S10 Power system analysis · Practice
Problem set 8: stability, inverter-based resources and distribution
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A machine with H = 6 s delivers 0.9 pu with = 1.6 pu.
(a)
Equilibrium angle?
(b)
Synchronizing coefficient?
(c)
Swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A 150 MVA machine with H = 2.5 s on its rating, delivering 1 pu when a fault drops its output to zero.
(a)
Stored energy?
Write units the way you normally would: 1.5 MJ, 1500 kJ and 0.0015 GJ are the same answer.
(b)
H on a 1000 MVA base?
(c)
Angle advance in 0.06 s?
Check
A zero-transfer fault on a machine at 0.5 pu, = 1.8, H = 6 s, cleared with the network unchanged.
(a)
Critical clearing angle?
(b)
Critical clearing time?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
After clearing at 85° the curve is 1.6 sin δ with = 0.6; the machine started at its equilibrium on the same curve.
(a)
Accelerating area for a zero-transfer fault?
(b)
Available decelerating area?
Check
= 2 before the fault, 0.2 of it during, 0.7 of it after; = 1.
(a)
Post-fault unstable equilibrium?
(b)
Critical clearing angle?
Check
Two machines with H = 3 s and 5 s, = 2.5; a mode at .
(a)
?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
Swing frequency?
(c)
Damping ratio of the mode?
Check
A 90 GW system whose synchronous fleet has H = 4 s; 0.3 of generation becomes inverter-based. It loses 2 GW.
(a)
System H?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
ROCOF?
Check
A 150 MW inverter plant (fault current 1.4 × rated) at a 230 kV bus with a 600 MVA short-circuit level.
(a)
SCR?
(b)
Its fault contribution?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
An inverter of 50 MW emulating H = 3 s at 0.8 Hz/s; a 30 GW system with H = 1.5 s losing 7 GW with ROCOF capped at 0.5 Hz/s.
(a)
Synthetic inertia power?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Fast frequency response needed?
Check
A 12.47 kV feeder 3 km long, z = 0.25 + j0.5 Ω/km, carrying 6 MW at 0.85 pf.
(a)
Drop with the load lumped at the end?
(b)
With the load spread evenly?
Check
A 160 A fundamental with 12, 8 and 9 A of 3rd, 5th and 7th harmonics; a 2 Mvar capacitor at a 50 MVA bus.
(a)
THD?
(b)
Neutral third-harmonic current in a balanced set?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(c)
Resonant harmonic order?
Check
A utility of 20000 customers with 9000 interruptions averaging 120 minutes; and a DG exporting 1 MW, absorbing 0.3 Mvar, at the end of 2.5 + j1.5 Ω at 12.47 kV.
(a)
SAIDI?
(b)
SAIFI?
(c)
Voltage change at the DG?
Check
A unit with H = 5 s and = 2 pu goes from 1.2 pu to 1.8 pu of output (60 Hz).
(a)
What was its swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
What is it now?
Check
A power system stabilizer moves a mode at s⁻¹ left by 0.4 s⁻¹.
(a)
What damping ratio results?
(b)
By what factor does the halving time shrink?
Check
A 150 MW inverter plant sits at a 500 MVA bus; a 400 MVA synchronous condenser (X″ = 0.2 pu) is added there.
(a)
What short-circuit ratio results?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10