S10 · Lesson 3 · Transformers in power systems
The equivalent circuit from open- and short-circuit tests, voltage regulation and efficiency, three-phase connections and the 30° phase shift of Y–Δ banks, autotransformers, and tap changers
Between a power plant and a wall socket a kilowatt-hour typically passes through four or five transformers, each almost perfect: efficiencies above 99% are routine for large units. Their imperfections still matter. The leakage reactance sets how far the voltage sags under load and how large the fault currents are, the Y–Δ connection shifts the phase by 30° and blocks zero-sequence current, and taps let operators nudge voltages up and down by a few percent. This lesson builds the model power-system studies use.
- The phasor diagram of a loaded transformer in per unit: the secondary voltage (1 pu), the drop across the series impedance R + jX, and the primary voltage needed to supply it.
- At lagging power factor the drop adds almost in phase with the voltage, so the primary must be higher: positive regulation.
- Swing the load to leading power factor and the reactive drop turns to point backward: the secondary can end up above the primary.
Predict
A transformer has R = 0.012 pu and X = 0.060 pu. At full load and 0.8 power factor lagging, by how much does its secondary voltage drop from no load to full load?
The drop is with I = 1∠−36.9°: , so the primary needs = 1.0463 pu: 4.6% regulation. The quick estimate = 4.56% is close because the drop is nearly in phase with V.
Name it
Equivalent circuit
An ideal transformer plus a series impedance (winding resistance and leakage reactance) and a shunt branch (core loss and magnetizing reactance). In per unit the series impedance is the same from either side.
- Short-circuit test: short one winding and raise the voltage on the other until rated current flows. , , .
- Open-circuit test: rated voltage on one side, the other open: the input power is the core loss and the current is the magnetizing current.
Regulation and efficiency
Regulation is , approximately in per unit at full load (with φ positive for lagging). Efficiency is output over output plus copper loss (, varies with load) plus core loss (roughly constant).
Three-phase connections
Three single-phase units or one three-phase core, connected Y or Δ on each side. In a Y–Δ bank the line-to-line voltages on the two sides differ in phase by 30°; under the US standard the high-voltage side leads by 30° for positive sequence. A Δ winding also traps zero-sequence currents (lesson 37). A Y-connected winding's unit sees .
Autotransformers
A single tapped winding with part of the power passed by conduction. Rewiring a two-winding transformer as an autotransformer between and raises its rating to , and its per-unit series impedance falls by the factor , which raises fault currents.
Taps
Off-load taps set a fixed ratio a few percent from nominal; on-load tap changers and regulators move in steps (often ±10% in 32 steps) to hold voltage as load changes.
Worked example
A 20 kVA, 8000/240 V transformer's short-circuit test on the 8 kV side reads 489 V, 2.5 A and 240 W. Find its per-unit impedance and full-load regulation at 0.8 lagging.
Show the solution
- Series impedance from the test. so = 191.8 Ω.
- Per unit. The 8 kV base is so Z = 0.012 + j0.0599 pu.
- Regulation at 0.8 lagging.
- At 0.8 leading. The same calculation gives −2.48%: the secondary rises above no-load.
Answer Z = 0.012 + j0.0599 pu, and the full-load regulation at 0.8 lagging is 4.64%.
Worked example
A 100 kVA, 13.2/1.2 kV transformer is reconnected as a 13.2/14.4 kV autotransformer. What can it carry?
Show the solution
- What the windings carry. The windings still carry their rated currents, but now only the 1.2 kV series winding's share is transformed.
- Autotransformer rating. twelve times the two-winding rating.
- Where it's used. That's why autotransformers are used to tie systems of similar voltage, such as 345 and 230 kV.
Answer 1200 kVA, twelve times its rating as a two-winding transformer.
Worked example
A 100 kVA transformer has 500 W of core loss and 1500 W of copper loss at full load. At what load is it most efficient, and how efficient is it there and at full load (unity power factor)?
Show the solution
- Load for peak efficiency. Efficiency peaks where the copper loss, which grows as the square of the load fraction x, equals the fixed core loss:
- Efficiency there. In kW:
- Efficiency at full load.
- Why it matters. Distribution transformers, lightly loaded most of the day, are designed with low core loss for exactly this reason.
Answer it's most efficient at 57.7% of full load, where it reaches 98.30%, and 98.04% efficient at full load.
Check
A short-circuit test reads 489 V, 2.5 A and 300 W. What's the leakage reactance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A transformer with R = 0.005 pu and X = 0.04 pu runs at full load, power factor 0.9 lagging. What's its exact regulation?
Check
A 100 kVA two-winding transformer is reconnected as a 115/230 kV autotransformer. What's its new rating?
Write units the way you normally would: 1.5 kVA, 1500 VA and 0.0015 MVA are the same answer.
Check
A Y-connected bank of single-phase units serves a 230 kV line. What voltage does each unit's winding see?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
Check
A transformer rated 15 kW (unity power factor) runs at 0.75 of full load, with core loss 100 W and full-load copper loss 600 W. What's its efficiency?
Check
A regulator covers ±10% in 16 equal steps. What's one step?
Check
A 100 kVA transformer has 0.2% core loss and 3% copper loss at full load, both relative to its rating.
(a)
At what fraction of full load is it most efficient?
(b)
What efficiency does it reach there, at unity power factor?
(c)
What is the copper loss at that load?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A transformer carries load x (per unit of rating, unity power factor) with core loss c and full-load copper loss u (per unit).
Step 1
What is the copper loss?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is the efficiency?
Step 3
At what load is the efficiency highest?
Explain why
Why does a transformer's secondary voltage rise above no load when it supplies a leading load?
The voltage across the transformer's series impedance is the load current times R + jX, and in a power transformer X dominates. For a lagging load the current lags the voltage, so the drop across X, which leads the current by 90°, lines up nearly in phase with the voltage and subtracts from the secondary. For a leading load the current leads, and the jX drop swings around to point nearly opposite the voltage, so it adds to the secondary instead. That's why long cables and capacitor banks at light load can push voltages above nominal, and why operators switch capacitors out at night.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.