inverse relay (dial 1.5) picking up at 1.2 A secondary; fault current 2500 A.
(a)
CT secondary current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Multiple of pickup?
(c)
Operating time?
Check
A downstream relay operates in 0.25 s; an upstream very inverse relay sees 4 times pickup for the same fault; coordination interval 0.4 s.
(a)
Required upstream time?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
Upstream time dial?
Check
A line of 25 Ω, CT ratio 200, VT ratio 3000.
(a)
Line in secondary ohms?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
Zone 1 setting (0.85 of the line), secondary?
(c)
Zone 2 setting (1.2 of the line), secondary?
Check
A differential relay with slope 0.35 sees 8 A in and 7 A out.
(a)
Operating current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
As a percentage of the restraint?
Check
One phase of a line carrying 1 pu breaks. Across the break = j0.6 pu and = j3 pu.
(a)
Positive-sequence current, in per unit?
(b)
Negative-sequence current magnitude, in per unit?
(c)
Current returning through the ground, in per unit?
Check
A bolted line-to-ground fault occurs on the grounded-wye low side (34.5 kV) of a delta–wye transformer, where = j0.15 pu and = j0.1 pu on 200 MVA.
(a)
Fault current in per unit?
(b)
Fault current in kiloamperes?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(c)
Current in each of the two faulted phases on the delta side, in per unit?
Check
A 40 kA symmetrical fault with X/R = 12 (60 Hz) is interrupted after 1.5 cycles.
(a)
What is the DC time constant?
Write units the way you normally would: 1.5 ms, 1500 µs and 0.0015 s are the same answer.
(b)
What worst-case RMS current must the breaker interrupt?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10