S10 Power system analysis · Practice
Transformers in power systems
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A short-circuit test reads 489 V, 2.5 A and 300 W. What's the leakage reactance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A transformer with R = 0.005 pu and X = 0.04 pu runs at full load, power factor 0.9 lagging. What's its exact regulation?
Check
A 100 kVA two-winding transformer is reconnected as a 115/230 kV autotransformer. What's its new rating?
Write units the way you normally would: 1.5 kVA, 1500 VA and 0.0015 MVA are the same answer.
Check
A Y-connected bank of single-phase units serves a 230 kV line. What voltage does each unit's winding see?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
Check
A transformer rated 15 kW (unity power factor) runs at 0.75 of full load, with core loss 100 W and full-load copper loss 600 W. What's its efficiency?
Check
A regulator covers ±10% in 16 equal steps. What's one step?
Check
A 100 kVA transformer has 0.2% core loss and 3% copper loss at full load, both relative to its rating.
(a)
At what fraction of full load is it most efficient?
(b)
What efficiency does it reach there, at unity power factor?
(c)
What is the copper loss at that load?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
Winding resistance from a test at 120 V, 4 A, 900 W?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
Approximate regulation: R = 0.008, X = 0.05, pf 0.95 lagging?
Check
Autotransformer rating: 25 kVA winding, 12/13.8 kV?
Write units the way you normally would: 1.5 kVA, 1500 VA and 0.0015 MVA are the same answer.
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10